146 Elm Sprinkler 2014-09-19X
Initial Construction Control Document
To be submitted with the building permit application by a
Registered Design Professional
for work per the 8th edition ofthe
Massachusetts State Building Code, 780 CMR, Section 107
Project Title: Smith College, Residence Conversion Date:6/281l4
Property Address: 146 Elm Street
Project: Check (x) one or both as applicable: x Existing Construction
Project description: Convert to student housing
I Carl C. Koslowski MA Registration Number: 37810 Expiration date: 6/30/2014, am a registered design professional,
and I ha;e prepared or directly supervised the preparation of all design plans, computations and specifications
concernmg:
Fire Protection, fire sprinkler
for the above named project and that to the best of my knowledge, information, and belief such plans, computations and
specifications meet the applicable provisions ofthe Massachusetts State Building Code,. (780 CMR), and accepted
engineering practices for the proposed project. I understand and agree that I (or my designee) shall perform the necessary
professional services and be present on the construction site on a regular and periodic basis to:
1. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the
contractor in accordance with the requirements ofthe construction documents.
2. Perform the duties for registered design professionals in 780 CMR Chapter 17, as applicable.
3. Be present at intervals appropriate to the stage ofconstruction to become generally familiar with the progress and
quality ofthe work and to determine if the work is being performed in a manner consistent with the approved
construction documents and this code.
Nothing in this document relieves the contractor of its responsibility regarding the provisions of 780 CMR 107.
When required by the building official, I shall submit field/progress reports (see item 3.) together with pertinent
comments, in a form acceptable to the building official.
Upon completion of the work, I shall submit to the building official a 'Final Construction Control Document'.
Enter in the spac,9J,,''.' ".<:" '~t','wet" or electronic signature and seal: ~x,.\>.\.. MAo'"
1} ~ ~(~~:::\
II ~ CARL C " L.,." .
, \ 'c:;.
KG I' u'
r \ ,~
. u rlRE PROTECT/ON I :',
\ -0 No, 37810 J \\!bA$t,'G/~m:?:r )S'J 4'\~ .~_c~Q0{~
Phone number (413)436-5500 xlII Email: cck@rybak-fpc.com
Building Official Use Only
Building Official Name: PennitNo.: Date:
Note I, Indicate with an 'x' project design plans, computations and specifications that you prepared or directly supervised. If 'other' is chosen,
provide a description.
Fire Protection Construction Documents
Fire Sprinkler Narrative Report for
Smith College
Residence Conversion
146 Elm Street
Northampton, Massachusetts
By
Cutler Design, Inc.
43 Harvard Street
Worcester, MA 01609
Rybak Engineering, Inc. -Fire Sprinklers
Fire Protection Consultants
132 Forest Avenue
Warren, Massachusetts 01083
Tel: (413) 436-5500
June 28, 2014
FIRE PROTECTION SYSTEMS NARRATIVE REPORTS
903.1.1 (1.a) BASIS (METHODOLOGY) OF DESIGN
Buildings is an existing three story wood framed residential building to be converted to housing.
SECTION 1 -Building Description
a) Building "Use" Group
Use Groups:
Residential (see Section 310): Group R-2
b) Total square footage of building -4,900
c) Building height -36
d) Number of floors above grade -3
e) Number of floors below grade 1
f) Square footage per floor-1,300 (typical floor)
g) Type(s) of occupancies (hazards) within the building -Residential
h) Type(s) of construction VB
i) Hazardous material usage and storage -none
j) High storage of commodities within a building usually over 12 ft.-none
SECTION 2 -Applicable Laws, Regulations and Standards
a) Massachusetts State Building Code, 8th Edition, 780 CMR
b) NFPA Standards and Edition used for design of each specific fire protection system
NFPA 13R, Installation of Sprinkler Systems Residential to Four Stories, 2013 edition
NFPA 72, National Fire Alarm Code, 2010 Edition
NFPA 24, Installation of Private Fire Service Mains, 2002 edition
SECTION 3 -Design Responsibility for Fire Protection Systems
The fire sprinkler system design responsibility is described as:
Fire Sprinkler System:
Rybak Engineering and Carl C. Koslowski, PE fully designs (complete layout and calculations) and
specifies the fire protection system or systems to be installed, reviews and approves the installing
contractor's shop drawings. The PE is considered the engineer of record and certifies system installation for
code compliance at completion.
Fire Alarm System:
See fire alarm plans.
Overall Building Coordination:
Cutler design is the professional of record and assumes responsibility for the coordination of each specific
fire protection system requiring integration, forming an entire building life safety system.
SECTION 4 -Fire Protection Systems to be installed
a) Water supply, fire mains and hydrants New service from city main
b) Automatic sprinkler systems and components Each floor will have individual zone controls. The
third floor is unheated storage and will have a dry system. The l3R system is note required to have
full sprinkler protection.
