Loading...
31C-082 (8) AM 4/ 411v BP-2021-0246 140 OLANDER DR G1S#: COMMONWEALTH OF MASSACHUSETTS Map:Block: 31C-082 CITY OF NORTHAMPTON Lot: - PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A) New Multi-Family Housing BUILDING PERMIT Pennit# BP-2021-0246 Project# JS-2021-000413 Est. Cost: $1 1006280.00 Fee: $36794.00 PERMISSION IS HEREBY GRANTED TO: Const. Class: Contractor: License: Use Group: SALOOMEY CONSTRUCTION 018780 I,ot Size(sd. ft.): Owner: NORTH COMMONS AT VILLAGE HILL LLC Zoning: Applicant: SALOOMEY CONSTRUCTION AT: 140 OLANDER DR Applicant Address: Phone: Insurance: P O BOX 1203 (413) 269-4360 WC WESTFIELDMA01086 ISSUED ON:9/4/2020 0:00:00 TO PERFORM THE FOLLOWING WORK:NEW 53 PASSIVE UNIT HOUSE APARTMENT BUILDING POST THIS CARD SO IT IS VISIBLE FROM THE STREET Inspector of Plumbing Inspector of Wiring U.P.W. Building Inspector Underground: Service: Meter: Footings: Rough: Rough: House# Foundation: Driveway Final: Final•/Z,- ---/ Final: a_ /I 7 Rough Frame: Gas: Fire Department Fireplace/Chimney: Rough: Oil: Insulation: Final:! Z-zP.--al Smoke: Final: 01Z Wii/da d4 '14 "1/ THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF ANY OF ITS RULES AND REGULATIONS. 1 I cal, Certificate of Occupancy _ Signature: .I 10 FeeType: Date Paid: Amount: Building 9/4/2020 0:00:00 $36794.00 212 Main Street, Phone(413)587-1240,Fax: (413)587-1272 Louis Hasbrouck--Building Commissioner PROJECT NAME PROJECT ADDRESS I110 0 fJ nis DATE NAME/INITIALS INSPECTION TYPE/NOTES STATUS /o-1y�� i . z .0,`.5, 1,vAte, -> co12 2.. of 1-'Ov 1'\ iJ*,- Az_ rapkx. k &)o ii WALL. T-0or11-4,5 - eti-S— IQ-ZO-2vw jl i 1 . kmSi - ran-ADA i+ON MILL O.V 571112wc-L.L 3 500-H - u:R Ei asp 112e-t36L D- ►4"III . ib Z3-2ozc y g (ilJ�7i Fbu,Joft110,-- iF0 JL44- IUi-> ii✓ —(X)7 T H" I I-3-2oze K a L ot'm er., -r roar 11.,c. r x)omli tut- ge me 6 ks tNcn,n Fann,-,c. Svvtrl IY+ t j. *LA— 1/—)51s Levi ickj t-1.262(, if;e e L1 E.Le i)et ote- 4P 2 - f3A1,2 .4- WALL W QeePh2 11-10-2o2o ©•it esu r 1e►i WL „_^ Util ,l-ii�5.� r 1�i-� !I-13 2026 Y1. 6: ..4-or_ 4, -r3f e t tti-,- rrx:i.,0,41.-10,.., "- 13rt,2•o- i Wti&C Ac-i ',1 ) V I I.18 7 Zo )('' a eo14;#,i�, A1LrY47 ( ‘44,- 1 zrT16/'• - ' f RdIt/ rn3P 0 ic- -'0L.125144g INsUt.4-110,.„ T'v L1a,ie L; 4- 12-ii-zo2o //,1 l N;a, N .--5 0 / ii►,A.,c,-IC.5 L-i NC 1c- LiNc cf 12- it 24) i6k7 it USE BACK SIDE FOR ADDITIONAL NOTES PROJECT NAME PROJECT ADDRESS DATE NAME/INITIALS INSPECTION TYPE/NOTES STATUS ,)Nne4541-8 002 13i4(12► WIRc Nt-Dti 1-21-26 i"I< kr1 _ / 27/04) ffi &c-c ac-4-4.-tva) 1- o I r✓V 7 port_ 5 Mt 25 Go i mac:. ';i) 13ikf (�9I -24-4-2( K J2 w 4121 24r5-' iP.#/ 26-irae--/-e- 4,4„vc ai r 6/Q.`" 3/?- = 04, a,„cd, 3 r 7 l►�o.,r�e ,` 2 C. 2) � 3/7 y/rf; 3) 9 /27/2.1 U S 3► )& )9 c�R C-/ -2/ 6-mow 7)A sJL>043-. �1 I f` C�itiUt��,E'.tx� . ,Q-dpr�- I S93' 1J 1 ULJ;I OtJ - Zr)', 3) 4, 3 i9 ` ELEV 0 C `Z a0y� O k J�7 R. µ,ll. N f o itjh £1 tic."fr v l7 Oc;41. 3io,,3i/ 3/z,3/3 6/1724 31Y,316; 14 f 0)at) 7=2.04w cRC'u&►N VRAll\J & U lns 3iO 3)(t) 64g/2/ toy, USE BACK SIDE FOR ADDITIONAL NOTES PROJECT NAME PROJECT ADDRESS DATE NAME/INITIALS INSPECTION TYPE/NOTES STATUS 1 u-Ut, � - 2,iO - i CA) O K 6 4 )1 R M r I-l.. a/o l / C- l/c r (.,t/� „ ("4 ' �- �- /z—/f z,? 2// -1 -6-27 Rf6 , 0-1'`.1-‘'. 1 it r/.6=. -�'' ' 'T o_,„ev )L i /7(.2 ;kV. Qcf)v, ROUG N FRAtAk47: uu, Uulrs 4�10 I NSOL. uur-S 4aa.-mats IV)9/9A ABo r� C AIL I I.IG LOO goOTH CO R►i " ©K ZZ 2 ° iArer-, /6,0/4- is t LEI /2 ,y is—i , / '7 / in - ZIC.-2.11 - 2 I '- 2`"'T Laci2 7-23 z l( 12 Mc� ' Cy— aocm /0 - r I V.1 l-n-l&-tL R d U c - 7 - 2-2/ O/` ai C -Cr , kcJIN V) l Gam/ 3,e0 Z 5rx1 H 1ALL 7V Hrzr Ri^ 03 t. -72_8-z I 1.% • USE BACK SIDE FOR ADDITIONAL NOTES PROJECT NAME PROJECT ADDRESS DATE NAME/INITIALS INSPECTION TYPE/NOTES STATUS V6. �MSULJ TION I 4 //.-c)i ca\ 02 4- f(b01\- VI tM - L_W. 0\\/ -g.6 61k Qt.q.e. I ,2,k_ ,ot,),,,_ . ey-i g -aa -al v.,. 4. 4,,,-- a y s ,,,I- 6,&,- o� 3Ro FLooR ){Of T�1 u l�-S -- t�ouG)a ©K . `JJ /3o/ j Ct..XSFZWK. Wl0L1,s o)4L ©I` Ulc' 2;_3‘, 4,4 Tee vz i-r, 6,fr e Jr' re 1 aCilL , 01Z 2'Rb PL© .1.1oPX'4 . g/31//1 ; 7 ; (cxcEFT 30'7 e LAupn 2M) OR 2-/-c- :5-"- 2... .9 FLe- '2 e,. 4 t\ 3 ..J1/4-- 1.)-lk4fil ua k, 1// oZl q 4, YR►zWit taoK 6i/a 61 1 J M )L, Uu ng 2'0).- ow Soy ,,btoi 1 7 11,1SU1., u>J►YS a0,5- 2-0a USE BACK SIDE FOR ADDITIONAL NOTES Cere-re- 617? PROJECT NAME PROJECT ADDRESS iF DATE NAME/INITIALS INSPECTION TYPE/NOTES STATUS /6_1-a1 lfy •', 9."