Kaskey, Michelle Planset
76 North Meadowbrook Drive
Scott E. Wyssling, PE Alpine, UT 84004
Coleman D. Larsen, SE, PE office (201) 874-3483
Gregory T. Elvestad, PE swyssling@wysslingconsulting.com
December 19, 2023
Greenlancer Energy Inc.
500 Woodward Avenue, Suite 2125
Detroit, MI 48226
Re: Engineering Services
Kaskey Residence
28 Mark Warner Drive, Northampton MA
3.780 kW System - New
To Whom It May Concern:
We have received information regarding solar panel installation on the roof of the above referenced
structure. Our evaluation of the structure is to verify the existing capacity of the roof system and its ability
to support the additional loads imposed by the proposed solar system.
A. Site Assessment Information
1. Site visit documentation identifying attic information including size and spacing of framing
for the existing roof structure.
2. Design drawings of the proposed system including a site plan, roof plan and connection
details for the solar panels. This information will be utilized for approval and construction
of the proposed system.
B. Description of Structure:
Roof Framing: 2x10 dimensional lumber at 16” on center.
Roof Material: Composite Asphalt Shingles
Roof Slope: 37 degrees
Attic Access: Accessible
Foundation: Permanent
C. Loading Criteria Used
• Dead Load
o Existing Roofing and framing = 7 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 10 PSF
• Dead Load
o Existing Roofing and framing = 7 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 10 psf
• Live Load = 20 psf (reducible) – 0 psf at locations of solar panels
• Ground Snow Load = 40 psf
• Wind Load based on ASCE 7-10
o Ultimate Wind Speed = 117 mph (based on Risk Category II)
o Exposure Category C
Analysis performed of the existing roof structure utilizing the above loading criteria is in accordance
with the 2015 IRC, including provisions allowing existing structures to not require strengthening if
the new loads do not exceed existing design loads by 105% for gravity elements and 110% for
seismic elements. This analysis indicates that the existing framing will support the additional panel
loading without damage, if installed correctly.
Page 2 of 2
D. Solar Panel Anchorage
1. The solar panels shall be mounted in accordance with the most recent Ironridge installation manual.
If during solar panel installation, the roof framing members appear unstable or deflect non-
uniformly, our office should be notified before proceeding with the installation.
2. The maximum allowable withdrawal force for a 5/16” lag screw is 229 lbs per inch of penetration as
identified in the National Design Standards (NDS) of timber construction specifications. Based on
a minimum penetration depth of 2½”, the allowable capacity per connection is greater than the
design withdrawal force (demand). Considering the variable factors for the existing roof framing
and installation tolerances, the connection using one 5/16” diameter lag screw with a minimum of
2½” embedment will be adequate and will include a sufficient factor of safety.
3. Considering the wind speed, roof slopes, size and spacing of framing members, and condition of
the roof, the panel supports shall be placed no greater than 48” on center.
Based on the above evaluation, this office certifies that with the racking and mounting specified, the existing
roof system will adequately support the additional loading imposed by the solar system. This evaluation is in
conformance with the 2015 IRC, current industry standards, and is based on information supplied to us at the
time of this report.
Should you have any questions regarding the above or if you require further information do not hesitate to
contact me.
Very truly yours,
Scott E. Wyssling, PE
MA License No. 50507
Massachusetts COA # 1629764
GENERAL NOTES
1.1.1 PROJECT NOTES:
1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE NATIONAL ELECTRIC
CODE (NEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING AND INSTALLATION
INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY
HAVING JURISDICTION’S (AHJ) APPLICABLE CODES.
1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEM
INSPECTED PRIOR TO PARALLEL OPERATION
1.1.4 ALL PV SYSTEM COMPONENTS;MODULES,UTILITY-INTERACTIVE INVERTERS,AND
SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE IN
PHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC 690.4: PV MODULES: UL1703,
IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIRE INVERTERS: UL 1741 CERTIFIED,
IEEE 1547, 929, 519 COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY
1.1.5 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP
COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATED
ACCORDING TO NEC 690.7.
1.1.6 ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AND SOURCE
CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL
BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D). SHALL BE
INSTALLED ACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING [NEC
110.3].
1.1.7 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. IF
EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE
WILL BE INSTALLED AS REQUIRED BY THE NEC AND AHJ.
1.2.1 SCOPE OF WORK:
1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OF
THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BE
RESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN,
SPECIFY, AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THE
PHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT.
