CAPEN BOILER PLANT 2024 Condensing Boilers Start-up Report - SubmittalREVIEWED AND APPROVED FOR SUBMISSION BY CATEGORY# JOB# DATE: Exceptions and Notes: 6 Second Ave. B-G MECHANICAL, INC.SUBMITTAL 060 3000E Brian Redfern Chicopee, MA 01020 Condensing Boilers Start-up Report Spec 23 52 16 Par. 3.4 18 March 2024 CM0482-012 Salas O'Brien CONSTRUCTION MANAGER: Bond Building Smith College North District Capen Energy Plant 25B Henshaw Ave. Northampton, MA 01060 ENGINEER: Page 1 of 16 03/16/2021 BENCHMARK BOILER START-UP FORM Please complete one (1) form for each UNIT at the site and return to AERCO for warranty validation within 30 days of start-up. After completion, e-mail this form to: STARTUP@AERCO.COM. Please insure that the Edge Firmware is updated as the first step in the startup process Form Completed By: Date: Location Installation Site Name: Company: Street Address: Phone #: City, State, Zip: Startup Technician Name: AERCO Sales Rep: Startup Technician is: ATT Technician AMT Technician Non-AERCO Trained Technician UNIT SERIAL #: Equipment Classification Unit Type: BMK750 BMK1000 BMK1500 BMK2000 BMK2500 Number at Site __________ __________ __________ __________ __________ Unit Type: BMK3000 BMK4000 BMK5000N BMK5000 BMK6000 Number at Site __________ __________ __________ __________ __________ Benchmark Models Please go to the section corresponding to the boiler you are starting up, fill in the combustion calibration values from the unit just started, and the Gateway section. Optionally, add any notes you wish to include on the Additional Notes page. Once completed, e-mail this form to: STARTUP@AERCO.COM. Benchmark 750 – Page 2 Benchmark 1000 – Page 4 Benchmark 1500 – Page 6 Benchmark 2000 – Page 7 Benchmark 2500 – Page 8 Benchmark 3000 – Page 9 Benchmark 4000 – Page 10 Benchmark 5000N – Page 11 Benchmark 5000 – Page 12 Benchmark 6000 – Page 13 Gateway – Page 15 Additional Notes – Page 16 NOTE: For proper oxygen (O2) and combustion calibration settings, consult the following manuals: • For all standard (non-Platinum) models, see OMM-0145 (GF-218). • For all PLATINUM models, see OMM-0137 (GF-211). Page 2 of 16 03/16/2021 Benchmark 750 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @80% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @60% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 750 Single-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @80% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @60% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 750 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 3 of 16 03/16/2021 Benchmark 750 Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 4 of 16 03/16/2021 Benchmark 1000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @80% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @60% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 1000 Single-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @80% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @60% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 1000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 5 of 16 03/16/2021 Benchmark 1000 Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 6 of 16 03/16/2021 Benchmark 1500 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 1500 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 1500 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 7 of 16 03/16/2021 Benchmark 2000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 2000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 2000 Single-Fuel and Dual-Fuel Boiler –PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 8 of 16 03/16/2021 Benchmark 2500 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 2500 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @20% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 2500 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @22% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 9 of 16 03/16/2021 Benchmark 3000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @14% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 14% valve position:__________ Benchmark 3000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @85% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @65% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @14% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 14% valve position:__________ Benchmark 3000 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @85% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @65% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 10 of 16 03/16/2021 Benchmark 4000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @23% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 23% valve position:__________ Benchmark 