(Qh s Q oi_zt, CI e.. G'vO L ash lsT rLoo:2 1JUIL,-K UJ.ri3 Oi-)L'(} Pr F4. 10-12-21 l/ a50uiH HAt+- D v _ /o/ /dz /o4 %o 7 c cSat/7W'S � Yn'4-r Ai, j NSuL, 101 107 OU 6-W C EN` R, SI liZuwtA.. 1049PI J'E. OK % g 1 a J / t,k, /C 1 rz-41f"-fri-v 6‘-/ -2,-- --e iti-f-e-#4-yv d_20._2/ , Zo AI 6r' , ITRouC11.1 1' F Coq�1\ �f /0, ).LI% G _,��� i)O v6H ri-ii‘„ �P L-64r� , Roua.-f PIM J r Y( NCE ji / i R CO AIAOM Aq A oR r ? i U L ATI ON - �I� €��i \t!C{t 1J/iC} /I CoK IJkoN Inge K 413p Ovls Teel--we Vy o/ USE BACK SIDE FOR ADDITIONAL NOTES PROJECT NAME PROJECT ADDRESS ( DATE NAME/INITIALS INSPECTION TYPE/NOTES STATUS /3.43 31 QPm Isa -3 9I1j `e vt \ CA'? ;a-�s� 0 AC FI:), L , CONxaN 'w as Sece,4, ri-K43 "w/4t-A i=t,vo-L ® (L "21`2l V 3 I ci Zi v #+rzb nor ape itr x t z--2,F-zi ..7., ___ ,g0,-.2-t, ,.... 1.4,-eicy '1C i -7?,9- ilk_ _Cmcie/c .,..,/i.ei- (74-i q-het 01; 0 i(--. V i e - 0 -to DCCuP4 (�kcLUbFC ) ,Plit110 l/7 2 d, 1 ?Mgkf\ C o r o IS, z, I< - i 1-as (11C" �;,p 1 r1A,Q.,- oXV /ii/aa II• ----1 tiliPtt,- Og D OCCuP ALL AczCAS o)( USE BACK SIDE FOR ADDITIONAL NOTES SYSTEM RECORD OF INSPECTION AND TESTING This form is to be completed by the system inspection and testing contractor at the time of a system test. It shall be permitted to modify this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Attach additional sheets,data, or calculations as necessary to provide a complete record. Inspection/Test Start Date/Time: 12/10/2021 7:00 Inspection/Test Completion Date/Time: 12/10/2021 21:00 Supplemental Form(s)Attached: YES (yes/no) 1. PROPERTY INFORMATION Name of property: North Commons Address: 140 Ortander Dr,Northampton,Ma Description of property: Housing Name of property representative: Address: Phone- Fax: E-mail: 2. TESTING AND MONITORING INFORMATION I-esting organization: Wel-Design Alarms Address: 2 Weston St.Wilbraham,MA 01095 Phone: 413-543-9090 Fax: N/A E-mail: Jack@wel-design.com Monitoring organization: AiaC7W 41tr'Jait/ Address: Phone: 44/S ..slfr 7'/ ZO I.ac F:-mail. Account number: 4$7? Phone line I Phone line 2: Means oftransmission: Cititi. QADrp Entity to which alarms are retransmitted: Phone 3. DOCUMENTATION On-site location of the required record documents and site-specific software: 4. DESCRIPTION OF SYSTEM OR SERVICE 4.1 Control t nit Manufacturer: Nolo Model number: NFS2-640 4.2 Software and Firmware Firmware revision number: 27 4.3 System Power 4.3.1 Primary(Main)Power Nominal voltage: 120Volts Amps: 2.6 Location: Main Electric room Overcurrent protection type: Breaker Amps: 20 Disconnecting means location: PP21L-42 Copynght 0 2012 National Fre Protection Assooation This form may be coped for individual use other than for resale It may not be coped for commercial sate or Cistnbution SYSTEM RECORD OF INSPECTION AND TESTING (continued) 4. DESCRIPTION OF SYSTEM OR SERVICE (continued) 4.3.2 Secondary Power Type: S.L.A I.ocauiin inside FRCP Battery type(if applicable): Calculated capacity of batteries to drive the s\stem: In standby mode(hours): In alarm mode(minutes): 5. NOTIFICATIONS MADE PRIOR TO TESTING Monitoring organization Contact Yes 'Time: 7:00 Building management Contact: YES Time: 7:00 Building occupants Contact: Yes Time: 7:00 Authority having jurisdiction Contact: Time: Other,if Contact: Time: required 6. TESTING RESULTS 6.1 Control I. nit and Related Equipment Visual Functional Description Inspection Test Comments Control unit ❑ ® Good Lamps/LEDs/LCDs 0 ® Good Fuses ❑ Good Trouble signals ❑ ® Good Disconnect switches ❑ 0 Good Ground-fault monitoring ❑ ® _ Good Supervision ❑ ® Good Local annunciator ❑ ® Good Remote annunciators ❑ ❑ N/A Remote power panels ❑ ❑ N/A ❑ ❑ 6.2 Secondary Power Visual Functional Description Inspection Test Comments Battery condition ❑ ® Good Load voltage ❑ 0 Good Discharge test ❑ ® Good Charger test ❑ ® Good Remote panel batteries ❑ ® Good Copynght cC 2012 National Fne Protection Assouation This torn may be copied for indmrdual use other than for resale It may not be coped for commeroat sale or distnbubon (p. 2 of 4) SYSTEM RECORD OF INSPECTION AND TESTING (continued) 6. TESTING RESULTS (continued) 6.3 Alarm and Supervisory Alarm Initiating Device Attach supplementary device test sheets for all initiating devices. 