-no coverage in porch, outside areas, or combustible concealed spaces.
-closets are protected as an improvement beyond the code minimum
d) See Shepherd Engineering Documents
f) Seismic considerations -fire sprinkler system is fully braced for earthquake protection
903.1.1 (1.b) SEQUENCE OF OPERATION
SECTION 1
WET SPRINKLER SYSTEM
System operates automatically upon the fusing of a single fIre sprinkler.
Operational Sequence:
1. The activation of a single sprinkler will discharge water and close the contacts of a vane type flow
switch.
2. Closed contact on the flow switch will activate local electric bell (upon 30 second delay) and provide
an alarm contact for the alarm control panel.
DRY SPRINKLER SYSTEM
System operates automatically upon the fusing of a single fIre sprinkler.
Operational Sequence:
1. The activation of a single sprinkler will allow the air to exhaust the system and discharge water.
2. The dry valve will activate the system pressure switch.
3. Closed contact will activate local alarm indication including strobes, horns and bells.
4. Closed contact will send signal through local alarm panel to central station, central station will then
notifY fIre department.
GENERAL NOTE: all supervisory and alarm contacts are to be relayed to the fIre alarm panel. The main
fIre alarm panel is required to be supervised by a central station service.
FIRE ALARM SYSTEM
Operational Sequence, Alarm:
1. Alarm condition in any alarm contact including smoke detector, heat detector, pull station, or fIre
sprinkler flow switch will be identified at panel
2. Audible devices will indicate alarm condition.
3. Digital Dialer will relay alarm condition to COPS Monitoring Central Station.
4. Central Station must contact fIre department and owner
Operational Sequence, Trouble or Supervisory:
1. Abnormal condition in any contact including tamper switch, low air, etc will identifIed at panel.
2. Digital Dialer will relay alarm condition to COPS Monitoring Central Station.
3. Central Station must contact the owner
903.1.1 (1.c) TESTING CRITERIA
SECTION 1 -Testing Criteria
FIRE SPRINKLER SYSTEM
Hydrostatically test at a pressure of200 psi for two hours without a loss in pressure.
Conduct forward flow test ofbackflow preventer at a rate of750 GPM.
Opening of the inspectors test connection shall initiate an alann at the main frre alarm panel within 90
seconds.
Hydrostatically test at a pressure of200 psi. Maximum leakage rate shall not exceed 1 quart per hour.
Underground: Thoroughly flush at a rate of 400 GPM
2" drain test shall be conducted. Static and Residual pressures must be recorded on test certificate.
Pnuematically test system at a pressure of 40 psi for 24 hr. Maximum pressure loss is I Yz psi
Conduct system operational test from inspectors test connection. Local alann must sound within 90
seconds. Central station must receive alann and trouble signals.
Working test of dry valve.
Water delivery time to inspectors test: 60 seconds
All supervisory switches shall be tested and shall register a trouble condition an the main alann panel.
All alarm switches shall be tested and shall register an alarm condition an the main alann panel.
FIRE ALARM SYSTEM
See fire alarm narrative.
SECTION 2 -Approval Requirements
a) Rybak Engineering will provide a certificate of completion for the fIre sprinkler system only.
b) Fire alarm contractor shall provide the fIre department with the fIre alarm system test results prior to
the fIre department testing for occupancy.
c) Approval of local authorities is required.
d) The sprinkler contractor shall inform Rybak Engineering when the system piping is roughed in and
prior to installation of the ceilings.
e) Contractors must schedule a "rough" inspection with the Fire Department before piping and wiring is
covered by the wall or ceiling.
1) Prior to scheduling a final acceptance test, documentation shall be submitted to the Fire Department
certifying that the systems are installed in accordance with the codes and all components of the system
have been tested.
DEFINITIONS
Fire Protection Systems Fire Protection Systems -Automatic sprinkler systems, fIre detection system,
fire alarm notification system, smoke control system, kitchen hood suppression system, etc.
Building Life Safety System Building Life Safety System -A combination of fIre protection systems and
other building fire protection features such as automatic door closers, emergency generators, emergency
egress lighting, elevator systems, etc., interconnected or integrated with multiple fIre protection systems
functioning simultaneously when activated.
Preparer of Narrative Report -An individual who has taken charge of a project and has knowledge of
required and non-required fIre protection systems and buildings life safety systems. The designer in charge
of a specific design for a fIre protection system may prepare their portion of the Narrative Report to be
submitted to the individual who has "taken charge". The individual who has "taken charge" shall compile
the data from the designer of each system and prepare a single, comprehensive and coordinated fmal
Narrative Report describing each system and when applicable a description of how each system interlaces
with the building life safety system's integration and sequence of operation. The take charge individual
may be the architect, engineer of record, and the designer of any of the fIre protection systems or an
independent qualified consultant.