Levitt, Sam Letter SS ® VSE Project Number: U6045.0020.241 June 11, 2024 Current Energy LLC 305 Wells Street Greenfield, MA 01301 REFERENCE: Levitt, Sam Residence: 69 Lyman Road, Northampton, MA 01060 Current Energy LLC Project: 379 Solar Array Installation To Whom It May Concern: We have reviewed the existing structure at the above referenced site.The purpose of our review was to determine the adequacy of the existing structure to support the proposed installation of solar panels on the roof as shown on the panel layout plan. Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel installation. Design Parameters Code: Massachusetts State Residential Code (780 CMR Chapter 51, 9th Edition (2015 IRC)) Risk Category: II Design wind speed, Vult: 117 mph (3-sec gust) Wind exposure category: C Ground snow load, Pg: 40 psf Flat roof snow load, Pf: 35 psf Existing Roof Structure Roof structure: 2x6 rafters @ 24" o.c. Roofing material: asphalt (composite) shingles Roof slope: 27° Connection to Roof Mounting connection: (1) Ironridge HUG w/(2) screws to framing at max. 48" o.c. (portrait and landscape) along rails • Install (2) rails per row of panels, evenly spaced from panel center • Maximum panel dimension: 74x44 in • Rail cantilever shall not exceed the lesser of 50% of the connection spacing or max cantilever allowed by manufacturer • Connections shall be staggered so as not to overload any existing structural member Conclusions Based upon our review,we conclude that the existing structure is adequate to support the proposed solar panel installation. The glass surface of the solar panels allows for a lower slope factor per ASCE 7,resulting in reduced design snow load on the panels.The gravity loads,and thus the stresses of the structural elements,in the area of the solar array are either decreased or increased by no more than 5%.Therefore,the requirements of Section 807.4 of the 2015 IEBC as referenced in 780 CMR Chapter 34, 9th Edition are met and the structure is permitted to remain unaltered. 651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com ® VSE Project Number: U6045.0020.241 Levitt, Sam Residence 6/11/2024 The solar array will be flush-mounted (no more than 10"above the roof surface)and parallel to the roof surface.Thus,we conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible. The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift), the governing load case.Increases in lateral forces less than 10%are considered acceptable.Thus the existing lateral force resisting system is permitted to remain unaltered. Limitations Installation of the solar panels must be performed in accordance with manufacturer recommendations.All work performed must be in accordance with accepted industry-wide methods and applicable safety standards.The contractor must notify Vector Structural Engineering,LLC should any damage,deterioration or discrepancies between the as-built condition of the structure and the condition described in this letter be found.The use of solar panel support span tables provided by others is allowed only where the building type,site conditions,site-specific design parameters,and solar panel configuration match the description of the span tables.The design of the solar panels,solar racking (mounts,rails,etc.)and electrical engineering is the responsibility of others.Waterproofing around the roof penetrations is the responsibility of others.Vector Structural Engineering assumes no responsibility for improper installation of the solar array.Vector Structural Engineering shall be notified of any changes from the approved