6.4 Notification Appliances Attach supplementary appliance test sheets for all notification appliances. 6.5 Interface Equipment Attach supplementary interface component test sheets for all interface components. Circuit Interface/Signaling Line Circuit Interface/Fire Alarm Control Interface 6.6 Supervising Station Monitoring Description Yes No Time Comments Alarm signal ❑ ® N/A Alarm restoration ❑ ® N/a Trouble signal 0 ® N/A Trouble restoration ❑ ® N/A Supervisory signal 0 ® N/A Supervisory restoration ❑ 0 N/A 6.7 Public Emergency Alarm Reporting System Description Yes No Time Comments Alarm signal ® 0 12 00 Good Alarm restoration 0 0 12 00 , Good Trouble signal ® 0 12.00 Good Trouble restoration 0 0 12.00 Good Supervisory signal ® 0 12.00 Good ___ Supervisory restoration ® 0 12.00 Good Copyright C 2012 National Fre Protection Association This form may be copied for individual use other than for resale It may not be copied for commercial sale or Otstnbuuon NOTIFICATION APPLIANCE POWER PANEL SUPPLEMENTARY RECORD OF COMPLETION This form is a supplement to the System Record of Completion. It includes a list of types and locations of notification appliance power extender panels This form is to be completed by the system installation contractor at the time of system acceptance and approval it shall be permitted to modify this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Form Completion Date: 12/10/2021 Number of Supplemental Pages Attached: 0 1. PROPERTY INFORMATION Name of propert\: North Commons Address: 140()dander Dr.Northampton, Ma 2. NOTIFICATION APPLIANCE POWER EXTENDER PANELS Make and Model Location Area Served Power Source Potter PSN-106 2n0 Floor 2'Floor EP11L-7 Potter PSN-106 3id Floor 3'd Floor and Attic PP12L-18 &kaki GODI.boGIt See\lain Ss stem Record of Completion for additional information,certifications,and approsals. Copyright t 2012 National Fre Protection Association This form may be copied for individual use other than for resale it may not be coped for commercial sale or dtstnbution SYSTEM RECORD OF COMPLETION This form is to be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Attach additional sheets,data,or calculations as necessary to provide a complete record. Form Completion Date: 12/10/2021 Supplemental Pages Attached: 1. PROPERTY INFORMATION Name of property: North Commons Address: 140 Olander Dr, Northampton.Ma Description ot'property: Housing Name of property representative: Address: Phone: Fax: E-mail: 2. INSTALLATION,SERVICE,TESTING,AND MONITORING INFORMATION Installation contractor: Gable Electric Address: 5 Westview Rd,Pittsfield,Ma 01201 Phone: 413-443-4082 Fax: E-mail: Service organization: Address: Phone: Fax: E-mail: Testing organization: Wel-Design Alarms Address: 2 Weston Street,Wilbraham,Ma Phone: 413-543-9090 Fax: E-mail: Effective date for test and inspection contract: Monitoring organization: Address: Phone: Fax: E-mail: Account number: Phone line I: Phone line 2: Means of transmission: Entity to which alarms are retransmitted: Phone: 3. DOCUMENTATION On-site location of the required record documents and site-specific software: 4. DESCRIPTION OF SYSTEM OR SERVICE This is a: ®New system ❑Modification to existing system Permit number: NFPA 72 edition: 2013 4.1 Control l nit Manufacturer: Notifier Model number: NFS2-640 4.2 Software and Firmware Firmware recision number: 27 4.3 Alarm Verification ®This system does not incorporate alarm verification. Number of devices subject to alarm verification: Alarm verification set for seconds Copyright 02012 National Fire Protection Assooation This form may be copied for individual use othhe than for resale it may not be copied for commercial sale or disc 11rcn. (p. 1 of 3) SYSTEM RECORD OF COMPLETION (continued) 5. SYSTEM POWER 5.1 Control Unit 5.I.1 Primary Power Input voltage of control panel: 120 Control panel amps: 2 6 Overcurrent protection: Type: Breaker Amps: 20 Branch circuit disconnecting means location: Main Electric Room Number: PP21 L-42 5.1.2 Secondary Power Type of secondary power: Battery Location,if remote from the plant: Calculated capacity of secondary power to drive the system: In standby mode(hours): In alarm mode(minutes): 5.2 Control Unit ❑ This system does not have power extender panels ® Power extender panels are listed on supplementary sheet A 6. CIRCUITS