Ryan, Julia Planset 76 North Meadowbrook Drive Scott E. Wyssling, PE Alpine, UT 84004 Coleman D. Larsen, SE, PE office (201) 874-3483 Gregory T. Elvestad, PE swyssling@wysslingconsulting.com February 27, 2024 Greenlancer Energy Inc. 500 Woodward Avenue, Suite 2125 Detroit, MI 48226 Re: Engineering Services Ryan Residence 985 Florence Road, Northampton, MA 10.920 kW System To Whom It May Concern: We have received information regarding solar panel installation on the roof of the above referenced structure. Our evaluation of the structure is to verify the existing capacity of the roof system and its ability to support the additional loads imposed by the proposed solar system. A. Site Assessment Information 1. Site visit documentation identifying attic information including size and spacing of framing for the existing roof structure. 2. Design drawings of the proposed system including a site plan, roof plan and connection details for the solar panels. This information will be utilized for approval and construction of the proposed system. B. Description of Structure: Roof Framing: 2x6 dimensional lumber at 24” on center with knee wall. (Main house) Roof Framing: Flat 2x4 purlins at 24” on center supported by prefabricated 2x6 top chord trusses at 4’-0” on center. Roof Material: Composite Asphalt Shingles & Metal Roofing Roof Slope: 47 and 21 degrees Attic Access: Accessible Foundation: Permanent C. Loading Criteria Used • Dead Load o Existing Roofing and framing = 7 psf o New Solar Panels and Racking = 3 psf o TOTAL = 10 PSF • Dead Load o Existing Roofing and framing = 7 psf o New Solar Panels and Racking = 3 psf o TOTAL = 10 psf • Live Load = 20 psf (reducible) – 0 psf at locations of solar panels • Ground Snow Load = 40 psf • Wind Load based on ASCE 7-10 o Ultimate Wind Speed = 117 mph (based on Risk Category II) o Exposure Category C Analysis performed of the existing roof structure utilizing the above loading criteria is in accordance with the 2015 IRC, including provisions allowing existing structures to not require strengthening if the new loads do not exceed existing design loads by 105% for gravity elements and 110% for seismic elements. This analysis indicates that the existing framing will support the additional panel loading without damage, if installed correctly. Page 2 of 2 D. Solar Panel Anchorage 1. Composite Asphalt Shingles i. The solar panels shall be mounted in accordance with the most recent Ironridge installation manual. If during solar panel installation, the roof framing members appear unstable or deflect non-uniformly, our office should be notified before proceeding with the installation. ii. The maximum allowable withdrawal force for a 5/16” lag screw is 229 lbs per inch of penetration as identified in the National Design Standards (NDS) of timber construction specifications. Based on a minimum penetration depth of 2½”, the allowable capacity per connection is greater than the design withdrawal force (demand). Considering the variable factors for the existing roof framing and installation tolerances, the connection using one 5/16” diameter lag screw with a minimum of 2½” embedment will be adequate and will include a sufficient factor of safety. iii. Considering the wind speed, roof slopes, size and spacing of framing members, and condition of the roof, the panel supports shall be placed no greater than 48” on center. 