1.3.1 WORK INCLUDES:
1.3.2 PV ROOF ATTACHMENTS - IRONRIDGE FLASH VUE
1.3.3 PV RACKING SYSTEM INSTALLATION - IRONRIDGE AIRE A1
1.3.4 PV MODULE AND INVERTER INSTALLATION -
REC SOLAR REC420AA PURE-R / ENPHASE IQ7X-96-2-US
1.3.5 PV EQUIPMENT GROUNDING
1.3.6 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX
1.3.7 PV LOAD CENTERS (IF INCLUDED)
1.3.8 PV METERING/MONITORING (IF INCLUDED)
1.3.9 PV DISCONNECTS
1.3.10 PV FINAL COMMISSIONING
1.3.11 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV
1.3.12 SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE
*NEC2020I2
OWNER
NAME:MICHELLE KASKEY
PROJECT MANAGER
NAME:PATRICK RONDEAU
PHONE: 413-584-8844
CONTRACTOR
NAME:VALLEY SOLAR LLC
PHONE: 413-584-8844
AUTHORITIES HAVING JURISDICTION
BUILDING: CITY OF NORTHAMPTON
ZONING: CITY OF NORTHAMPTON
UTILITY: NATIONAL GRID
DESIGN SPECIFICATIONS
OCCUPANCY: II
CONSTRUCTION: SINGLE-FAMILY
ZONING:RESIDENTIAL
GROUND SNOW LOAD: 40 PSF
WIND EXPOSURE: C
WIND SPEED: 117 MPH
APPLICABLE CODES & STANDARDS
BUILDING: MASSACHUSETTS BUILDING CODE, 9TH
EDITION, AS AMENDED (780 CMR),
MASSACHUSETTS RESIDENTIONAL BUILDING
CODE, 9TH EDITION, AS AMENDED (780 CMR)
ELECTRICAL: NEC 2023
FIRE:MASSACHUSETTS COMPREHENSIVE FIRE
SAFETY CODE (527 CMR 1.00)
NFPA 1 FIRE CODE - 2021 (SETBACKS)
CODE (527 CMR 1.00)
PROJECT INFORMATION
NEW PV SYSTEM: 3.780 kWp
EXISTING PV SYSTEM: 7.800 kWp
TOTAL PV SYSTEM: 11.580 kWp
MICHELLE KASKEY RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
ASSESSOR'S #: 16B-001-045
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
01 AERIAL PHOTO
NOT TO SCALE
N
EW
S
02 PLOT MAP
NOT TO SCALE MARK WARNER DRSHEET LIST TABLE
SHEET NUMBER SHEET TITLE
T-001.00 COVER PAGE
G-001.00 NOTES
A-101.00 SITE PLAN
A-102.00 ELECTRICAL PLAN
A-103.00 SOLAR ATTACHMENT PLAN
A-104.00 ROOF PLAN
E-601.00 LINE DIAGRAM
E-602.00 DESIGN TABLES
E-603.00 PLACARDS
S-501.00 ASSEMBLY DETAILS
R-001.00 RESOURCE DOCUMENT
R-002.00 RESOURCE DOCUMENT
R-003.00 RESOURCE DOCUMENT
R-004.00 RESOURCE DOCUMENT
R-005.00 RESOURCE DOCUMENT
T-001.00
COVER PAGE
-SERVICE PHASE: SINGLE
-SERVICE SIZE (AMPS): 200
-DISTANCE FROM UTILITY METER TO TRANSFORMER: N/A
-CONNECTIVITY TYPE: UNDERGROUND
-UTILITY METER NUMBER: 05621891
-INVERTER: (9) ENPHASE IQ7X-96-2-US
-PANELS: (9) REC 420AA PURE-R
-DC-STC RATING OF SYSTEM: 3.780 kW
SCOPE OF WORK
NEW SYSTEM SIZE:
STC: 9 X 420W = 3.780KW
PTC: 9 X 399.84W = 3.599KW
AC SYSTEM DESIGN CAPACITY (NOMINAL): 2.835KW AC
AC DESIGN CAPACITY (MAX CONTINUOUS): 2.835 KW AC
(9) REC SOLAR REC420AA PURE-R
(9) ENPHASE IQ7X-96-2-US
ATTACHMENT TYPE: IRONRIDGE FLASH VUE
MSP UPGRADE:NO
EXISTING SYSTEM SIZE:
PTC: 26 X 270.4W = 7.030KW
STC: 26 X 300W = 7.800KW
AC SIZE (NOMINAL): 14.2W AC
AC SIZE (MAX CONTINUOUS): 14.2W AC
(26) SILFAB SLA300M
(26) ENPHASE M250-60-2LL-S25
(1) ENPHASE ENCHARGE-10
(1) ENPHASE ENCHARGE-3
TOTAL SYSTEM SIZE:
AC SIZE (NOMINAL): 14.2W AC
AC SIZE (MAX CONTINUOUS): 14.2W AC
Signed 12/19/2023
2.1.1 SITE NOTES:
2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.
2.1.3 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY
INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.
2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING
ROOF VENTS.
2.1.5 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL
EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.
2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH
THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF
COVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE.
2.2.1 EQUIPMENT LOCATIONS
2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.