AND PATHWAYS Pathway Type Dual Media Pathway Separate Pathway Class Survivability Level Signaling Line B Device Power Initiating Device B Notification Appliance Other(specify): 7. REMOTE ANNUNCIATORS Type Location 8. INITIATING DEVICES 1 Addressable or Type Quantity Conventional Alarm or Supervisory Sensing Technology Manual Pull Stations 14 Addressable Alarm Manua. Smoke Detectors 182 Addressable Alarm/Supervisory Photo Duct Smoke Detectors 6 Addressable Alarm In Duct Photo Heat Detectors Gas Detectors 55 Addressable Supervisory C 0 Waterflow Switches 5 Addressable Alarm Mechanical Tamper Switches 9 Addressable Supervisory Manual Copyright c 2012 National Fire Protection Association This form may be copied for individual use other than for resale it may not be coped for commercial sale or distribution SYSTEM RECORD OF COMPLETION (continued) 9. NOTIFICATION APPLIANCES Type Quantity Description Audible 131 Sounder Bases Visible 13 Strobe Only Combination Audible and Visible 27 H/S 10. SYSTEM CONTROL FUNCTIONS Type Quantity Hold-Open Door Releasing Devices HVAC Shutdown 3 Fire/Smoke Dampers 1 Door Unlocking Elevator Recall 3 Elevator Shunt Trip 11. INTERCONNECTED SYSTEMS ® This system does not have interconnected systems. ❑ Interconnected systems are listed on supplementary sheet 12. CERTIFICATION AND APPROVALS 12.1 System Installation • ctor This system as ,. itied r••••n installed according to all NFPA standards cited herein. I/7/2A2.2.. Signed: ,►irj: MOW Printed name: ( )r m\7 bei C#Si Date: 4+?1 2C21 Organization:• able Title: Electrician Phone: 413-443-4082 12.2 System Operational Test This system as specified herein has tested according to all NFPA standards cited herein. i/7f2OZ2- Signed: 'icha�d Godbout Printed name: Richard Godbout Date: 12113772t24 Organization: Wel-Design Alarms Title: Tech/Electrician Phone: 413-543-9090 12.3 Acceptance Test Date and time of acceptance test: Installing contractor represen tive: Testing contractor represent ve: / Property representative: AHJ representative: ;jd J— 7— Copyright 0 2012 National Fre Protection Association This form may be coped for individual use other than for resale It may not be coped for commeraal sale or tlistnbuuon (p. 3of3) CONTRACTOR'S MATERIAL TEST CERTIFICATE FOR ABOVEGROUND PIPING PROCEDURE Upon completion of work,inspection and tests shall be made by the contractors representative and witnessed by the property owner or their authorized representative. All defects shall be corrected and system left in service before contractors personnel finally leave the job. A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities,owners and contractor. It is understood the property owners authorized representative's in no way prejudices any claim against contractor for faulty material,poor workmanship,or failure to comply with approving auttroritys requirements or local ordinances. Once the system(s)are in service the property owner/owners representative accepts full responsibility for the system as installed and agrees that it is in compliance with the applicable approving authontiys requirements and local ordinances. PROPERTY NAME DATE North Commons 1 Z _ 13 _ Z PROPERTY ADDRESS 140 Olander Drive - Northampton, Massachusetts ACCEPTED BY APPROVING AUTHORITIES NAMES Local AHJ ADDRESS PLANS Northampton, Ma INSTALLATION CONFORMS TO ACCEPTED PLANS X YES NO EQUIPMENT USED IS APPROVED X YES NO IF NO,EXPLAIN DEVIATIONS HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT IF NO,EXPLAIN i X i YES i NO INSTRUCTIONS HAVE COPIES OF THE FOLLOWING BEEN GIVEN TO THE PROPERTY OWNER OR PROPERTY OWNER'S AUTHORIZED REPRESENTITIVE? 1.SYSTEM COMPONENTS INTRUCTIONS: X YES NO 2.CARE AND MAINTENANCE INSTRUCTIONS: X YES NO 3. NFPA 25: X YES NO SUPPLIES BLDGS. LOCATION OF SYSTEM Complet Building MAKE MODEL MANUFACTURE ORIFICE SIZE/ QUANTITY TEMPERATURE RATING YEAR K-FACTOR Reliable Pendent RFC5B 2021 5.8 517 165' Reliable-CC Sprinkler KFR-CCS 2021 5.6 346 212° SPRINKLERS Reliable-Pendent G5-56 2021 5.6 137 212° Reliable-Sidewall DDH56 2021 5.6 1 200° Reliable Upright F3QR56 2021 5.6 227 200° Reliable-Res Sidewall RFC42 2021 4.2 35 165° PIPE CONFORMS TO NFPA STANDARD x YES NO FITTINGS CONFORM TO NFPA STANDARD x YES NO PIPE AND FITTINGS - IF NO,EXPLAIN: ALARM DEVICE MAXIMUM TIME TO OPERATE THROUGH TEST CONNECTION MAKE/BRAND TYPE MODEL