2. Metal Roofing i. The solar panels shall be mounted in accordance with the most recent EcoFasten Solar Installation manual. If during solar panel installation, the roof framing members appear unstable or deflect non-uniformly, our office should be notified before proceedin g with the installation. ii. System will be attached to the metal roofing material utilizing the patented EcoFasten Solar Connection. Installation of the connections shall be in accordance with the manufacturer’s recommendations. iii. Considering the wind speed, roof slopes, size and spacing of framing members, and condition of the roof, the panel supports shall be placed no greater than 48” on center. Based on the above evaluation, this office certifies that with the racking and mounting specified, the existing roof system will adequately support the additional loading imposed by the solar system. This evaluation is in conformance with the 2015 IRC, current industry standards, and is based on information supplied to us at the time of this report. Should you have any questions regarding the above or if you require further information do not hesitate to contact me. Very truly yours, Scott E. Wyssling, PE MA License No. 50507 Massachusetts COA # 001629764 GENERAL NOTES1.1.1PROJECT NOTES:1.1.2THISPHOTOVOLTAIC(PV)SYSTEMSHALLCOMPLYWITHTHENATIONALELECTRICCODE(NEC)ARTICLE690,ALLMANUFACTURERS’SLISTINGANDINSTALLATIONINSTRUCTIONS,ANDTHERELEVANTCODESASSPECIFIEDBYTHEAUTHORITYHAVING JURISDICTION’S (AHJ) APPLICABLE CODES.1.1.3THEUTILITYINTERCONNECTIONAPPLICATIONMUSTBEAPPROVEDANDPVSYSTEMINSPECTED PRIOR TO PARALLEL OPERATION1.1.4ALLPVSYSTEMCOMPONENTS;MODULES,UTILITY-INTERACTIVEINVERTERS,ANDSOURCECIRCUITCOMBINERBOXESAREIDENTIFIEDANDLISTEDFORUSEINPHOTOVOLTAICSYSTEMSASREQUIREDBYNEC690.4:PVMODULES:UL1703,IEC61730,ANDIEC61215,ANDNFPA70CLASSCFIREINVERTERS:UL1741CERTIFIED,IEEE 1547, 929, 519 COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY1.1.5MAXDCVOLTAGECALCULATEDUSINGMANUFACTURERPROVIDEDTEMPCOEFFICIENTFORVOC.IFUNAVAILABLE,MAXDCVOLTAGECALCULATEDACCORDING TO NEC 690.7.1.1.6ALLINVERTERS,PHOTOVOLTAICMODULES,PHOTOVOLTAICPANELS,ANDSOURCECIRCUITCOMBINERSINTENDEDFORUSEINAPHOTOVOLTAICPOWERSYSTEMWILLBEIDENTIFIEDANDLISTEDFORTHEAPPLICATIONPER690.4(D).SHALLBEINSTALLEDACCORDINGTOANYINSTRUCTIONSFROMLISTINGORLABELING[NEC110.3].1.1.7ALLSIGNAGETOBEPLACEDINACCORDANCEWITHLOCALBUILDINGCODE.IFEXPOSEDTOSUNLIGHT,ITSHALLBEUVRESISTANT.ALLPLAQUESANDSIGNAGEWILL BE INSTALLED AS REQUIRED BY THE NEC AND AHJ.1.2.1 SCOPE OF WORK:1.2.2PRIMECONTRACTORISRESPONSIBLEFORTHEDESIGNANDSPECIFICATIONSOFTHEGRID-TIEDPHOTOVOLTAICSYSTEMRETROFIT.PRIMECONTRACTORWILLBERESPONSIBLEFORCOLLECTINGEXISTINGONSITEREQUIREMENTSTODESIGN,SPECIFY,ANDINSTALLTHEEXTERIORROOF-MOUNTEDPORTIONOFTHEPHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT.1.3.1 WORK INCLUDES:1.3.2PV ROOF ATTACHMENTS - IRONRIDGE FLASH VUE, ECOFASTEN CORRUSLIDE1.3.3PV RACKING SYSTEM INSTALLATION - IRONRIDGE AIRE RAIL A21.3.4PVMODULEANDINVERTERINSTALLATION-RECSOLARREC420AAPURE-R/TESLASOLAR INVERTER 7.6 KW (240V)1.3.5PV EQUIPMENT GROUNDING1.3.6PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX1.3.7PV LOAD CENTERS (IF INCLUDED)1.3.8PV METERING/MONITORING (IF INCLUDED)1.3.9PV DISCONNECTS1.3.10PV FINAL COMMISSIONING1.3.11(E) ELECTRICAL EQUIPMENT RETROFIT FOR PV1.3.12SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE*NEC2020ISCOPE OF WORKSYSTEM SIZE:STC: 26 X 420W = 10.920KWPTC: 26 X 397.9W = 10.345KW(26) REC SOLAR REC420AA PURE-R(1) TESLA SOLAR INVERTER 7.6 KWATTACHMENT TYPE: IRONRIDGE FLASH VUE,ECOFASTEN CORRUSLIDEMSP UPGRADE: NOPROJECT INFORMATION:-SERVICE PHASE: SINGLE-SERVICE SIZE (AMPS): 200A-DISTANCE FROM UTILITY METER TO TRANSFORMER: 70 FT-CONNECTIVITY TYPE: OVERHEAD-UTILITY METER NUMBER: # 16356905SCOPE OF WORK-INVERTER: (1) TESLA SOLAR INVERTER 7.6 KW(240)-PANELS: (26) REC SOLAR REC420AA PURE-R-DC-STC RATING OF SYSTEM: 10.920 KWP-AC SYSTEM DESIGN CAPACITY (NOMINAL): 7.600 KWP-AC SYSTEM DESIGN CAPACITY (MAXIMUM): 7.600 KWPOWNERNAME:JULIA RYANPROJECT MANAGERNAME:PATRICK