2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING
TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLE 310.15 (B)(1).
2.2.4 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO NEC
690.34.
2.2.5 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN
SIGHT OF THE AC SERVICING DISCONNECT.
2.2.6 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO
NEC APPLICABLE CODES.
2.2.7 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN
APPROPRIATE.
2.3.1 STRUCTURAL NOTES:
2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT
INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES,
AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE
ARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS.
2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IF
ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS.
2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/ APPROVED
CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR.
2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE
SPECIFIED BY THE RACKING MANUFACTURER.
2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST
THE ROOF FRAMING MEMBERS.
2.4.1 GROUNDING NOTES:
2.4.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING
DEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE.
2.4.3 PV SYSTEMS REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR. ALL METAL ELECTRICAL
EQUIPMENT AND STRUCTURAL COMPONENTS BONDED TO GROUND, IN ACCORDANCE WITH
250.134 OR 250.136(A). ONLY THE DC CONDUCTORS ARE UNGROUNDED.
2.4.4 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM NEC TABLE
250.122.
2.4.5 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURE CONSIDERED
GROUNDED IN ACCORD WITH 250.134 AND 250.136(A).
2.4.6 EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN
MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED,
MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES
PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS.
2.4.7 THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL
OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE.
2.4.8 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR
MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]
2.4.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50 THROUGH
250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE
SYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47 AND AHJ.
2.4.10 DC PV ARRAYS SHALL BE PROVIDED WITH DC GROUND-FAULT PROTECTION MEETING THE
REQUIREMENTS OF 690.41(B)(1) THROUGH (3) TO REDUCE FIRE HAZARDS
2.5.1 INTERCONNECTION NOTES:
2.5.2 LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 705.12]
2.5.3 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S)OUTPUT CIRCUIT CURRENT AND THE
RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL NOT EXCEED 120
PERCENT OF THE AMPACITY OF THE BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE
LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(3)(2)].
2.5.4 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL RATING OF ALL
OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER,THE
COMBINED OVERCURRENT DEVICE MAY BE EXCLUDED ACCORDING TO NEC 705.12 (B)(3)(3).
2.5.5 FEEDER TAP INTERCONNECTION (LOAD SIDE) ACCORDING TO NEC 705.12 (B)(1) AND (2)
2.5.6 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.11 WITH SERVICE ENTRANCE
CONDUCTORS IN ACCORDANCE WITH NEC 230.42
2.5.7 BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT FROM
ADDITIONAL FASTENING [NEC 705.12 (E)].
2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:
2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE
CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE
SIDE” (TYPICALLY THE UPPER TERMINALS).
2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A
VISIBLE-BREAK SWITCH.
2.6.4 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED. THEREFORE BOTH MUST
OPEN WHERE A DISCONNECT IS REQUIRED, ACCORDING TO NEC 690.13.
2.6.5 ISOLATING DEVICES OR EQUIPMENT DISCONNECTING MEANS SHALL BE INSTALLED IN CIRCUITS
CONNECTED TO EQUIPMENT AT A LOCATION WITHIN THE EQUIPMENT, OR WITHIN SIGHT AND
WITHIN 10 FT. OF THE EQUIPMENT. AN EQUIPMENT DISCONNECTING MEANS SHALL BE
PERMITTED TO BE REMOTE FROM THE EQUIPMENT WHERE THE EQUIPMENT DISCONNECTING
MEANS CAN BE REMOTELY OPERATED FROM WITHIN 10 FT. OF THE EQUIPMENT, ACCORDING
TO NEC 690.15 (A).
2.6.6 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN
FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN ACCORDANCE WITH
690.12(A) THROUGH (D)
2.6.7 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND 240.
2.6.8 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED, THEREFORE BOTH
REQUIRE OVER-CURRENT PROTECTION, ACCORDING TO NEC 240.21. (SEE EXCEPTION IN NEC
690.9)
2.6.9 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO
NEC 690.11 AND UL1699B.
2.7.1 WIRING & CONDUIT NOTES:
2.7.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND
WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT
TO LIMIT UP-SIZING.
2.7.3 ALL CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.
2.7.4 EXPOSED PV SOURCE CIRCUITS AND OUTPUT CIRCUITS SHALL USE WIRE LISTED AND
IDENTIFIED AS PHOTOVOLTAIC (PV) WIRE [690.31 (C)]. PV MODULES WIRE LEADS SHALL
BE LISTED FOR USE ON PV ARRAYS, ACCORDING TO NEC 690.31 (A).