MIN. SEC. Potter- Main Flow VSR-F 'ZS ALARM VALVE OR FLOW Potter- First Flow VSR-F INDICATOR Z Potter-Second Flow VSR-F Z6 Potter-Third Flow VSR-F 3u Potter-Attic Flow VSR-F /7V DRY VALVE Q.O.D. v MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. DRY PIPE OPERATING TIME TO TRIP THRU TEST WATER TRIP POINT TIME WATER ALARM TEST CONNECTION ('a,'b) PRESSURE AIR PRESSURE AIR REACHED TEST OPERATED PRESSURE OUTLET PROPERLY MIN. SEC. PSI. PSI. PSI. MIN. SEC. YES NO Without D.O.D. With Q.O.D N/A IF NO,EXPLAIN 'a=Measured from time inspector's test connection is completely opened OPERATION PNEUMATIC ELECTRIC 'HYDRAULICS DELUGE&PREACTION PIPING SUPERVISED 'YES NO I DETECTING MEDIA SUPERVISED YES NO VALVES DOES VALVE OPERATE FROM THE MANUAL TRIP,REMOTE,OR BOTH CONTROL STATIONS? YES NO IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTING? IF NO,EXPLAIN nYES E NO N/A MAKE MODEL DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT MAXIMUM TIME TO OPERATE RELEASE SUPERVISION LOSS ALARM? OPERATE VALVE RELEASE? YES NO YES NO MINUTES SECONDS HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 psi(1 .6 bars)for two hours or S(Tpsi(3.4 bars) above static pressure in excess of 150 psi(10.2 bars)for two hours. Differential dry-pipe valve clappers shall be left open during test to prevent damage. All aboveground piping leakage shall be stopped. FLUSHING: Flow the required rate until water is clear as indicated by no collection of foreign material In burlap bags at TEST DESCRIPTION outlets such as hydrants and blow-offs. Flush at flows not less than 390 GPM for 4-inch pipe,880 for 6-inch pipe,1,560 for 8-inch Pipe,2,440 GPM for 10-inch pipe,and 3,520 for 12-inch pipe. When supply cannot produce stipulated flow rates,obtain maximum available. PNEUMATIC: Establish 40 psi(2.7 bars)air pressure and measure drop which shall not exceed 1-112 psi(0.1 bars)in 24 tours Test pressure tanks at normal water level and air pressure and measure air pressure drop which shall not exceed 1-1/2 psi(0.1 bars)in 24 hours. ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HRS. IF NO,STATE REASON. DRY PIPING PNEUMATICALLY TESTED I X IVES I INO I DRY PIPING PNEUMATICALLY TESTED AT PSI FOR 24 HRS. EQUIPMENT OPERATES PROPERLY I X 'YES I INO I DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSION CHECMICALS.SODIUM SILICATE OR DERIVATIVES OF SODIUM SILICATE,BINE,OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING SYSTEMS OR STOPPING OF LEAKS? I X IYES I INO I READING OF GAUGE LOCATED NEAR WATER SUPPLY TEST RESIDUAL PRESSURE WITH VALVE IN TEST TESTS DRAIN TEST CONNECTION -STATIC PRESSURE I S L PSI CONNECTION OPEN WIDE. PSI Underground mains and lead-in connections to system risers flushed before connection made to sprinkler piping. VERIFIED BY COPY OF THE CONTRACTOR'S MATERIAL AND TEST X IYES I INO OTHER EXPLAIN CERTIFICATE FOR UNDERGROUND PIPING, FLUSHED BY INSTALLER OF UNDER GROUND X IYES I INO SPRINKLER PIPING: IF POWDER-DRIVEN FASTENERS ARE USED IN IF NO,EXPLAIN CONCRETE.HAS A REPRESENTATIVE SAMPLE TESTING BEEN SATISFACTORILY COMPLETED? IYES IX INO BLANK TESTING NUMBER USED LOCATIONS NUMBER REMOVED GASKETS 0 0 WELDING PIPING X I YES( NO IF YES DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES USED COMPLIED WITH THE X I YES I INO MINIMUM REQUIREMENTS OF AWS B2.1,ASME SECTION IX WELDING AND BRAZING QUALIFICATIONS,OR OTHER APPLICABLE QUALIFICATION STANDARD AS REQUIRED BY THE AHJ? DO YOU CERTIFY THAT ALL WELDING WAS PERFORMED BY WELDERS OR WELDING OPERATORS QUALIFIED IN X I YES I INO WELDING ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF AWS B2.1,ASME SECTION IX WELDING AND BRAZING QUALIFICATIONS,OR OTHER APPLICABLE QUALIFICATIONS STANDARD AS REQUIRED BY THE NO? DO YOU CERTIFY THAT WELDING WAS CONDUCTED IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL X I YES I INO PROCEDURE TO ENSURE THAT(1)ALL DISCS ARE RETRIEVED;(2)THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAGE AND OTHER WELDING RESIDUE ARE REMOVED;(3)THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED;(4)COMPLETED WELD ARE FREE FROM CRACKS,INCOMPLETE FUSION,SURFACE POROSITY GREATER THAN 1/16 IN.DIAMETER,UNDERCUT DEEPER THAT THE LESSER OF 25%OF THE WALL THICKNESS OR 1/32 IN.;(5)COMPLETED CORCUMFERENTIAL BUTT WELD REINFORCEMENT DOES NOT EXCEED 3/32 IN? CUTOUTS(DISCS) DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS(DISCS) X