RONDEAUPHONE: 413-588-8185PROJECT DESIGNEDNAME:TIMOTHY SOBERANOPROJECT SUPERVISEDNAME:JESSE BREKELBAUMCONTRACTORNAME:VALLEY SOLAR LLCPHONE: 413-584-8844AUTHORITIES HAVING JURISDICTIONBUILDING: CITY OF NORTHAMPTONZONING: CITY OF NORTHAMPTONUTILITY: NATIONAL GRIDDESIGN SPECIFICATIONSOCCUPANCY: IICONSTRUCTION: SINGLE-FAMILYZONING:RESIDENTIALGROUND SNOW LOAD: 40 PSFWIND EXPOSURE: CWIND SPEED: 117 MPHAPPLICABLE CODES & STANDARDSBUILDING: MASSACHUSETTS BUILDING CODE, 9TH EDITION, AS AMENDED (780 CMR)RESIDENTIAL:MASSACHUSETTS RESIDENTIONAL BUILDING CODE, 9TH EDITION, ASAMENDED (780 CMR)ELECTRICAL: NEC 2023FIRE:NFPA 1 FIRE CODE - 2021PROJECT INFORMATIONNEW PV SYSTEM: 10.920 kWpJULIA RYAN RESIDENCE985 FLORENCE ROAD NORTHAMPTON, MA 01062ASSESSOR'S #: 44 -048-001BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCET-001.00COVER PAGE(SHEET 1)01AERIAL PHOTONOT TO SCALENEWS02PLAT MAPNOT TO SCALESHEET LIST TABLESHEET NUMBERSHEET TITLET-001COVER PAGEG-001NOTESA-101SITE PLANA-102ELECTRICAL PLANA-103SOLAR ATTACHMENT PLANA-104INSTALLER REFERENCE PAGEE-601LINE DIAGRAME-602DESIGN TABLESE-603PLACARDSS-501ASSEMBLY DETAILSS-502ASSEMBLY DETAILSR-001RESOURCE DOCUMENTR-002RESOURCE DOCUMENTR-003RESOURCE DOCUMENTR-004RESOURCE DOCUMENTR-005RESOURCE DOCUMENTR-006RESOURCE DOCUMENTFLORENCE ROADSigned 2/27/2024 2.1.1SITE NOTES:2.1.2A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.2.1.3THEPVMODULESARECONSIDEREDNON-COMBUSTIBLEANDTHISSYSTEMISAUTILITYINTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.2.1.4THESOLARPVINSTALLATIONWILLNOTOBSTRUCTANYPLUMBING,MECHANICAL,ORBUILDINGROOF VENTS.2.1.5PROPERACCESSANDWORKINGCLEARANCEAROUNDEXISTINGANDPROPOSEDELECTRICALEQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.2.1.6ROOFCOVERINGSSHALLBEDESIGNED,INSTALLED,ANDMAINTAINEDINACCORDANCEWITHTHISCODEANDTHEAPPROVEDMANUFACTURER'SINSTRUCTIONSSUCHTHATTHEROOFCOVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE.2.2.1EQUIPMENT LOCATIONS2.2.2ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.2.2.3WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATINGTEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLE 310.15 (B)(1).2.2.4JUNCTIONANDPULLBOXESPERMITTEDINSTALLEDUNDERPVMODULESACCORDINGTONEC690.34.2.2.5ADDITIONALACDISCONNECT(S)SHALLBEPROVIDEDWHERETHEINVERTERISNOTWITHINSIGHT OF THE AC SERVICING DISCONNECT.2.2.6ALLEQUIPMENTSHALLBEINSTALLEDACCESSIBLETOQUALIFIEDPERSONNELACCORDINGTONEC APPLICABLE CODES.2.2.7ALLCOMPONENTSARELISTEDFORTHEIRPURPOSEANDRATEDFOROUTDOORUSAGEWHENAPPROPRIATE.2.3.1STRUCTURAL NOTES:2.3.2RACKINGSYSTEM&PVARRAYWILLBEINSTALLEDACCORDINGTOCODE-COMPLIANTINSTALLATIONMANUAL.TOPCLAMPSREQUIREADESIGNATEDSPACEBETWEENMODULES,ANDRAILSMUSTALSOEXTENDAMINIMUMDISTANCEBEYONDEITHEREDGEOFTHEARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS.2.3.3JUNCTIONBOXWILLBEINSTALLEDPERMANUFACTURERS'SPECIFICATIONS.IFROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS.2.3.4ROOFTOPPENETRATIONSFORPVRACEWAYWILLBECOMPLETEDANDSEALEDW/APPROVEDCHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR.2.3.5ALLPVRELATEDROOFATTACHMENTSTOBESPACEDNOGREATERTHANTHESPANDISTANCESPECIFIED BY THE RACKING MANUFACTURER.2.3.6WHENPOSSIBLE,ALLPVRELATEDRACKINGATTACHMENTSWILLBESTAGGEREDAMONGSTTHE ROOF FRAMING MEMBERS.2.4.1GROUNDING NOTES:2.4.2GROUNDINGSYSTEMCOMPONENTSSHALLBELISTEDFORTHEIRPURPOSE,ANDGROUNDINGDEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE.2.4.3PV SYSTEMS REQUIRE AN EQUIPMENTGROUNDINGCONDUCTOR.ALLMETALELECTRICALEQUIPMENTANDSTRUCTURALCOMPONENTSBONDEDTOGROUND,INACCORDANCEWITH250.134 OR 250.136(A). ONLY THE DC CONDUCTORS ARE UNGROUNDED.2.4.4PVEQUIPMENTSHALLBEGROUNDEDACCORDINGTONEC690.43ANDMINIMUMNECTABLE250.122.2.4.5METALPARTSOFMODULEFRAMES,MODULERACKING,ANDENCLOSURECONSIDEREDGROUNDED