2.7.5 PV WIRE BLACK WIRE MAY BE FIELD-MARKED WHITE [NEC 200.6 (A)(5)].
2.7.6 MODULE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY.
2.7.7 ACCORDING TO NEC 200.7, UNGROUNDED SYSTEMS DC CONDUCTORS COLORED OR MARKED
AS FOLLOWS:
DC POSITIVE-RED, OR OTHER COLOR EXCLUDING WHITE, GRAY AND GREEN
DC NEGATIVE- BLACK, OR OTHER COLOR EXCLUDING WHITE, GRAY AND GREEN
2.7.8 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS:
PHASE A OR L1- BLACK
PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE
PHASE C OR L3- BLUE, YELLOW, ORANGE*, OR OTHER CONVENTION
NEUTRAL- WHITE OR GRAY
*IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED
ORANGE [NEC 110.15].
*NEC2020I2
*NEC2020I2
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
G-001.00
NOTES
Signed 12/19/2023
GENERAL NOTES
1.FIELD VERIFY ALL MEASUREMENTS
2.ITEMS BELOW MAY NOT BE ON THIS PAGE
3.THE SOLAR PANELS ARE LESS THAN 4 FEET
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
A-101.00
SITE PLAN
N
EW
S
01/16" = 1'-0"
SITE PLAN01 8'16'
ENTRANCE
AREA OF WORK
PROPERTY LINE
AC DISCONNECT #2
UTILITY METER
MARK WARNER DR12'-10"
46'-6"
29'-8"
48'-9"
AC DISCONNECT #1
AC DISCONNECT
EXISTING PV SYSTEM
EXISTING PV SYSTEM
Signed 12/19/2023
GENERAL NOTES
1.FIELD VERIFY ALL MEASUREMENTS
2.ITEMS BELOW MAY NOT BE ON THIS PAGE
3.THE SOLAR PANELS ARE LESS THAN 4 FEET
MODULE:
REC SOLAR
REC420AA PURE-R
420 WATTS
44''
68.1''
SQUARE FOOTAGE OF ROOF: 3068.9 SQ. FT.
SQUARE FOOTAGE OF ARRAY: 644.47 SQ. FT.
PERCENTAGE OF ROOF COVERED BY THE ARRAYS: 21%
MODULE:
SILFAB
SLA-300M
300 WATTS
38.97"
64.96"
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
A-102.00
ELECTRICAL PLAN
N
E
W
S
03/32" = 1'-0"
ELECTRICAL PLAN015'-4"10'-8"
A MODULE STRINGING
FIRE CLEARANCE
(N) (1) JUNCTION BOX
A
CONDUIT WILL NOT BE PLACED WITHIN FIRE
SETBACKS AS PER NFPA 1 2021
18" FIRE ACCESS PATH
18" FIRE ACCESS PATH
36" FIRE ACCESS PATH
36" FIRE ACCESS PATH
18" FIRE ACCESS PATH
18" FIRE ACCESS PATH 36" FIRE ACCESS PATH
18" FIRE ACCESS PATH
18" FIRE ACCESS PATH
36" FIRE ACCESS PATH
A A A
A
A
A
A
A
ARRAY 1 - 2.520 KW
[x6] (N) MODULES
TILT: 37 DEGREES
ROOF PITCH: 9:12
AZIMUTH: 284 DEGREES
EXISTING PV SYSTEM
EXISTING PV SYSTEM
ARRAY 2 - 1.260 KW
[x3] (N) MODULES
TILT: 37 DEGREES
ROOF PITCH: 9:12
AZIMUTH: 194 DEGREES
18" FIRE ACCESS PATH
18" FIRE ACCESS PATH
(E) (1) UTILITY METER
EXTERIOR PV EQUIPMENT
(E) (2) AC DICONNECTS
(N) (1) AC DICONNECT
INTERIOR PV EQUIPMENT
(E) (1) MAIN ELECTRICAL PANEL
(E) (1) ENPHASE ENPOWER SMART SWITCH
(E) (1) CRITICAL LOADS PANEL
(E) (1) AC COMBINER BOX
(N) (1) AC COMBINER BOX
(E) (1) CUSTOMER OWNED PRODUCTION METER
(E) (1) ENPHASE ENCHARGE 10
(E) (1) ENPHASE ENCHARGE
INTERIOR PV EQUIPMENT
18" FIRE ACCESS PATH
18" FIRE ACCESS PATH
GENERAL NOTES
1.FIELD VERIFY ALL MEASUREMENTS
2.ITEMS BELOW MAY NOT BE ON THIS PAGE
3.THE SOLAR PANELS ARE LESS THAN 4 FEET
MODULE:
REC SOLAR
REC420AA PURE-R
420 WATTS
44''
68.1''
MODULE:
SILFAB
SLA-300M
300 WATTS
38.97"
64.96"
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
A-103.00
SOLAR ATTACHMENT PLAN
03/32" = 1'-0"