I YES I INO ARE RETRIEVED? NAMEPLATE PROVIDED: IF NO,EXPLAIN HYDRAULIC DATA UYESU NO NAMEPLATE SPRINKLER CONTRACTOR REMOVED ALL PROTECTIVE CAPS AND STRAPS? x YES NO DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN: I REMARKS NAME OF SPRINKLER CONTRACTOR: I Legacy Fire Protection, Inc. TESTS WITNESSED BY THE PROPERTY OWNER OR THEIR AUTHORIZED AGENT TITLE DATE (SIGN ). SIGNATURES crb �� � I� DATE / C FOR SPRINKLER TRA' R(SIGNED) TITLE DATE FOR FIRE o ARTMENT(SIGNED) C01r(WWL 12— 13 - 'a-)TITLE DATE _ f7— F lib i e• ' 13-,7/ ADDITIONAL EXPLANATION AND NOTES: I Hydrostatic Test Date: 1 2 — 1 i...; -a 1 L" g W� City of Northampton Partial Certificate of Use and Occupancy This is to certify that work granted under 780 CMR,9th Edition of the Massachusetts State Building Code, allowing the occupancy of use of the premises or Structure or part thereof located at address below as shown on the Assessor's Map. Owner: NORTH COMMONS (a VILLAGE HILL, LLC. Location: 140 OLANDER DR. Permit Number: BP-2021-0246 Construction Type (780 CMR Table 602): 5A Use Group Classification (780 CMR 3): R-2 Occupant Load Per Floor (780 CMR Table 1004.1.2): 200 Square Feet Per Person Live Load Per Floor (780 CMR Table 1607.1): 40 PSF Under the following limitations, special stipulations, and/or conditions of the permit: Construct 53 Unit Dwelling Facility—Ok to Occupy(Excludes Units#116,#218 & #319) Issued this 10th day of January 2022 Northampton Building Inspector(Name):_Jonathan S. Flagg Northampton Building Inspector(Signature): i i (t i Ii This Certificate shall be posted by owner, in a pehnanent manner and in a visible location, on all floors designated as use group H, S, M, F, or B, and in every room where practicable of use group A, I, R-1, or R-2 per the requirement of 780 CRM section 120.5 Posting Structures. ty,,..',' i j , 1,- -4 , , I ....,..e) ,,,......,,,,,,..., City of Northampton Partial Certificate of Use and Occupancy This is to certify that work granted under 780 CMR,9th Edition of the Massachusetts State Building Code, allowing the occupancy of use of the premises or Structure or part thereof located at address below as shown on the Assessor's Map. Owner: NORTH COMMONS (ai VILLAGE HILL, LLC. Location: 140 OLANDER DR. Permit Number: BP-2021-0246 Construction Type (780 CMR Table 602): 5A Use Group Classification (780 CMR 3): R-2 Occupant Load Per Floor (780 CMR Table 1004.1.2): 200 Square Feet Per Person Live Load Per Floor (780 CMR Table 1607.1): 40 PSF Under the following limitations, special stipulations, and/or conditions of the permit: Construct 53 Unit Dwelling Facility—Ok to Occupy (Excludes Units#116,#218 & #319) Issued this 10th day of January 2022 Northampton Building Inspector(Name):_Jonathan S. Flagg 6 Northampton Building Inspector(Signature): 9 ti,A,, 2 , V 6 This Certificate shall be posted by owner, in a permanent manner and in a visible location, on all floors designated as use group H, S,M, F, or B, and in every room where practicable of use group A, I, R-1, or R-2 per the requirement of 780 CRM section 120.5 Posting Structures. SYSTEM RECORD OF INSPECTION AND TESTING This form is to be completed by the system inspection and testing contractor at the time of a system test It shall be permitted to modify this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Attach additional sheets,data,or calculations as necessary to provide a complete record. Inspection/Test Start Date/rime: 12/10/2021. 7:00 Inspection/Test Completion Date/Time: 12/10/2021 21:00 Supplemental Form(s)Attached: YES (yes/no) 1. PROPERTY INFORMATION Name of property: North Commons Address: 140 Orlander Dr,Northampton,Ma Description of property: Housing Name of property representative: Address: Phone: Fax: E-mail: 2. TESTING AND MONITORING INFORMATION Testing organization: Wel-Design Alarms Address: 2 Weston St.Wilbraham,MA 01095 Phone: 413-543-9090 Fax: N/A E-mail: Jack@wei-design.com Monitoring organization: A/0477j Mfpr Krtitir Address: Phone: '///•,3117 Jar I ,t\ E-mail Account number: as-A 3 ('hone line I: Phone line 2: Means of transmission: LEL L JZQD/G Entity to which alarms are retransmitted: Phone: 3. DOCUMENTATION On-site location of the required record documents and site-specific software: 4. DESCRIPTION OF SYSTEM OR SERVICE 4.1 Control t nit Manufacturer: Notifier Model number: NFS2-640 4.2 Software and 1•irm.