layout prior to installation. VECTOR STRUCTURAL ENGINEERING, LLC 06/11/2024 _______________________________________________________ Wells Holmes, S.E. MA License: 54240 - Expires: 06/30/2026 Project Engineer Enclosures WLH/bpp 06/11/2024 651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com JOB NO.:U6045.0020.241 SUBJECT:WIND PRESSURE ® PROJECT:Levitt, Sam Residence Label:Note: Calculations per ASCE 7-10 SITE-SPECIFIC WIND PARAMETERS: Basic Wind Speed [mph]:117 Notes: Exposure Category:C Risk Category:II Importance Factor, I: ADDITIONAL INPUT & CALCULATIONS: Height of Roof, h [ft]:25 (Approximate)Hip? Comp/Cladding Location:No Enclosure Classification: Zone 1 GCp:0.9 Figure 30.4-2B (enter negative pressure coefficients) Zone 2 GCp:1.7 Zone 3 GCp:2.5 α:9.5 Table 26.9-1 zg [ft]:900 Table 26.9-1 Kh:0.95 Table 30.3-1 Kzt:1 Equation 26.8-1 Kd:0.85 Table 26.6-1 Velocity Pressure, qh [psf]:28.2 Equation 30.3-1 GCpi:0 Table 26.11-1 PRESSURES:Equation 30.9-1 Zone 1, p [psf]:25.1 psf (1.0 W, Interior Zones, beyond 'a' from roof edge) Zone 2, p [psf]:46.6 psf (1.0 W, End Zones, within 'a' from roof edge) Zone 3, p [psf]:71.6 psf (1.0 W, Corner Zones, within 'a' from roof corner) (a= 3 ft) Solar Panel Array Gable/Hip Roofs 7° < θ ≤ 27° Enclosed Buildings Components and Cladding Wind Calculations ()()piphGCGCqp−= JOB NO.:U6045.0020.241 SUBJECT:CONNECTION ® PROJECT:Levitt, Sam Residence Calculate Uplift Forces on Connection Pressure (0.6 Dead -0.6 Wind) (psf) Max Trib. Width1 (ft) Max Trib. Area2 (ft2) Max Uplift Force (lbs) Zone 1 13.3 4.0 12.3 164 Zone 2 26.2 4.0 12.3 323 Zone 3 41.2 4.0 12.3 508 Calculate Connection Capacity Roof Connector: Additional Connection Info: Ultimate Capacity3 [lbs/in]:3011 Factor of Safety:3 Qty. of Connectors:1 Prying Coefficient:1 Total Capacity [lbs]:1004 Determine Result Maximum Demand:508 Connection Capacity:1004 Result:Capacity > Demand, Connection is adequate. Notes 1. 'Max Trib. Width' is the width along the rails tributary to the connection. 3. Ultimate capacity values are from manufacturer testing. 4. Install metal roof connector per manufacturer's written instructions with recommended fasteners when indicated. 2. 'Max Trib Area' is the product of the 'Max. Trib Width' and 1/2 the panel width/height perpendicular to the rails. (2) rails per row of panels. Length of panels perpendicular to the rails shall not exceed 74". Ironridge HUG w/(2) screws to framing VECTOR STRUCTURAL ENGINEERS JOB NO.:U6045.0020.241 SUBJECT:GRAVITY LOADS ® PROJECT:Levitt, Sam Residence MP1-MP3 GRAVITY LOADS Roof Pitch: 6.1 :12 ROOF DEAD LOAD (D) Increase due to pitch Material weight [psf] Asphalt (Composite) Shingles 1.12 2.0 1/2" Plywood 1.12 1.0 Framing 1.00 3.0 Insulation 1.00 0.0 1/2" Gypsum Clg.1.12 0.0 M, E & Misc 1.00 0.0 Total Existing Roof DL PV Array DL 1.12 3 DL:1.12 ROOF LIVE LOAD (Lr) Existing Design Roof Live Load [psf]20 ASCE 7-10 Table 4-1 Roof Live Load With PV Array [psf]20 SNOW LOAD (S):w/ Solar Array Roof Slope [x:12]:6.1 Roof Slope [°]:27 Ground Snow Load, pg [psf]:40 ASCE 7-10, Section 7.2 Terrain Category:C ASCE 7-10, Table 7-2 Exposure of Roof:Fully Exposed ASCE 7-10, Table 7-2 Exposure Factor, Ce:0.9 ASCE 7-10, Table 7-2 Thermal Factor, Ct:1.1 ASCE 7-10, Table 7-3 Risk Category:II ASCE 7-10, Table 1.5-1 Importance Factor, Is:1.0 ASCE 7-10, Table 1.5-2 Flat Roof Snow Load, pf [psf]:35 ASCE 7-10, Equation 7.3-1 Minimum Roof Snow Load, pm [psf]:0 ASCE 7-10, Section 7.3.4 Unobstructed Slippery Surface?Yes ASCE 7-10, Section 7.4 Slope Factor Figure:Figure 7-2b ASCE 7-10, Section 7.4 Roof Slope