4000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 4000 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 11 of 16 03/16/2021 Benchmark 5000N Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 5000N Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 5000N Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 12 of 16 03/16/2021 Benchmark 5000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 5000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 5000 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 13 of 16 03/16/2021 Benchmark 6000 Single-Fuel – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 6000 Single-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 6000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @85% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @65% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 14 of 16 03/16/2021 Benchmark 6000 Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 15 of 16 03/16/2021 Gateway Configuration Name: Gateway Model: ProtoNode (Serial) Phone Number: ProtoNode (Lon) E-Mail Address: Job Name: Input wiring termination to the Gateway translation device (Check one) • EIA-485 (2 wire) • EIA-485 (4 wire) • EIA-232 Building Automation System (BAS) protocol (Check one) • BacNet: o IP: o MS/TP: • Johnson Controls - N2: • LonWorks: • Modbus - IP: What Baud Rate. (Check One): • 156,000 • 19,200 • 76,800 • 9,600 • 38,400 • Other BAS Device Address #’s N2 Device Node ID _____________ OR: BACnet Device Instance #’s BACnet Network Number ___________ BACnet IP Address _________________ OR: LonWorks Program ID Page 16 of 16 03/16/2021 ADDITIONAL NOTES: Page 1 of 16 03/16/2021 BENCHMARK BOILER START-UP FORM Please complete one (1) form for each UNIT at the site and return to AERCO for warranty validation within 30 days of start-up. After completion, e-mail this form to: STARTUP@AERCO.COM. Please insure that the Edge Firmware is updated as the first step in the startup process Form Completed By: Date: Location Installation Site Name: Company: Street Address: Phone #: City, State, Zip: Startup Technician Name: AERCO Sales Rep: Startup Technician is: ATT Technician AMT Technician Non-AERCO Trained Technician UNIT SERIAL #: Equipment Classification Unit Type: BMK750 BMK1000 BMK1500 BMK2000 BMK2500 Number at Site __________ __________ __________ __________ __________ Unit Type: BMK3000 BMK4000 BMK5000N BMK5000 BMK6000 Number at Site __________ __________ __________ __________ __________ Benchmark Models Please go to the section corresponding to the boiler you are starting up, fill in the combustion calibration values from the unit just started, and the Gateway section. Optionally, add any notes you wish to include on the Additional Notes page. Once completed, e-mail this form to: STARTUP@AERCO.COM. Benchmark 750 – Page 2 Benchmark 1000 – Page 4 Benchmark 1500 – Page 6 Benchmark 2000 – Page 7 Benchmark 2500 – Page 8 Benchmark 3000 – Page 9 Benchmark 4000 – Page 10 Benchmark 5000N – Page 11 Benchmark 5000 – Page 12 Benchmark 6000 – Page 13 Gateway – Page 15 Additional Notes – Page 16 NOTE: For proper oxygen (O2) and combustion calibration settings, consult the following manuals: • For all standard (non-Platinum) models, see OMM-0145 (GF-218). • For all PLATINUM models, see OMM-0137 (GF-211). Page 2 of 16 03/16/2021 Benchmark 750 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @80% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @60% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 750 Single-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @80% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @60% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 750 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 3 of 16 03/16/2021 Benchmark 750 Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 4 of 16 03/16/2021 Benchmark 1000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @80% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @60% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 1000 Single-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @80% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @60% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 1000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 5 of 16 03/16/2021 Benchmark 1000 Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 6 of 16 03/16/2021 Benchmark 1500 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 1500 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 1500 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 7 of 16 03/16/2021 Benchmark 2000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 2000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 2000 Single-Fuel and Dual-Fuel Boiler –PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 8 of 16 03/16/2021 Benchmark 2500 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 2500 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @20% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 2500 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @22% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 9 of 16 03/16/2021 Benchmark 3000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @14% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 14% valve position:__________ Benchmark 3000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @85% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @65% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @14% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 14% valve position:__________ Benchmark 3000 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @85% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @65% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 10 of 16 03/16/2021 Benchmark 4000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @23% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 23% valve position:__________ Benchmark 4000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 4000 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 11 of 16 03/16/2021 Benchmark 5000N Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 5000N Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 5000N Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 12 of 16 03/16/2021 Benchmark 5000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 5000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 5000 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 13 of 16 03/16/2021 Benchmark 6000 Single-Fuel – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 6000 Single-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 6000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @85% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @65% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 14 of 16 03/16/2021 Benchmark 6000 Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 15 of 16 03/16/2021 Gateway Configuration Name: Gateway Model: ProtoNode (Serial) Phone Number: ProtoNode (Lon) E-Mail Address: Job Name: Input wiring termination to the Gateway translation device (Check one) • EIA-485 (2 wire) • EIA-485 (4 wire) • EIA-232 Building Automation System (BAS) protocol (Check one) • BacNet: o IP: o MS/TP: • Johnson Controls - N2: • LonWorks: • Modbus - IP: What Baud Rate. (Check One): • 156,000 • 19,200 • 76,800 • 9,600 • 38,400 • Other BAS Device Address #’s N2 Device Node ID _____________ OR: BACnet Device Instance #’s BACnet Network Number ___________ BACnet IP Address _________________ OR: LonWorks Program ID Page 16 of 16 03/16/2021 ADDITIONAL NOTES: Page 1 of 16 03/16/2021 BENCHMARK BOILER START-UP FORM Please complete one (1) form for each UNIT at the site and return to AERCO for warranty validation within 30 days of start-up. After completion, e-mail this form to: STARTUP@AERCO.COM. Please insure that the Edge Firmware is updated as the first step in the startup process Form Completed By: Date: Location Installation Site Name: Company: Street Address: Phone #: City, State, Zip: Startup Technician Name: AERCO Sales Rep: Startup Technician is: ATT Technician AMT Technician Non-AERCO Trained Technician UNIT SERIAL #: Equipment Classification Unit Type: BMK750 BMK1000 BMK1500 BMK2000 BMK2500 Number at Site __________ __________ __________ __________ __________ Unit Type: BMK3000 BMK4000 BMK5000N BMK5000 BMK6000 Number at Site __________ __________ __________ __________ __________ Benchmark Models Please go to the section corresponding to the boiler you are starting up, fill in the combustion calibration values from the unit just started, and the Gateway section. Optionally, add any notes you wish to include on the Additional Notes page. Once completed, e-mail this form to: STARTUP@AERCO.COM. Benchmark 750 – Page 2 Benchmark 1000 – Page 4 Benchmark 1500 – Page 6 Benchmark 2000 – Page 7 Benchmark 2500 – Page 8 Benchmark 3000 – Page 9 Benchmark 4000 – Page 10 Benchmark 5000N – Page 11 Benchmark 5000 – Page 12 Benchmark 6000 – Page 13 Gateway – Page 15 Additional Notes – Page 16 NOTE: For proper oxygen (O2) and combustion calibration settings, consult the following manuals: • For all standard (non-Platinum) models, see OMM-0145 (GF-218). • For all PLATINUM models, see OMM-0137 (GF-211). Page 2 of 16 03/16/2021 Benchmark 750 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @80% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @60% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 750 