%are Firmware revision number: 27 4.3 System l'osscr 4.3.1 Priman (slain)Power Nominal voltage: 120Volts Amps: 2.6 Location: Main Electric room Overcurrent protection type: Breaker Amps: 20 Disconnecting means location: PP21 L-42 Copyright C 2012 National Fre Protection Association This form may be copied for me Jai use other than for resale It may not be coped for cOmmercal sale Of dishaturon. (p. 1 of 4) SYSTEM RECORD OF INSPECTION AND TESTING (continued) 4. DESCRIPTION OF SYSTEM OR SERVICE (continued) 4.3.2 Secondary Power Type: S L.A Location: inside FACP Battery type(if applicable): Calculated capacity of batteries to drive the system: In standby mode(hours): In alarm mode(minutes): 5. NOTIFICATIONS MADE PRIOR TO TESTING Monitoring organization Contact: Yes Time: 7:00 Building management Contact: YES Time: 7:00 Building occupants Contact: Yes Time: 7:00 Authority having jurisdiction Contact: Time: Other,if Contact: Time: required 6. TESTING RESULTS 6,I Control I nit and Related Equipment Visual Functional Description Inspection Test Comments Control unit ❑ ® Good Lamps/LEDs/LCDs ❑ ® Good Fuses ❑ ❑ Good Trouble signals ❑ ® Good Disconnect switches ❑ ® Good Ground-fault monitoring ❑ ® Good Supervision ❑ ® Good Local annunciator ❑ ® Good Remote annunciators 0 0 N/A Remote power panels ❑ ❑ N/A 0 ❑ 6.2 Secondar' Power Visual Functional Description Inspection Test Comments Battery condition ❑ ® Good Load voltage 0 ® Good Discharge test 0 ® Good Charger test 0 ® Good Remote panel batteries ❑ ® Good Copyright ct',2012 Natrona)F re Protection Association.This form may be copied for individual use other than for resale It may not be copied for commercial sale or distribution fp 2 of 4) SYSTEM RECORD OF INSPECTION AND TESTING (continued) 6. TESTING RESULTS (continued) 6.3 Alarm and Supervisory: larnr Initiating Del ice Attach supplementary device test sheets for all initiating devices. 6.4 Notification Appliances Attach supplementary appliance test sheets for all notification appliances. 6.5 Interface Equipment Attach supplementary interface component test sheets for all interface components. Circuit Interface/Signaling Line Circuit Interface/Fire Alarm Control Interface 6.6 Supervising Station Monitoring Description Yes No Time Comments Alarm signal ❑ 0 N/A Alarm restoration 0 0 N/a Trouble signal 0 0 N/A Trouble restoration ❑ 0 N/A Supervisory signal ❑ 0 N/A Supervisory restoration i ❑ ® N/A 6.7 Public Emergency Alarm Reporting System Description Yes No Time Comments Alarm signal ® ❑ 12.00 Good Alarm restoration ❑ 0 12 00 Good Trouble signal 0 0 12.00 Good Trouble restoration 0 0 12:00 Good Supervisory signal ® 0 12 00 Good Supervisory restoration 0 0 12 00 Good Copyrignt C 2012 National Fire Protection Association This form may be copied for individual use other than for resale It may not be copied for commercial sale or dlstnbution Ip.3 of 4) NOTIFICATION APPLIANCE POWER PANEL SUPPLEMENTARY RECORD OF COMPLETION This form is a supplement to the System Record of Completion. It includes a list of types and locations of notification appliance power extender panels This form is to be completed by the system installation contractor at the time of system acceptance and approval. it shall be permitted to modify this form as needed to provide a more complete and/or clear record Insert N/A in all unused lines. inn Completion Date: 12/10/2021 Number of Supplemental Pages Attached: 0 1. PROPERTY INFORMATION Name of property: North Commons Address: 140 Orlander Dr,Northampton, Ma 2. NOTIFICATION APPLIANCE POWER EXTENDER PANELS Make and Model Location Area Served Power Source Potter PSN-106 2nd Floor 2'Floor EP11L-7 Potter PSN-106 3f°Floor 3rd Floor and Attic PP12L-18 Go 'bocci See slain System Record of Completion for additional information,certifications,and appros als. Copyright 3w'2012 National Fire Protection Association This form may be copied for individual use other than for resale It may not be copied for commercial sate or dtstnbution tp. 1 of 1) SYSTEM RECORD OF COMPLETION This form is to be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modem this form as needed to provide a more complete and/or clear record Insert N/A in all unused lines. Attach additional sheets,data,or calculations as necessary