Factor, Cs:0.72 ASCE 7-10, Figure 7-2 Sloped Roof Snow Load, ps [psf]:25 ASCE 7-10, Equation 7.4-1 Design Snow Load, S [psf]:2535 6.1 27 40 C Fully Exposed 0.9 1.1 II 1.0 35 0 No Figure 7-2b 1.00 35 Design material weight [psf] 2.2 1.1 3.0 0.0 0.0 0.0 6.4 3.4 #VALUE! Existing JOB NO.:U6045.0020.241 SUBJECT:LOAD COMPARISON ® PROJECT:Levitt, Sam Residence MP1-MP3 Summary of Loads Existing With PV Array D [psf]6 10 Lr [psf]20 20 S [psf]35 25 Maximum Gravity Loads: Existing With PV Array (D + Lr) / Cd [psf]21 24 ASCE 7-10, Section 2.4.1 (D + S) / Cd [psf]36 30 ASCE 7-10, Section 2.4.1 Maximum Gravity Load [psf]:36 30 Ratio Proposed Loading to Current Loading:84%OK The gravity loads, and thus the stresses of the structural elements, in the area of the solar array are either decreased or increased by no more than 5%. Therefore, the requirements of Section 807.4 of the 2015 IEBC as referenced in 780 CMR Chapter 34, 9th Edition are met and the structure is permitted to remain unaltered. (Cd = Load Duration Factor = 0.9 for D, 1.15 for S, and 1.25 for Lr) VECTOR STRUCTURAL ENGINEERS JOB NO.:U6045.0020.241 SUBJECT:GRAVITY LOADS ® PROJECT:Levitt, Sam Residence MP4 GRAVITY LOADS Roof Pitch: 6.1 :12 ROOF DEAD LOAD (D) Increase due to pitch Material weight [psf] Asphalt (Composite) Shingles 1.12 2.0 1/2" Plywood 1.12 1.0 Framing 1.00 3.0 Insulation 1.00 0.0 1/2" Gypsum Clg.1.12 0.0 M, E & Misc 1.00 0.0 Total Existing Roof DL PV Array DL 1.12 3 DL:1.12 ROOF LIVE LOAD (Lr) Existing Design Roof Live Load [psf]20 ASCE 7-10 Table 4-1 Roof Live Load With PV Array [psf]20 SNOW LOAD (S):w/ Solar Array Roof Slope [x:12]:6.1 Roof Slope [°]:27 Ground Snow Load, pg [psf]:40 ASCE 7-10, Section 7.2 Terrain Category:C ASCE 7-10, Table 7-2 Exposure of Roof:Fully Exposed ASCE 7-10, Table 7-2 Exposure Factor, Ce:0.9 ASCE 7-10, Table 7-2 Thermal Factor, Ct:1.1 ASCE 7-10, Table 7-3 Risk Category:II ASCE 7-10, Table 1.5-1 Importance Factor, Is:1.0 ASCE 7-10, Table 1.5-2 Flat Roof Snow Load, pf [psf]:35 ASCE 7-10, Equation 7.3-1 Minimum Roof Snow Load, pm [psf]:0 ASCE 7-10, Section 7.3.4 Unobstructed Slippery Surface?No ASCE 7-10, Section 7.4 Slope Factor Figure:Figure 7-2b ASCE 7-10, Section 7.4 Roof Slope Factor, Cs:1.00 ASCE 7-10, Figure 7-2 Sloped Roof Snow Load, ps [psf]:35 ASCE 7-10, Equation 7.4-1 Design Snow Load, S [psf]:3535 6.1 27 40 C Fully Exposed 0.9 1.1 II 1.0 35 0 No Figure 7-2b 1.00 35 Design material weight [psf] 2.2 1.1 3.0 0.0 0.0 0.0 6.4 3.4 #VALUE! Existing JOB NO.:U6045.0020.241 SUBJECT:LOAD COMPARISON ® PROJECT:Levitt, Sam Residence MP4 Summary of Loads Existing With PV Array D [psf]6 10 Lr [psf]20 20 S [psf]35 35 Maximum Gravity Loads: Existing With PV Array (D + Lr) / Cd [psf]21 24 ASCE 7-10, Section 2.4.1 (D + S) / Cd [psf]36 39 ASCE 7-10, Section 2.4.1 Maximum Gravity Load [psf]:36 39 Maximum Member Forces: GEOMETRY Span(ft)12.6 (Approximate) Solar Panel Array Start, a (ft)5.8 (Approximate) Solar Panel Array Length, b (ft)5.5 (Approximate) Framing Spacing (ft)2.0 MEMBER FORCES Existing With PV Array Vertical Reaction, V1 (lbs)454 464 OK Vertical Reaction, V2 (lbs)454 476 OK Existing With PV Array Moment @ Center, M (lbs-ft)1433 1498 OK Ratio The gravity loads, and thus the stresses of the structural elements, in the area of the solar array are either decreased or increased by no more than 5%. Therefore, the requirements of Section 807.4 of the 2015 IEBC as referenced in 780 CMR Chapter 34, 9th Edition are met and the structure is permitted to remain unaltered. (Cd = Load Duration Factor = 0.9 for D, 1.15 for S, and 1.25 for Lr) Ratio 105% 102% 105%