SOLAR ATTACHMENT PLAN015'-4"10'-8"
ROOF MATERIAL IS ASPHALT SHINGLE
FLUSH MOUNT SOLAR MODULES
ATTACHED TO ROOF SURFACE (SEE
SHEET S-501.00 FOR MOUNTING DETAILS)ROOF RAFTERS
N
E
W
S
11'-1"
22'-1"
EXISTING PV SYSTEM
EXISTING PV SYSTEM
Signed 12/19/2023
GENERAL NOTES
1.FIELD VERIFY ALL MEASUREMENTS
2.ITEMS BELOW MAY NOT BE ON THIS PAGE
3.THE SOLAR PANELS ARE LESS THAN 4 FEET
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
A-104.00
ROOF PLAN
01 ROOF PLAN
NOT TO SCALE
Signed 12/19/2023
G
G
E
(E) (1) BATTERY
ENPHASE ENCHARGE 3
(E) (1) BATTERY
ENPHASE ENCHARGE 10
PV SYSTEM EQUIPPED WITH RAPID
SHUTDOWN DISCONNECT PER NEC 690.12
SYSTEM COMPLIANT WITH NEC 690.13
(E) ENPHASE SYSTEM
SHUTDOWN SWITCH
MODEL: EP200G-NA-02-RSD
NC4NC3
12 AWG
WIRES GN
TO (E)
LOADS
E
(E) CRITICAL LOADS PANEL
240/120 V 1Ø, 3W
MAIN BUSS: 125A
BLACK
RED
G
BLACK
RED
E
(E) (26) SILFAB
SLA-300M
300 WATTS
(E) (26) ENPHASE
M250-60-2LL-S25
(E) JUNCTION BOX
L1N L2 G
ENPHASE ENVOY
COMMUNICATIONS
GATEWAY
CELL
MODEM
ENSEMBLE WIRELESS
COMMUNICATION KIT
CT'sNOTE:HOLD ON KITS FOR PV BREAKERS
IS MANDATORY FOR IQ COMBINER 4 / 4C.
NOTE:HOLD DOWN KIT BRHDK125
IS NEEDED PER NEC 710.15 FOR PV
BREAKER FOR ALL IQ 8 SERIES
MICRO INVERTERS FAMILY
E
20A
E
20A
125A AC COMBINER BOX
ENPHASE IQ COMBINER 3
(X-IQ-AM1-240-3)
120/240V, 1Ø, 3W
MAX. CONTINUOUS CURRENT: 65A
MAX. OCPD: 90A
POWER
CONTROL
SYSTEM
PCS CT's
NFT
N
CONTROLLER
L1 L2
PV IN
L1 L2
BATTERY
IN
L1 L2
LOAD
OUT
L1 L2
LOAD
IN
LUGS LUGSLUGS
LUGS
L1 L2
ENVOY
LUGS
W/ESS HOLD
DOWN KIT
BRHDK 125
ENVHARGE
GN
(E) ENPHASE ENPOWER
MODEL: EP200G101-M240US00
240/120 V 1Ø, 3W
E
40A
E
10A
E
40A
E
50A
E
EQUIPMENT LEFT
OF LINE IS (N) NEW
UNLESS OTHERWISE NOTED.
EQUIPMENT RIGHT
OF LINE IS (E) EXISTING
UNLESS OTHERWISE NOTED.
GROUND
ROD
(E) GROUNDING
ELECTRODE
TO UTILITY
GRID (UG)
L1
L2
N(E) MAIN ELECTRICAL PANEL
240/120 V 1Ø, 3W
MAIN BUSS: 200A
MAX BREAKER SIZE:
(200A X 1.2 ) - 200A = 40A
ESS AND PV SYSTEM OUTPUT:
(E) PV: 26 X 1A X 125% = 32.5A
(N) PV: 9 X 1.31A X 125% = 14.74A
ESS: (16A+5.3A) X 125% = 26.63A
TOTAL: 73.87A MAX CURRENT PER NEC 705.12(B)(2)(3)(A)
PCS ENABLE TO LIMIT OUTPUT TO 30A
(E)
UTILITY
METER
GN
TO (E)
LOADS
(E) MAIN
200A
L2
L1
NNN
TAP
(1) ENCHARGE 10 AND (1) ENCHARGE 3 CANNOT HAVE
MORE THEN 21.3 AAC CONTINUOUS AND 29.9 AAC
SURGE FOR 10 SECONDS. TWO LARGEST BREAKERS IN
BACKED UP LOAD PANEL CAN OPERATE AT THE SAME
TIME AND CANNOT EXCEED THE (ESS) STORAGE
OUTPUT CAPACITY (AAC) PER NEC 710.15 (A)
G
SW1
(E) AC DISCONNECT, 60A
VM1
(E) PV METER
EEE
G
(E) CIRCUIT BREAKER
DISCONNECT
OCPD RATING: 60A
MLO BUSS: 125A
E
L2
L1
L2
L1
CB3
(N)
20A
(N) AC DISCONNECT, 30A
GL1NL2
ENPHASE ENVOY
COMMUNICATIONS
GATEWAY
125A AC COMBINER BOX
120/240V, 1Ø, 3W, X-IQ-AM1-240-4
MAX. CONTINUOUS CURRENT: 65A
MAX. OCPD: 90A
20A
15A
CB1
CB2
RED
BLACK
G
1
G
2 SW1
(N) JUNCTION BOX
(9) REC SOLAR
REC420AA PURE-R
420 WATTS
(9) ENPHASE
IQ7X-96-2-US
IN BRANCH
A
9
3
NOTE: READILY ACCESSIBLE OPEN BLADE AC
SYSTEM DISCONNECT VISIBLE FROM APPROACH
TO RESIDENCE 60A 240V LOCATED EXTERIOR
ON WALL NEAR METER NEMA 3R
NOTE: THE ESS WILL ONLY BE CHARGED BY PV.