IN ACCORD WITH 250.134 AND 250.136(A).2.4.6EACHMODULEWILLBEGROUNDEDUSINGWEEBGROUNDINGCLIPSASSHOWNINMANUFACTURERDOCUMENTATIONANDAPPROVEDBYTHEAHJ.IFWEEBSARENOTUSED,MODULEGROUNDINGLUGSMUSTBEINSTALLEDATTHESPECIFIEDGROUNDINGLUGHOLESPER THE MANUFACTURERS' INSTALLATION REQUIREMENTS.2.4.7THEGROUNDINGCONNECTIONTOAMODULESHALLBEARRANGEDSUCHTHATTHEREMOVALOF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE.2.4.8GROUNDINGANDBONDINGCONDUCTORS,IFINSULATED,SHALLBECOLOREDGREENORMARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]2.4.9THEGROUNDINGELECTRODESYSTEMCOMPLIESWITHNEC690.47ANDNEC250.50THROUGH250.106.IFEXISTINGSYSTEMISINACCESSIBLE,ORINADEQUATE,AGROUNDINGELECTRODESYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47 AND AHJ.2.4.10DCPVARRAYSSHALLBEPROVIDEDWITHDCGROUND-FAULTPROTECTIONMEETINGTHEREQUIREMENTS OF 690.41(B)(1) THROUGH (3) TO REDUCE FIRE HAZARDS2.5.1INTERCONNECTION NOTES:2.5.2LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 705.12]2.5.3THESUMOF125PERCENTOFTHEPOWERSOURCE(S)OUTPUTCIRCUITCURRENTANDTHERATINGOFTHEOVERCURRENTDEVICEPROTECTINGTHEBUSBARSHALLNOTEXCEED120PERCENTOFTHEAMPACITYOFTHEBUSBAR,PVDEDICATEDBACKFEEDBREAKERSMUSTBELOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(3)(2)].2.5.4ATMULTIPLEELECTRICPOWERSOURCESOUTPUTCOMBINERPANEL,TOTALRATINGOFALLOVERCURRENTDEVICESSHALLNOTEXCEEDAMPACITYOFBUSBAR.HOWEVER,THECOMBINED OVERCURRENT DEVICE MAY BE EXCLUDED ACCORDING TO NEC 705.12 (B)(3)(3).2.5.5FEEDER TAP INTERCONNECTION (LOAD SIDE) ACCORDING TO NEC 705.12 (B)(1) AND (2)2.5.6SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.11 WITH SERVICE ENTRANCECONDUCTORS IN ACCORDANCE WITH NEC 230.422.5.7BACKFEEDINGBREAKERFORELECTRICPOWERSOURCESOUTPUTISEXEMPTFROMADDITIONAL FASTENING [NEC 705.12 (E)].2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:2.6.2DISCONNECTINGSWITCHESSHALLBEWIREDSUCHTHATWHENTHESWITCHISOPENEDTHECONDUCTORSREMAININGENERGIZEDARECONNECTEDTOTHETERMINALSMARKED“LINESIDE” (TYPICALLY THE UPPER TERMINALS).2.6.3DISCONNECTSTOBEACCESSIBLETOQUALIFIEDUTILITYPERSONNEL,BELOCKABLE,ANDBEAVISIBLE-BREAK SWITCH.2.6.4BOTHPOSITIVEANDNEGATIVEPVCONDUCTORSAREUNGROUNDED.THEREFOREBOTHMUSTOPEN WHERE A DISCONNECT IS REQUIRED, ACCORDING TO NEC 690.13.2.6.5ISOLATINGDEVICESOREQUIPMENTDISCONNECTINGMEANSSHALLBEINSTALLEDINCIRCUITSCONNECTEDTOEQUIPMENTATALOCATIONWITHINTHEEQUIPMENT,ORWITHINSIGHTANDWITHIN10FT.OFTHEEQUIPMENT.ANEQUIPMENTDISCONNECTINGMEANSSHALLBEPERMITTEDTOBEREMOTEFROMTHEEQUIPMENTWHERETHEEQUIPMENTDISCONNECTINGMEANSCANBEREMOTELYOPERATEDFROMWITHIN10FT.OFTHEEQUIPMENT,ACCORDINGTO NEC 690.15 (A).2.6.6PVSYSTEMCIRCUITSINSTALLEDONORINBUILDINGSSHALLINCLUDEARAPIDSHUTDOWNFUNCTIONTOREDUCESHOCKHAZARDFOREMERGENCYRESPONDERSINACCORDANCEWITH690.12(A) THROUGH (D)2.6.7ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND 240.2.6.8BOTHPOSITIVEANDNEGATIVEPVCONDUCTORSAREUNGROUNDED,THEREFOREBOTHREQUIREOVER-CURRENTPROTECTION,ACCORDINGTONEC240.21.(SEEEXCEPTIONINNEC690.9)2.6.9IFREQUIREDBYAHJ,SYSTEMWILLINCLUDEARC-FAULTCIRCUITPROTECTIONACCORDINGTONEC 690.11 AND UL1699B.2.7.1WIRING & CONDUIT NOTES:2.7.2ALLCONDUITANDWIREWILLBELISTEDANDAPPROVEDFORTHEIRPURPOSE.CONDUITANDWIRESPECIFICATIONSAREBASEDONMINIMUMCODEREQUIREMENTSANDARENOTMEANTTO LIMIT UP-SIZING.2.7.3ALL CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.2.7.4EXPOSEDPVSOURCECIRCUITSANDOUTPUTCIRCUITSSHALLUSEWIRELISTEDANDIDENTIFIED AS PHOTOVOLTAIC (PV) WIRE [690.31 (C)]. PV MODULES WIRELEADSSHALLBE LISTED FOR USE ON PV ARRAYS, ACCORDING TO NEC 690.31 (A).2.7.5PV WIRE BLACK WIRE MAY BE FIELD-MARKED WHITE [NEC 200.6 (A)(5)].2.7.6MODULE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY.2.7.7ACCORDINGTONEC200.7,UNGROUNDEDSYSTEMSDCCONDUCTORSCOLOREDORMARKEDAS FOLLOWS:DC POSITIVE-RED, OR OTHER COLOR EXCLUDING WHITE, GRAY AND GREENDC NEGATIVE- BLACK, OR OTHER COLOR EXCLUDING WHITE, GRAY AND GREEN2.7.8AC CONDUCTORS COLORED OR MARKED AS FOLLOWS:PHASE A OR L1- BLACKPHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASEPHASE C OR L3- BLUE, YELLOW, ORANGE*, OR OTHER CONVENTIONNEUTRAL- WHITE OR GRAY*IN4-WIREDELTACONNECTEDSYSTEMSTHEPHASEWITHHIGHERVOLTAGETOBEMARKEDORANGE [NEC 110.15].