Line Diagram Levitt, SamL2 L1 N EGC/ GEC 3 ABC V240 GND N Inverter 1 SOLAREDGE SE7600H-US EGC DC- DC+ DC- DC+ 1 1 EGC DC- DC+ DC- DC+ Typ. Junction Box STRING 2: 1x15 410W PANELS With 1X15 S500B OPTIMIZERS PHOTO VOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN STRING 1: 1x8 410W PANELS With 1X8 S500B OPTIMIZERS 2 2 (E) WIRING TO 120/240V SINGLE PHASE UTILITY SERVICE L L L L N A B EGC/GEC GEC (E) LOADS 200A/2P 60A/2P 3 Main Service Panel PV DISCONNECT 60A, 240 V, NEMA 3R MSP, 200A, 120/240V 1 INVERTER VOLTAGE AND FREQUENCY TRIP SETTINGS Shall Trip Function Required Settings Shall Trip Function Required Settings Voltage (%) Clearing time(s) Frequency (Hz) Clearing Time(s) OV2 1.20 0.16 OF2 62.00 0.16 OV1 1.10 2.00 OF1 61.20 300.00 UV1 0.88 2.00 UF1 58.50 300.00 UV2 0.50 1.10 UF2 56.50 0.16 ROOFTOP GENERAL NOTES ALL CONDUCTORS TO BE COPPER & 600V RATED UNLESS NOTED PV MODULES AND MOUNTING SYSTEM GROUNDING AND BONDING TO BE PERFORMED USING MANUFACTURER'S LISTED COMPONENTS UNLESS OTHERWISE NOTED INSTALLATION SUBJECT TO THE AUTHORITY HAVING JURISDICTION ELECTRICAL DIAGRAM CONFIDENTIAL THE INFORMATION HEREIN CONTAINED SHALL NOT BE DISCLOSED TO OTHERS OUTSIDE OF CURRENT ENERGY LLC, WITHOUT CONSENT OR IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE CURRENT ENERGY LLC SYSTEM Current Energy LLC 305 Wells St. Greenfield, MA 01301 www.currentenergy.pro 413-658-2047 CLIENT Levitt, Sam PROJECT 379 SYSTEM SIZE DC 9.4 UTILITY National Grid DATE REV:BY: ADDRESS 69 Lyman Rd MOUNTING SunModo SYSTEM SIZE AC 7.6 SHEET NUMBER 5/15/2024 1 CTKREZMIEN Northampton, MA 01060 MODULES Q.Cell 410G10 ENERGY STORAGE SYSTEM N/A SHEET SIZE 11" X 17" PHONE 413-530-8868 INVERTER SE HOME EV CHARGER N/A SHEET TITLE BASEMENTNORTH EXTERIOR WALL HOUSE EQUIPMENT SCHEDULE ITEM QTY ITEM DATA A 23 PV MODULE Q.PEAK DUO BLK ML-G10+ 410W A 23 DC OPTIMIZER SLAREDGE S500B B 1 PV INVERTER SOLAREDGE SE7600H-US C 1 PV DISCONNECT NON-FUSED, 3R, VISIBLE BREAK, 240V, 60A MIN. PHASE CONDUCTORS NEUTRAL GROUND TRANSMISSION ID Cu/Al QTY SIZE TYPE QTY SIZE TYPE QTY SIZE TYPE CONDUIT SIZE CONDUIT TYPE 1 Cu 2 #10 PV WIRE 0 N/A 1 #6 BARE FREE AIR NONE 2 Cu 2 #10 THWN-2 0 N/A 1 #8 THWN-2 3 4"EMT 3 Cu 2 #6 THWN-2 1 #8 THWN-2 1 #8 THWN-2 1"EMT BASEMENT BESIDE UTILITY METER BASEMENT