THE ESS WILL DISCHARGE TO ON SITE LOADS.
THE ESSDISCHARGES TO THE GRID ONLY IF
REQUESTED BY THE GRID VIA CONNECTED
SOLUTIONS.
NEW PV SYSTEM: 3.780 KWP DC / 2.400 KWP AC
EXISTING PV SYSTEM: 7.800 KWP DC / 6.240 KWP AC
EXISTING ESS SYSTEM: 5.12 KWP AC
TOTAL PV SYSTEM: 11.580 KWP DC / 14.200 KWP AC
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
ID TYPICAL CONDUCTOR CONDUIT CURRENT-CARRYING
CONDUCTORS IN CONDUIT OCPD EGC TEMP. CORR.
FACTOR
CONDUIT FILL
FACTOR
CONT.
CURRENT
MAX. CURRENT
(125%)BASE AMP.DERATED
AMP.TERM. TEMP. RATING AMP. @ TERMINAL
1 1 10 AWG THWN-2, COPPER 0.75'' DIA EMT 2 20A 6 AWG THWN-2, COPPER 0.96 (32.7 °C)1 11.79A 14.74A 40A 38.4A 75°C 35A
2 1 10 AWG THWN-2, COPPER 0.75'' DIA EMT 2 N/A 10 AWG THWN-2, COPPER 0.96 (32.7 °C)1 11.79A 14.74A 40A 38.4A 75°C 35A
3 1 10 AWG THWN-2, COPPER 0.75'' DIA EMT 2 20A 10 AWG THWN-2, COPPER 0.96 (32.7 °C)1 11.79A 14.74A 40A 38.4A 75°C 35A
E-601.00
LINE DIAGRAM
A MODULE STRINGING
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP DC
EXISTING PV SYSTEM: 7.800 KWP DC
TOTAL PV SYSTEM: 11.580 KWP DC
NEW PV SYSTEM: 2.840 KWP AC
EXISTING PV SYSTEM: 11.360 KWP AC
TOTAL PV SYSTEM: 14.200 KWP AC
SYSTEM SUMMARY
BRANCH #1
INVERTERS PER BRANCH 9
MAX AC CURRENT 11.79A
MAX AC OUTPUT POWER 2,835W
ARRAY STC POWER 3,780W
ARRAY PTC POWER 3,599W
MAX AC CURRENT 11.79A
MAX AC POWER 2,835W
DERATED (CEC) AC POWER 2,835W
DISCONNECTS
INVERTERS
OCPDS
MODULES
ASHRAE EXTREME LOW -25.9°C (-14.6°F), SOURCE: BARNES MUNI (42.16°; -72.72°)
ASHRAE 2% HIGH 32.7°C (90.9°F), SOURCE: BARNES MUNI (42.16°; -72.72°)
REF.QTY.RATED CURRENT MAX VOLTAGE
CB1 1 20A 240VAC
CB2 1 15A 240VAC
CB3 1 20A 240VAC
REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE
SW1 1 EATON DG221URB OR EQUIV.30A 240VAC
REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING
PM1-9 9 REC SOLAR REC420AA PURE-R 420W 399.84W 8.89A 8.4A 59.4V 50V -0.143V/°C (-0.24%/°C)25A
REF.QTY.MAKE AND MODEL AC
VOLTAGE GROUND OCPD
RATING
RATED
POWER
MAX OUTPUT
CURRENT
MAX INPUT
CURRENT
MAX INPUT
VOLTAGE
CEC WEIGHTED
EFFICIENCY
I1-9 9 ENPHASE IQ7X-96-2-US 240V FLOATING 20A 315W 1.31A 10A 80V 97.5%
BILL OF MATERIALS
CATEGORY MAKE MODEL NUMBER REF QTY UNIT QTY/UNIT DESCRIPTION
MODULE REC SOLAR REC420AA PURE-R PM1-9 9 PIECES 1 REC SOLAR REC420AA PURE-R 420W 0
INVERTER ENPHASE IQ7X-96-2-US I1-9 9 PIECES 1 ENPHASE IQ7X-96-2-US 315W INVERTER
DISCONNECT EATON DG221URB SW1 1 PIECE 1 EATON DG221URB, NON FUSED, 2-POLE, 30A, 240VAC OR EQUIVALENT
MISC ELECTRICAL EQUIPMENT GEN-CABLE-CLIP HDWR12-57 45 PIECES 1 GENERIC CABLE CLIP
AC COMBINER PANEL ENPHASE-IQ4-PANEL EP1 1 PIECE 1 ENPHASE IQ COMBINER 4 (X-IQ-AM1-240-4)
WIRING ENPHASE Q-12-10-240 EN1-9 9 PIECES 1 ENPHASE ENGAGE (TM) TRUNK CABLE
WIRING ENPHASE Q-TERM-10 EN10 1 BUNDLE 10 ENPHASE ENGAGE (TM) BRANCH TERMINATOR
WIRING ENPHASE Q-SEAL-10 EN11 1 BUNDLE 10 ENPHASE ENGAGE (TM) WATERTIGHT SEALING CAP