*NEC2020I *NEC2020I BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCEG-001.00NOTES(SHEET 2)Signed 2/27/2024 GENERAL NOTES1.FIELD VERIFY ALL MEASUREMENTS2.ITEMS BELOW MAY NOT BE ON THIS PAGEPROPERTY LINECONDUIT IN TRENCHNEWS01/32" = 1'-0"SITE PLAN0116'32'BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCEA-101.00SITE PLAN(SHEET 3)ENTRANCEAREA OF WORK SOLAR REC METER -CUSTOMER OWNED FLORENCE ROAD METER/MAINAC DISCONNECT109'-10"13'-11"57'-11"50'-10"CONDUIT RUN IN TRENCH 24" DEEP57' LENGTHDC DISCONNECTSigned 2/27/2024 MODULE:REC SOLARREC420AA PURE-R420 WATTS44''68.1''GENERAL NOTES1.FIELD VERIFY ALL MEASUREMENTS2.ITEMS BELOW MAY NOT BE ON THIS PAGEFIRE CLEARANCECONDUIT IN TRENCHBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCENEWS03/32" = 1'-0"ELECTRICAL PLAN015'-4"10'-8"A-102.00ELECTRICAL PLAN(SHEET 4)ARRAY 1 - 5.880 kW[x14] (N) MODULESTILT: 47 DEGREESROOF PITCH: 13:12AZIMUTH: 166 DEGREESBMODULE STRINGINGAMODULE STRINGINGEXTERIOR PV EQUIPMENT(E) (1) METER/MAIN(N) (1) MAIN ELECTRICAL PANELINTERIOR PV EQUIPMENT(N) (1) INVERTER(N) (1) SOLAR REC METER -CUSTOMER OWNED18'' FIRE ACCESS PATHHOUSE:TOTAL ROOF AREA: 2427.67 SQ. FTSOLAR PANELS AREA: 291.32 SQ. FTROOF COVERAGE: 12%.(N) (1) AC DISCONNECTBDARRAY 2 - 5.040 kW[x12] (N) MODULESTILT: 21 DEGREESROOF PITCH: 5:12AZIMUTH: 166 DEGREES18'' FIRE ACCESS PATHDMODULE STRINGINGCMODULE STRINGING(N) (1) JUNCTION BOXGARAGE:TOTAL ROOF AREA: 924.81 SQ. FTSOLAR PANELS AREA: 249.7 SQ. FTROOF COVERAGE: 27%.AAAAAABBBBBBBC36'' FIRE ACCESS PATHDCDCDCDCDCCONDUIT RUN IN TRENCH 24" DEEP57' LENGTH(N) (1) JUNCTION BOX(N) (1) DC DISCONNECTEXTERIOR PV EQUIPMENT GENERAL NOTES1.FIELD VERIFY ALL MEASUREMENTS2.ITEMS BELOW MAY NOT BE ON THIS PAGEMETAL RIBSROOF RAFTERSMODULE:REC SOLARREC420AA PURE-R420 WATTS44''68.1''BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCE03/32" = 1'-0"SOLAR ATTACHMENT PLAN015'-4"10'-8"A-103.00SOLAR ATTACHMENTPLAN(SHEET 5)FLUSH MOUNT SOLAR MODULESATTACHED TO ROOF SURFACE (SEESHEET S-501 FOR MOUNTING DETAILSNEWSROOF MATERIAL ISASPHALT SHINGLEFLUSH MOUNT SOLAR MODULESATTACHED TO ROOF SURFACE (SEESHEET S-502 FOR MOUNTING DETAILSROOF MATERIAL ISCORRUGATED METAL29'-4"22'-0"Signed 2/27/2024 GENERAL NOTES1.FIELD VERIFY ALL MEASUREMENTS2.ITEMS BELOW MAY NOT BE ON THIS PAGEBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCE01STICKER MAPNOT TO SCALEA-104.00(SHEET 6)STICKER MAPSigned 2/27/2024 MAX BREAKER SIZE:(200 A x 1.2 ) - 200 A = 40 AEQUIPMENT LEFTOF LINE IS (N) NEWUNLESS OTHERWISE NOTED.EQUIPMENT RIGHTOF LINE IS (E) EXISTINGUNLESS OTHERWISE NOTED.GROUNDROD(E) GROUNDINGELECTRODEL2L1NL2L1N(N)40A/2PCB1PV SYSTEM EQUIPPED WITH RAPIDSHUTDOWN DISCONNECT PER NEC 690.12SYSTEM COMPLIANT WITH NEC 690.134GSW1(N) AC DISCONNECT60AEATON DG222URB65READILY ACCESSIBLEOPEN BLADE AC SYSTEMDISCONNECT VISIBLE FROMAPPROACH TO RESIDENCE60A 240V LOCATEDEXTERIOR ON WALL NEARMETER NEMA 3RNOTE:TOP LUGS TO SOLARGENERATION BOTTOM LUGSTO UTILITY LOCATEDEXTERIORTO UTILITYGRID (OH)L2NL1(Е) METER/MAIN240/120 V 1Ø, 3WMAIN BUSS: 200A(E)UTILITYMETERGNGNTO (E)LOADSUTILITY METER #:16356905 (N) SOLAR REC METER-CUSTOMER OWNEDVM1TOP LUGSBOTTOM LUGS(Е) MAIN ELECTRICAL PANEL240/120 V 1Ø, 3WMAIN BUSS: 200A(E)MAIN200A(E)MAIN200AL1L2NGG(N) INVERTERTESLA SOLAR INVERTER 7.6 KWRATED POWER 7600WC66(N) JUNCTION BOX12(N) (9) TESLA RAPIDSHUTDOWN