Single-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @80% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @60% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 750 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 3 of 16 03/16/2021 Benchmark 750 Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 4 of 16 03/16/2021 Benchmark 1000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @80% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @60% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 1000 Single-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @80% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @60% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 1000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 5 of 16 03/16/2021 Benchmark 1000 Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 6 of 16 03/16/2021 Benchmark 1500 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 1500 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 1500 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 7 of 16 03/16/2021 Benchmark 2000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 2000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 2000 Single-Fuel and Dual-Fuel Boiler –PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 8 of 16 03/16/2021 Benchmark 2500 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 2500 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @20% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @16% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 16% valve position:__________ Benchmark 2500 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @22% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 9 of 16 03/16/2021 Benchmark 3000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @14% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 14% valve position:__________ Benchmark 3000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @85% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @65% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @14% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 14% valve position:__________ Benchmark 3000 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @85% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @65% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 10 of 16 03/16/2021 Benchmark 4000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @23% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 23% valve position:__________ Benchmark 4000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 4000 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 11 of 16 03/16/2021 Benchmark 5000N Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 5000N Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 5000N Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 12 of 16 03/16/2021 Benchmark 5000 Single-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 5000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 5000 Single-Fuel and Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 13 of 16 03/16/2021 Benchmark 6000 Single-Fuel – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 6000 Single-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Benchmark 6000 Dual-Fuel Boiler – NATURAL GAS Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @85% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @65% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @45% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 14 of 16 03/16/2021 Benchmark 6000 Dual-Fuel Boiler – PROPANE Combustion air temperature during calibration °F Gas Pressure downstream of the SSOV at 100% valve position ________ inches W.C. Valve Position O2 CO NOx Drive Voltage To Blower Supply Gas Pressure Manifold Gas Pressure @100% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @70% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @50% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @40% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @30% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. @18% ______ % ______ ppm ______ ppm ______ Vdc _____ in. W.C. _____ in. W.C. Vacuum at Blower Proof Switch at 18% valve position:__________ Page 15 of 16 03/16/2021 Gateway Configuration Name: Gateway Model: ProtoNode (Serial) Phone Number: ProtoNode (Lon) E-Mail Address: Job Name: Input wiring termination to the Gateway translation device (Check one) • EIA-485 (2 wire) • EIA-485 (4 wire) • EIA-232 Building Automation System (BAS) protocol (Check one) • BacNet: o IP: o MS/TP: • Johnson Controls - N2: • LonWorks: • Modbus - IP: What Baud Rate. (Check One): • 156,000 • 19,200 • 76,800 • 9,600 • 38,400 • Other BAS Device Address #’s N2 Device Node ID _____________ OR: BACnet Device Instance #’s BACnet Network Number ___________ BACnet IP Address _________________ OR: LonWorks Program ID Page 16 of 16 03/16/2021 ADDITIONAL NOTES: DBTech Service Remit Payments To: Emerson Swan P.O. Box 783 Randolph MA 02368 (781) 986-2555 LICENSE CUSTOMER B-G Mechanical Contractors 38375 #6 Second Ave. Chicopee MA 01020 QTY DESCRIPTION RATE TOTAL 10.00 AERCO LABOR CHARGE 0.00 0.00 APPROVAL I have the authority to order the work as outlined above. It is agreed that DBTech Service ("the seller") will retain title to any equipment or material that may be furnished until final payment is made, and if settlement is not made as agreed, the seller shall have the right to remove same and the seller will be held harmless for any damages resulting from the removal thereof. Date:Mar 04 2024 Service At:25B HENSHAW AVENUE NORTHAMPTON, MA 01060 OPEN Service Call #MM-87324 Tech Mike McGinty Order# / Name 2419453/344132 WARRANTY SERVICE REQUESTED Time Requested:7:00am (looking for startup week of March 4th or March 11th) Service Start-up Sales Order/Purchase Order Number 2419453/344132 Sold To Name B-G MECHANICAL CONTRACTORS continued on next page WORK PERFORMED/RECOMMENDATIONS Worked with ; Jason and Brian of Automated Logic Joe , GC coordinator. Dillon and Brian of BG Mechanical Joe , commissioning continued on next page Date Completed Mar 04 2024 PAYMENT/TERMS Net 30 Remit Payments To: Emerson Swan P.O. Box 783 Randolph, MA 02368 Include service call # on payment DBTech Service Remit Payments To: Emerson Swan P.O. Box 783 Randolph MA 02368 (781) 986-2555 LICENSE Date:Mar 04 2024 Service At:25B HENSHAW AVENUE NORTHAMPTON, MA 01060 OPEN Service Call #MM-87324 Tech Mike McGinty Order# / Name 2419453/344132 WARRANTY This section left intentionally blank SERVICE REQUESTED - Continued Job Name SMITH COLLEGE NORTH DISTRICT CAPEN BOILER PLANT Job Site Address 25B HENSHAW AVENUE NORTHAMPTON, MA 01060 Site Contact Name DILLON LAGOY Site Contact Phone +14134271567 Site Contact Email dillon.lagoy@bgmechanical.com Emerson Swan Salesman Name JASON BESSETTE Originator Email tmacdonald@emersonswan.com Additional Notification Email jbessette@emersonswan.com Reported Problems/Instructions STARTUP OF (3) BMK6000 BOILERS Product Line AERCO Model Number BMK6000 Quantity 3 WORK PERFORMED/RECOMMENDATIONS - Continued agent Jeff, CSL owners rep Chuck, Smith College mechanical staff DBTech Service Remit Payments To: Emerson Swan P.O. Box 783 Randolph MA 02368 (781) 986-2555 LICENSE Date:Mar 04 2024 Service At:25B HENSHAW AVENUE NORTHAMPTON, MA 01060 OPEN Service Call #MM-87324 Tech Mike McGinty Order# / Name 2419453/344132 WARRANTY This section left intentionally blank WORK PERFORMED/RECOMMENDATIONS - Continued Larry , Northampton Gas inspector Tested shunt trip emergency switch for the 3 boilers. All three boilers shutoff. Boiler 2 shunt trip contacter is noisy and will be replaced . Setup boiler BSt and modbus communication . Automated Logic was able to communicate with manager AERCO benchmark platinum Bacnet MSTP connection . Address is 2 , device instance 2525102, and baud of 76800. Tested 4-20 ma signal with temperature range of 100-180F . System supply and return header sensor read good. There are no boiler disconnect switches within sight of boilers . Used the 20 amp 460 vac circuit breaker in panel board outside mechanical room . Also used boilers circuit breaker behind two covers of boiler to shutdown power . Had an issue with boiler 1 blower fan . It was purging at a very high speed . Eventually found the blower fan purge setting set at 6.8 vdc where the other 2 were set at 4.8 vdc . Will test blower fan more tomorrow because it still sound like it’s has a vibration issue . Gas pressure to each boiler, after gas regulator is between 38 to 46”wc . Boiler 3 internal boiler gas fitting had a crack in it . Boiler 1 and 2 had small gas leaks on internal gas fittings that connect to natural gas SSOV . BG Mechanical fixed all gas leaks and thoroughly checked for gas leaks after fixes . All good . Started all three boilers and tested the safeties to get ready for state gas inspector . All safeties tested DBTech Service Remit Payments To: Emerson Swan P.O. Box 783 Randolph MA 02368 (781) 986-2555 LICENSE Date:Mar 04 2024 Service At:25B HENSHAW AVENUE NORTHAMPTON, MA 01060 OPEN Service Call #MM-87324 Tech Mike McGinty Order# / Name 2419453/344132 WARRANTY This section left intentionally blank WORK PERFORMED/RECOMMENDATIONS - Continued good . Boiler 2 exhaust temp sensor needs to be replaced . Ticket # 47986 Exhaust temp sensor part # 61051 DBTech Service Remit Payments To: Emerson Swan P.O. Box 783 Randolph MA 02368 (781) 986-2555 LICENSE CUSTOMER B-G Mechanical Contractors 38375 #6 Second Ave. Chicopee MA 01020 QTY DESCRIPTION RATE TOTAL 8.00 AERCO LABOR CHARGE 0.00 0.00 