WIRING GEN-10-AWG-THWN-2-CU-RD WR1-3 75 FEET 1 10 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-10-AWG-THWN-2-CU-BLK WR1-3 75 FEET 1 10 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-10-AWG-THWN-2-CU-WH WR2-3 30 FEET 1 10 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-10-AWG-THWN-2-CU-GR WR2-3 30 FEET 1 10 AWG THWN-2, COPPER, GREEN (GROUND)
WIRING GEN-6-AWG-THWN-2-CU-GR WR1 45 FEET 1 6 AWG THWN-2, COPPER, GREEN (GROUND)
WIREWAY ENPHASE ET-SPLK-05 EN4 1 BUNDLE 5 ENPHASE ENGAGE (TM) ENGAGE COUPLER
WIREWAY GEN-EMT-0.75'' DIA WW1-3 75 FEET 1 EMT CONDUIT, 0.75'' DIA
OCPD GENERIC MANUFACTURER GEN-CB-20A-240VAC CB1 1 PIECE 1 CIRCUIT BREAKER, 20A, 240VAC
OCPD GENERIC MANUFACTURER GEN-CB-15A-240VAC CB2 1 PIECE 1 CIRCUIT BREAKER, 15A, 240VAC
OCPD GENERIC MANUFACTURER GEN-CB-20A-240VAC CB3 1 PIECE 1 CIRCUIT BREAKER, 20A, 240VAC
TRANSITION BOX GENERIC MANUFACTURER GEN-AWB-TB-4-4X JB1 1 PIECE 1 TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKS
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
E-602.00
DESIGN TABLES
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2023 NATIONAL ELECTRICAL CODE,
INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z535
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING
JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED
BACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE
YELLOW BACKGROUND. [ANSI Z535]
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
LABEL 1
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT (2" X 4").
[NEC 690.13].
POWER SOURCE
OUTPUT CONNECTION
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
WARNING
LABEL 2
AT POINT OF INTERCONNECTION
OVERCURRENT DEVICE (2" X 4").
[NEC 705.12(B)(2)(3)(B)].
LABEL 3
AT POINT OF INTERCONNECTION, MARKED
AT DISCONNECTING MEANS (4" X 3").
[NEC 690.54]
LABEL 4
AT EACH AC DISCONNECTING MEANS
(4" X 1").
[NEC 690.13(B)].
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE
DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING
MEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8").
[NEC 690.56(B)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A
DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PV
SYSTEM DISCONNECTING MEANS.
PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED IN
BATHROOMS
[NEC 690.4(D),(E)]
PHOTOVOLTAIC POWER SOURCE
LABEL 9
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
OR FLOORS (5 3/4" X 1 1/8").
[CEC 690.31(D)(2)]
SOLAR PV SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
TURN RAPID SHUTDOWN SWITCH TO
THE "OFF" POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE SHOCK
HAZARD IN ARRAY
SOLAR ELECTRIC
PV PANELS
LABEL 6
AT RAPID SHUTDOWN SYSTEM
(3 3/4" X 5 1/4"). [NEC 690.56(C)(1)(A)].
WARNING
DUAL POWER SUPPLY
SOURCES: UTILITY GRID
AND PV SOLAR
ELECTRIC SYSTEM
LABEL 7
AT POINT OF INTERCONNECTION
(2 3/4" X 1 5/8").
[NEC 705.12(B)(3)]
WARNING
SOLAR ELECTRIC
CIRCUIT BREAKER
IS BACKFED
LABEL 8
AT POINT OF INTERCONNECTION
(2" X 1").
[NEC 705.12(B)(3)]
CAUTION
MULTIPLE SOURCES OF POWER
LABEL 10
AT UTILITY METER (5 3/4" X 1 1/8")
[NEC 690.56(B)]
RAPID SHUTDOWN
SWITCH FOR
SOLAR PV SYSTEM
LABEL 5
AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2").