to provide a complete record. Form Completion Date: 12/10/2021 Supplemental Pages Attached: 1. PROPERTY INFORMATION Name of property: North Commons Address: 140 Olander Dr.Northampton.Ma Description of property: Housing Name of property representative: Address: Phone: Fax: E-mail: 2. INSTALLATION,SERVICE,TESTING,AND MONITORING INFORMATION Installation contractor: Gable Electric Address: 5 Westview Rd,Pittsfield,Ma 01201 Phone: 413-443-4082 Fax: E-mail: Service organization: Address: Phone: Fax: E-mail: Testing organization: Wel-Design Alarms Address: 2 Weston Street,Wilbraham,Ma Phone: 413-543-9090 Fax: E-mail: Effective date for test and inspection contract: Monitoring organization: Address: Phone: Fax: E-mail: Account number: Phone line I: Phone line 2: Means of transmission: Entity to which alarms are retransmitted: Phone: 3. DOCUMENTATION On-site location of the required record documents and site-specific software: 4. DESCRIPTION OF SYSTEM OR SERVICE This is a: 0 New system 0 Modification to existing system Permit number: NFPA 72 edition: 2013 4.1 Control Unit Manufacturer: Notifier Model number. NFS2-640 4.2 Software and Firmware Firmware revision number: 27 4.3 Alarm Verification El This system does not incorporate alarm verification. Number of devices subject to alarm verification: Alarm verification set for seconds Copynght A 2012 National Fire Protection Association This torm may be copied for mdrvidual use other than for resale it may not be copied for commeraal sake or distnbution (p. 1 of 3) • . SYSTEM RECORD OF COMPLETION (continued) 5. SYSTEM POWER 5.I ( untrol I. nit 5.1.1 Primary Power Input voltage of control panel: 120 l ontrol panel amps: 2.6 Overcurrent protection: Type: Breaker Amps: 20 Branch circuit disconnecting means location: Main Electric Room Number: PP21L-42 3.1.2 Secundar. Purer Type of secondary power: Battery Location.if remote from the plant: Calculated capacity of secondary power to drive the system: In standby mode(hours): In alarm mode(minutes): 5.2 Control Unit ❑ This system does not have power extender panels Power extender panels are listed on supplementary sheet A 6. CIRCUITS AND PATHWAYS Pathway Type Dual Media Pathway Separate Pathway Class Survivability Level Signaling Line B Device Power Initiating Device g Notification Appliance Other(specify): 7. REMOTE ANNUNCIATORS Type Location 8. INITIATING DEVICES Addressable or Type Quantity Conventional Alarm or Supervisory Sensing Technology Manual Pull Stations 14 Addressable Alarn. Manual Smoke Detectors 182 Addressable Alarm/Supervisory Photo Duct Smoke Detectors 6 Addressable Alarm In Duct Photo Heat Detectors Gas Detectors 55 Addressable Supervisory C 0 Waterflow Switches 5 Addressable Alarm Mechanical Tamper Switches 9 Addressable Supervisory Manual Copyright 0 2012 National Fire Protection Assocation This form may be copied for individual use other than for resale It may not be coped for commercial sale or d,stnbubon (p. 2 of 3) SYSTEM RECORD OF COMPLETION (continued) 9. NOTIFICATION APPLIANCES Type Quantity Description Audible 131 Sounder Bases Visible 13 Strobe Only Combination Audible and Visible 27 HIS 10. SYSTEM CONTROL FUNCTIONS Type Quantity Hold-Open Door Releasing Devices HVAC Shutdown 3 Fire/Smoke Dampers 1 Door Unlocking Elevator Recall 3 Elevator Shunt Trip 11. INTERCONNECTED SYSTEMS ® This system does not have interconnected systems. 0 Interconnected systems are listed on supplementary sheet 12. CERTIFICATION AND APPROVALS 12.1 System Installation nt ctor This system as • iticd erei as °en installed according to all NFPA standards cited herein. Signed: Printed name: A'+tt be/i/Cgoir Date: 12/10/2021 Organization: able E nc Title: Electrician J Phone: 413-443-4082 12.2 System Operational Test This system as specified herein has tested according to all NFPA standards cited herein. Signed: chard God 0Git Printed name: Richard Godbout Date: 1 2/1 0//2021 Organization: Wel-Design Alarms Title: Tech/Electrician Phone: 413-543-9090 12.3 Acceptance Test Date and time of acceptance test: Installing contractor represent e: Testing contractor rep e: r 7:22, Property representative: AHJ representative: .7 Copyrght C 2012 National Fxe Protection Assooahon This form may be copied for tntlswdual use other than for resale It may not be copied for commercial sale or distribution