DEVICE(N) JUNCTION BOX12DA68B(N) (26) REC SOLARREC420AA PURE-RNOTE:ALL CONSTRUCTION NEEDS TO ABIDE BY THE ESB 750 & ESB 756. INSTALLATIONS CAN NOT INCLUDE ANY KINDOF TAPS, METER COLLARS OR ADAPTERS INSIDE NATIONAL GRID OWNED AND MAINTAINED EQUIPMENT,METER SOCKETS, METER CABINETS OR ANYWHERE THERE ARE UN-METERED CONDUCTORS. ANY NEWMETERING AND DISCONNECT EQUIPMENT WILL NEED TO BE GROUPED, POTENTIALLY LOCATED OUTSIDE AND24/7 LOCKABLE AND ACCESSIBLE, IN ACCORDANCE WITH ESB 7.1.1. ALL EQUIPMENT LOCATIONS WILL NEED TOBE APPROVED BY NATIONAL GRID METERING DEPARTMENT PRIOR TO INSTALLATION.(N) DC DISCONNECT30A3CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONSIDTYPICALCONDUCTORCONDUITCURRENT-CARRYINGCONDUCTORS IN CONDUITOCPDEGCTEMP. CORR.FACTORCONDUIT FILLFACTORCONT.CURRENTMAX.CURRENT(125%)BASE AMP.DERATEDAMP.TERM. TEMP.RATINGAMP. @TERMINALLENGTHVOLTAGE DROP1410 AWG PV WIRE, COPPERFREE AIR2N/A6 AWG BARE, COPPER0.96 (32.7 °C)111.11A13.89A55A41.8A75°C50A2210 AWG THWN-2, COPPER0.75'' DIA EMT8N/A10 AWG THWN-2, COPPER0.96 (32.7 °C)0.711.11A13.89A40A21.28A75°C35A318 AWG THWN-2, COPPER0.75'' DIA PVC-402N/A10 AWG THWN-2, COPPER0.96 (32.7 °C)0.711.11A13.89A40A21.28A75°C50A57FT0.51%418 AWG THWN-2, COPPER0.75'' DIA EMT2N/A10 AWG THWN-2, COPPER0.96 (32.7 °C)132A40A55A52.8A75°C50A518 AWG THWN-2, COPPER0.75'' DIA EMT2N/A10 AWG THWN-2, COPPER0.96 (32.7 °C)132A40A55A52.8A75°C50A618 AWG THWN-2, COPPER0.75'' DIA EMT240A10 AWG THWN-2, COPPER0.96 (32.7 °C)132A40A55A52.8A75°C50AE-601.00LINE DIAGRAM(SHEET 7)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCEAMODULE STRINGINGBMODULE STRINGINGCMODULE STRINGINGDMODULE STRINGING BILL OF MATERIALSCATEGORYMAKEMODEL NUMBERREFQTYUNITQTY/UNITDESCRIPTIONMODULEREC SOLARREC420AA PURE-RPM1-2626PIECES1REC SOLAR REC420AA PURE-R 420W 128 CELLS, MONOCRYSTALLINE SILICONINVERTERTESLA7.6 KWI11PIECE1TESLA SOLAR INVERTER 7.6 KW 7600W INVERTERDISCONNECTEATONDG222URBSW11PIECE1EATON DG222URB, NON FUSED, 2-POLE, 60A, 240VAC OR EQUIVALENTPRODUCTION METERGENERIC MANUFACTURERGEN-METER-80AM11PIECE1ELECTRICAL METER, OWNER APPROVEDWIRINGGEN-10-AWG-PV-WIRE-CUWR1360FEET110 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE)WIRINGGEN-6-AWG-BARE-CUWR1180FEET16 AWG BARE, COPPER (GROUND)WIRINGGEN-10-AWG-THWN-2-CU-RDWR2240FEET110 AWG THWN-2, COPPER, RED (POSITIVE)WIRINGGEN-10-AWG-THWN-2-CU-BLKWR2240FEET110 AWG THWN-2, COPPER, BLACK (NEGATIVE)WIRINGGEN-10-AWG-THWN-2-CU-GRWR2-6150FEET110 AWG THWN-2, COPPER, GREEN (GROUND)WIRINGGEN-8-AWG-THWN-2-CU-RDWR3-690FEET18 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-8-AWG-THWN-2-CU-BLKWR3-690FEET18 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-8-AWG-THWN-2-CU-WHWR3-690FEET18 AWG THWN-2, COPPER, WHITE (NEUTRAL)WIREWAYGEN-EMT-0.75'' DIAWW2, 4-690FEET1EMT CONDUIT, 0.75'' DIAWIREWAYGEN-PVC-40-0.75'' DIAWW360FEET1PVC-40 CONDUIT, 0.75'' DIAOCPDGENERIC MANUFACTURERGEN-CB-40A-240VACCB11PIECE1CIRCUIT BREAKER, 40A, 240VACTRANSITION BOXGENERIC MANUFACTURERGEN-AWB-TB-4-4XJB11PIECE1TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKSSYSTEM SUMMARYINVERTER #1MPPT #1MPPT #2MPPT #3MODULES IN SERIES686ARRAY VMP300V400V300VARRAY IMP8.4A8.4A8.4AARRAY VOC356.4V475.2V356.4VARRAY MAX VOC400.1V533.4V400.1VARRAY ISC8.89A8.89A8.89AARRAY STC POWER10,920WARRAY PTC POWER10,345WMAX AC CURRENT32AMAX AC POWER7,600WDERATED (CEC) AC POWER7,600WDISCONNECTSOCPDSMODULESASHRAE EXTREME LOW-25.9°C (-14.6°F), SOURCE: BARNES MUNI (42.16°; -72.72°)ASHRAE 2% HIGH32.7°C (90.9°F), SOURCE: BARNES MUNI (42.16°; -72.72°)REF.QTY.MAKE AND MODELRATED CURRENTMAX RATED VOLTAGESW11EATON DG222URB OR EQUIV.60A240VACREF.QTY.MAKE AND MODELPMAXPTCISCIMPVOCVMPTEMP. COEFF. OF VOCFUSE RATINGPM1-2626REC SOLAR REC420AA PURE-R420W397.9W8.89A8.4A59.4V50V-0.143V/°C (-0.24%/°C)25AINVERTERSREF.QTY.MAKE AND MODELACVOLTAGEGROUNDOCPDRATINGRATEDPOWERMAX OUTPUTCURRENTMAX INPUTCURRENTMAX INPUTVOLTAGECEC WEIGHTEDEFFICIENCYI11TESLA SOLAR INVERTER 7.6 KW240VFLOATING40A7600W32A4x11A600V97.5%REF.QTY.RATED CURRENTMAX VOLTAGECB1140A240VACMPPT #46300V8.4A356.4V400.1V8.89AE-602.00DESIGN TABLES(SHEET 8)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCE FRONTBACK!CAUTION!POWER TO THIS BUILDING IS ALSO SUPPLIEDFROM ROOF MOUNTED SOLAR ARRAYS WITHSAFETY DISCONNECTS AS SHOWN:NEWSE-603.00PLACARDS(SHEET 9)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCEPV ARRAYELECTRICAL SHOCK HAZARDTERMINALS ON THE LINE ANDLOAD SIDES MAY BE ENERGIZEDIN THE OPEN POSITIONWARNINGLABEL 1AT EACH DISCONNECTING MEANS FORPHOTOVOLTAIC EQUIPMENT (2" X 4").[NEC 690.13].POWER SOURCEOUTPUT CONNECTIONDO NOT RELOCATE THISOVERCURRENT DEVICEWARNINGLABEL 2AT POINT OF INTERCONNECTIONOVERCURRENT DEVICE (2" X 4").[NEC 705.12(B)(3)(2)].LABEL 4AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRINGMETHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERESEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,OR FLOORS (5 3/4" X 1 1/8").[NEC 690.31(G)]RAPID SHUTDOWNSWITCH FORSOLAR PV SYSTEMLABEL 5AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2").[NEC 690.56(C)(3)].LABEL 9AT EACH AC DISCONNECTING MEANS(4" X 1").[NEC 690.13(B)].LABEL 10AT EACH DC DISCONNECTING MEANS(4" X 1").[NEC 690.13(B)].SOLAR PV SYSTEMEQUIPPED WITHRAPID SHUTDOWNTURN RAPID SHUTDOWN SWITCH TOTHE "OFF" POSITION TO SHUT DOWNPV SYSTEM AND REDUCE SHOCKHAZARD IN ARRAYSOLAR ELECTRICPV PANELSLABEL 3AT RAPID SHUTDOWN SYSTEM(3 3/4" X 5 1/4"). [NEC 690.56(C)(1)(A)].LABELING NOTES1.1 LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRICAL CODE,INTERNATIONAL FIRE CODE 608.12, OSHA STANDARD 1910.145, ANSI Z5351.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVINGJURISDICTION.1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENTINVOLVED.1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE REDBACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVEYELLOW BACKGROUND. [ANSI Z535]1.6 ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHERRESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN PER NEC 110.21(B)INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTEDPHOTOVOLTAIC SYSTEM DISCONNECT LOCATEDNW SIDE OF THE HOUSEDIRECTORYPERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICEDISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTINGMEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8").[NEC 690.56(B)]WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, ADIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PVSYSTEM DISCONNECTING MEANS.PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED INBATHROOMS[NEC 690.4(D),(E)]CAUTIONMULTIPLE SOURCES OF POWERLABEL 6AT UTILITY METER (5 3/4" X 1 1/8")[NEC 690.56(B)]WARNINGDUAL POWER SUPPLYSOURCES: UTILITY GRIDAND PV SOLARELECTRIC SYSTEMLABEL 7AT POINT OF INTERCONNECTION(2 3/4" X 1 5/8").[NEC 705.12(B)(3)]WARNINGSOLAR ELECTRICCIRCUIT BREAKERIS BACKFEDLABEL 8AT POINT OFINTERCONNECTION(2" X 1").[NEC 705.12(B)(3)]PHOTOVOLTAIC SOLARDC DISCONNECTPHOTOVOLTAIC POWER SOURCELABEL 11AT POINT OF INTERCONNECTION, MARKEDAT DISCONNECTING MEANS (4" X 2").[NEC 690.54]AC DISCONNECTPHOTOVOLTAIC SYSTEMPOWER SOURCERATED ACOUTPUT CURRENTNOMINAL OPERATINGAC VOLTAGEAMPSVOLTS32240LABEL 12AT EACH DC DISCONNECTINGMEANS (3" X 4").