APPROVAL I have the authority to order the work as outlined above. It is agreed that DBTech Service ("the seller") will retain title to any equipment or material that may be furnished until final payment is made, and if settlement is not made as agreed, the seller shall have the right to remove same and the seller will be held harmless for any damages resulting from the removal thereof. Date:Mar 05 2024 Service At:25B HENSHAW AVENUE NORTHAMPTON, MA 01060 OPEN Service Call #MM-87325 Tech Mike McGinty Order# / Name 2419453/344132 CONTRACT SERVICE REQUESTED Time Requested:7:00am (looking for startup week of March 4th or March 11th.) Service Start-up Sales Order/Purchase Order Number 2419453/344132 Sold To Name continued on next page WORK PERFORMED/RECOMMENDATIONS Tested gas pressures and combustion numbers of the three boilers . All good. Dillon of BG mechanical ran hoses out to drain hot water and add cold water to system because there was very little heat load available . The boilers aren’t installed on pads because of ceiling height issues . continued on next page Date Completed Mar 05 2024 PAYMENT/TERMS Net 30 Remit Payments To: Emerson Swan P.O. Box 783 Randolph, MA 02368 Include service call # on payment DBTech Service Remit Payments To: Emerson Swan P.O. Box 783 Randolph MA 02368 (781) 986-2555 LICENSE Date:Mar 05 2024 Service At:25B HENSHAW AVENUE NORTHAMPTON, MA 01060 OPEN Service Call #MM-87325 Tech Mike McGinty Order# / Name 2419453/344132 CONTRACT This section left intentionally blank SERVICE REQUESTED - Continued B-G MECHANICAL CONTRACTORS Job Name SMITH COLLEGE NORTH DISTRICT CAPEN BOILER PLANT Job Site Address 25B HENSHAW AVENUE NORTHAMPTON, MA 01060 Site Contact Name DILLON LAGOY Site Contact Phone +14134271567 Site Contact Email dillon.lagoy@bgmechanical.com Emerson Swan Salesman Name JASON BESSETTE Originator Email tmacdonald@emersonswan.com Additional Notification Email jbessette@emersonswan.com Reported Problems/Instructions Day2 meet inspector Product Line AERCO Model Number BMK6000 Quantity 3 WORK PERFORMED/RECOMMENDATIONS - Continued Jeff, state gas inspecter , and I tested all three boiler safeties . Jeff was satisfied with all testing . Boiler 1 blower fan DBTech Service Remit Payments To: Emerson Swan P.O. Box 783 Randolph MA 02368 (781) 986-2555 LICENSE Date:Mar 05 2024 Service At:25B HENSHAW AVENUE NORTHAMPTON, MA 01060 OPEN Service Call #MM-87325 Tech Mike McGinty Order# / Name 2419453/344132 CONTRACT This section left intentionally blank WORK PERFORMED/RECOMMENDATIONS - Continued worked good through the whole combustion testing process. Tested all three isolation valves and end switch operation while testing the AERCO BST ( boiler sequencing technology ) . Went over the boiler sequencing and BMS relays and isolation valve wiring with Brian and Jason of Automated Logic . Nate , control electrician , wired the controls. Each boiler has a RIB relay contact wired to each boilers remote interlock . That relay contact is opened if the system water temp rises above 132F . The RIBrelay on the manager boiler is programmed for the high temp shutdown and AERCO boiler system enable per BMS. The isolation valve end switch , on each boiler , is wired to relays in the BMS control panel in boiler mechanical room . Off each boilers end switch relay is two contacts . One contact is wired to its boilers delayed interlock . The other contact is wired to BMS digital input . The mechanical engineer designed the geo thermal heat pump system to be the primary heat source for the multiple buildings , I was told a total of 12 eventually . The geo system is to maintain 130F and if the geo system can’t handle load and system temp drops below 128F the BMS enables the AERCO boiler system . We talked about keeping the boiler system on all the time , at a setpoint of 128For so and the geo set at 132 F or so . By keeping the boiler system on , as apposed cycling the AERCO boiler system off a relay , will keep the boiler PID control loop modulating boilers without shutting boiler system down on a relay which resets the boilers system PID loop . Boilers 2 and 3 were cycling on system setpoint . Boiler 1 is in exhaust temp alarm . Replacement sensor was ordered. When I left , the AERCO boilers were running while Automated Controls were finishing testing their system points . BG Mechanical to shutdown DBTech Service Remit Payments To: Emerson Swan P.O. Box 783 Randolph MA 02368 (781) 986-2555 LICENSE Date:Mar 05 2024 Service At:25B HENSHAW AVENUE NORTHAMPTON, MA 01060 OPEN Service Call #MM-87325 Tech Mike McGinty Order# / Name 2419453/344132 CONTRACT This section left intentionally blank WORK PERFORMED/RECOMMENDATIONS - Continued system until they start tying into building systems . We talk