[NEC 690.56(C)(3)].
AC DISCONNECT
PHOTOVOLTAIC SYSTEM
POWER SOURCE
RATED AC
OUTPUT CURRENT
NOMINAL OPERATING
AC VOLTAGE
AMPS
VOLTS
PHOTOVOLTAIC SYSTEM
DISCONNECT
INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
NORTH SIDE OF THE HOUSE
11.79
240
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
E-603.00
PLACARDS
MAIN DISTRIBUTION
UTILITY DISCONNECT
(INTERIOR)
FRONT
BACK
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:NEWSPV ARRAY
PV METER MA
(CUSTOMER OWNED)
(INTERIOR)
(E) AC DISCONNECTS
(EXTERIOR)
ENPHASE ENCHARGE 10 (INSIDE)
(N) AC COMBINER PANEL
(INTERIOR)
EXISTING
PV SYSTEM
ENPHASE ENCHARGE 3 (INSIDE)
ENPHASE ENPOWER (INSIDE)
UTILITY METER
(EXTERIOR)
(N) AC DISCONNECT
(EXTERIOR)
(E) AC COMBINER PANEL
(INTERIOR)
(E) MAIN ELECTRICAL
PANEL (INTERIOR)
(E) CRITICAL LOADS
PANEL (INTERIOR)
GENERAL NOTES
1. FIELD VERIFY ALL MEASUREMENTS
2. ITEMS BELOW MAY NOT BE ON THIS PAGE
3. THE SOLAR PANELS ARE LESS THAN 4 FEET
111133
2727
54 8
252423
S-501
D4
2
ROOF SLOPE991010
1010
66 2121
77
2020
1212141413131515181822221111
S-501
D5
SHEET KEYNOTES
1. ROOF MATERIAL: ASPHALT SHINGLE
2. ROOF STRUCTURE: COLLAR TIE
3. ATTACHMENT TYPE: IRONRIDGE FLASH VUE
4. MODULE MANUFACTURER: REC SOLAR
5. MODULE MODEL: REC420AA PURE-R
6. MODULE LENGTH: 68.1''
7. MODULE WIDTH: 44''
8. MODULE WEIGHT: 47.4 LBS.
9. SEE SHEET A-103 FOR DIMENSION(S)
10. MIN. FIRE OFFSET: 18" FROM RIDGE, AT LEAST 2 PATHWAY
TO A STREET OR DRIVEWAY MINIMUM 3' WIDE
11. RAFTER SPACING: 16 IN. O.C.
12. RAFTER SIZE: 2X10 IN. NOMINAL
13. LAG BOLT DIAMETER: 5/16 IN.
14.LAG BOLT EMBEDMENT: 2.5 IN.
15. TOTAL # OF ATTACHMENTS: 21.
16. TOTAL AREA: 187.28 SQ. FT.
17. TOTAL WEIGHT: 476.8 LBS.
18. WEIGHT PER ATTACHMENT: 22.7 LBS.
19. DISTRIBUTED LOAD: 2.55 PSF
20. MAX. HORIZONTAL STANDOFF: 48 IN. IN.
21. MAX. VERTICAL STANDOFF: IN ACCORDANCE WITH
MODULE MANUFACTURER'S INSTRUCTIONS.
22. STANDOFF STAGGERING: YES
23. RAIL MANUFACTURER (OR EQUIV.): IRONRIDGE
24. RAIL MODEL (OR EQUIVALENT): AIRE A1
25. RAIL WEIGHT: 0.436 PLF
26. MAX. SPAN: N/A.
27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
S-501.00
ASSEMBLY DETAILS
D4 DETAIL (TRANSVERSE)
NOT TO SCALE D5 DETAIL (LONGITUDINAL)
NOT TO SCALE
D1 RACKING DETAIL (TRANSVERSE)
NOT TO SCALE
D3 RACKING DETAIL (TOP)
NOT TO SCALE
D2 RACKING DETAIL (LONGITUDINAL)
NOT TO SCALE
Signed 12/19/2023
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
R-001.00
RESOURCE DOCUMENT
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
R-002.00
RESOURCE DOCUMENT
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
R-003.00
RESOURCE DOCUMENT
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
R-004.00
RESOURCE DOCUMENT
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
E.T.DESIGN BY:
12.06.2023
M.M.
MICHELLE KASKEY
RESIDENCE
28 MARK WARNER DR.,
NORTHAMPTON, MA 01062
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 16B-001-045
MA HIC# 186338
MA EC# 664A1
NEW PV SYSTEM: 3.780 KWP
EXISTING PV SYSTEM: 7.800 KWP
TOTAL PV SYSTEM: 11.580 KWP
R-005.00
RESOURCE DOCUMENT