[NEC 690.53].MAXIMUM VOLTAGEMAX CIRCUIT CURRENTVDCAMPSDIRECT CURRENTPHOTOVOLTAIC POWER SOURCE8.89533.4MAIN DISTRIBUTIONUTILITY DISCONNECT (INSIDE)UTILITY METERPV AC DISCONNECTPV METER(CUSTOMER OWNED)PV ARRAYMAIN DISTRIBUTIONUTILITY DISCONNECTINVERTER (INSIDE)FLORENCE ROADNOTE:DIRECTORY STICKER WILL BE PRINTEDIN RED AND WHITEPHOTOVOLTAIC SOLARAC DISCONNECTPHOTOVOLTAIC SOLARAC DISCONNECT SHEET KEYNOTES1.ROOF MATERIAL: ASPHALT SHINGLE2.ROOF STRUCTURE: SINGLE SPAN RAFTER3.ATTACHMENT TYPE: IRONRIDGE FLASHVUE4.MODULE MANUFACTURER: REC SOLAR5.MODULE MODEL: REC420AA PURE-R6.MODULE LENGTH: 68.1 IN.7.MODULE WIDTH: 44 IN.8.MODULE WEIGHT: 47.4 LBS.9.SEE SHEET A-103 FOR DIMENSION(S)10.MIN. FIRE OFFSET: 18" FROM RIDGE, 36" FROM EDGE11.RAFTER SPACING: 24 IN. O.C.12.RAFTER SIZE: 2X6 IN.13.LAG BOLT DIAMETER: BOLT/SCREW SUPPLIED WITHRACKING.14.LAG BOLT EMBEDMENT: 2.5 IN.15.TOTAL # OF ATTACHMENTS: 3216.TOTAL AREA: 291.32 SQ. FT.17.TOTAL WEIGHT: 733.41 LBS.18.WEIGHT PER ATTACHMENT: 22.92 LBS.19.DISTRIBUTED LOAD: 2.52 PSF.20.MAX. HORIZONTAL STANDOFF: 48 IN.21.MAX. VERTICAL STANDOFF: IN ACCORDANCE WITHMODULE MANUFACTURER'S INSTRUCTIONS22.STANDOFF STAGGERING: YES23.RAIL MANUFACTURER (OR EQUIV.): IRONRIDGE24.RAIL MODEL (OR EQUIVALENT): AIRE RAIL A225.RAIL WEIGHT: 0.68 PLF.26.MAX. RAFTER SPAN: N/A.27.MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.S-501D52011121413151822ROOF SLOPE 910106217S-501D4154252423827231.FIELD VERIFY ALL MEASUREMENTSGENERAL NOTESBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCES-501.00ASSEMBLY DETAILS(SHEET 10)D4DETAIL (TRANSVERSE)NOT TO SCALED5DETAIL (LONGITUDINAL)NOT TO SCALED1RACKING DETAIL (TRANSVERSE)NOT TO SCALED3RACKING DETAIL (TOP)NOT TO SCALED2RACKING DETAIL (LONGITUDINAL)NOT TO SCALESigned 2/27/2024 SHEET KEYNOTES1.ROOF MATERIAL: CORRUGATED METAL2.ROOF STRUCTURE: TRUSS3.ATTACHMENT TYPE: ECOFASTENCORRUSLIDE4.MODULE MANUFACTURER: REC SOLAR5.MODULE MODEL: REC420AA PURE-R6.MODULE LENGTH: 68.1 IN.7.MODULE WIDTH: 44 IN.8.MODULE WEIGHT: 47.4 LBS.9.SEE SHEET A-103 FOR DIMENSION(S)10.MIN. FIRE OFFSET: NO FIRE CODE ENFORCED11.TRUSS SPACING: 48 IN. O.C.12. TRUSS SIZE: 2X6 IN. NOMINAL13. LAG BOLT DIAMETER: BOLT/SCREW SUPPLIED WITHRACKING.14. LAG BOLT EMBEDMENT: SEE MANUFACTURER15.TOTAL # OF ATTACHMENTS: 2816.TOTAL AREA: 249.7 SQ. FT.17.TOTAL WEIGHT: 628.64 LBS.18.WEIGHT PER ATTACHMENT: 22.45 LBS.19.DISTRIBUTED LOAD: 2.52 PSF.20.MAX. HORIZONTAL STANDOFF: 48 IN.21.MAX. VERTICAL STANDOFF: IN ACCORDANCE WITH MODULEMANUFACTURER'S INSTRUCTIONS22.STANDOFF STAGGERING: YES23.RAIL MANUFACTURER (OR EQUIV.): IRONRIDGE24.RAIL MODEL (OR EQUIVALENT): AIRE A225.RAIL WEIGHT: 0.68 PLF.26.MAX. TRUSS SPAN: N/A.27.MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.S-502D52011121413151822ROOF SLOPE 910106217S-502D4315425242382721.FIELD VERIFY ALL MEASUREMENTSGENERAL NOTESBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCES-502.00ASSEMBLY DETAILS(SHEET 11)D4DETAIL (TRANSVERSE)NOT TO SCALED5DETAIL (LONGITUDINAL)NOT TO SCALED1RACKING DETAIL (TRANSVERSE)NOT TO SCALED3RACKING DETAIL (TOP)NOT TO SCALED2RACKING DETAIL (LONGITUDINAL)NOT TO SCALESigned 2/27/2024 BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCER-001.00RESOURCE DOCUMENT(SHEET 12) BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCER-002.00RESOURCE DOCUMENT(SHEET 13) BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCER-003.00RESOURCE DOCUMENT(SHEET 14) BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCER-004.00RESOURCE DOCUMENT(SHEET 15) BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCER-005.00RESOURCE DOCUMENT(SHEET 16) BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 10.920 kWpENGINEER OF RECORD02.22.2024DESIGN BY:B.A.V.G.985 FLORENCE ROAD,NORTHAMPTON, MA 01062APN: 44 -048-001PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORLIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:664A1VALLEY SOLAR LLCPHONE:413-584-8844ADDRESS:116 PLEASANT STREETSUITE 321EASTHAMPTON, MA 01027186338JULIA RYANRESIDENCER-006.00RESOURCE DOCUMENTSHEET 17