Loading...
Williams Street FP1NEW 2" GATE VALVE BY OTHERS T f PROPOSED APARTMENT BUILDING NEW 2" WATER SERVICED F PER NFPA 13. BY OTHERS r? J r 3 EXISTING FLOW HYDRANT SITE PLAN SCALE: 1"=40'-0" GAUGE HYDRANT ELEV: Y-O" LOWER THAN FIRST FLOOR NEW 22" FIRE DER CONNECTION. WATER FLOW INFORMATION ORIFICE: 21/2" INC14 COEFF: .90 PITOT: 75 PSI STATIC: 120 PSI _ RESIDUAL: 118 PSI FLOW: 1453 GPM ELEVATION: Y-0" FT LOCATION: 107 Williams Street Northam ton MA. CONDUCTED BY: Hampshire Fire Protection_ LLC, WITNESSED BY: Northampton Water Dpaaariment- TEST DATE: 11-14-2022 TEST TIME: 5%00 AM THIRD FLOOR ATTIC SPACE INSULATION BY OTHERS WIRE MESH BY OTHERS 2 x FRANIING BY OTHERS SPRINKLER PIPING DETAIL OF INSULATION NOT TO SCALE FIRST FLOOR SPRINKLER LEGEND SYM CNT MFG SIN STYLE RESPONSE. K ORIF NPT HEAD TEMP COVFR TEMP ESCUTCH GUARD FINISH NOTES Q 24 RELIABLE R3516 PENDENT QUICK 4.9 7/16" 1/2" 1750 N/A RECESSED N/A WHITE Model FIRES 49 (W4 Wrench) S 2 RELIABLE RA1414 PENDENT QUICK 5,6 1/2 1/2" 1750 N/A RECESSED NIA WHITE FIFR56 GFR2 Wrench 0 1 RELIABLE RA1425 UPRIGHT QUICK 5.6 1/2" 1/2" I750 N/A N/A N/A BRASS Model F1FR56 ®on sprigs W2 Wrench Q 2 RELIABLE RA1435 SIDEWALL QUICK 5.6 1/2" 1/2" 1750 N/A N/A N/A WHITE FIFR56 SIDEWALL-FI-GFR2 WREN- 5 RELIABLE R5734 DRY SIDE QUICK 5.6 1/2" 1/2" 1750 N/A N/A N/A WHITE F3QR56 F1 ESCH- XL02 WRENCH 2 VICTAULIC V3506 DRY FLEX PE QUICK 5.6 1/2 V 1750 N/A RECESSED N/A WHITE VIC.DRY PENDENT VB1 BRACKET SPRINKLER HEADS WITHIN T-6" OF ALL DIFFUSERS SHALL BE INTERMEDIATE TEMPERATURE SIDEWINDER A.T R. FOR 1 "-4" PIPE HANGER #2 Nor TO SCALE SUPER SCREW JI A-T.R. FOR I"-4" PIPE HANGER # I A NORTH ENTRY STAIR C SOUTH ENTRY STAIR D E EXPOSED PIPE 1a0A p 10013 L IVINGIDINING � - - ENTR tNTfE;Y �,�} ENTRY LIVINGfDINING 1D4A �I 1DIA I i01C 8'-IG' ___ 1D4C ! LIVINGIDINING 3-8 3-1Z -1 0 �I _", _ _ ® i 2-9 9 �i 1� - LD C J9 -5 AF 9'-5" �`1 F UP-5 -0 �F� fi 4. =uP - - - - '-5" AF �. � PEN ENT SP j`9-5 AF19� 9 5 AF _ -V1aTCHEN .--1 ` CL KITCHEN - - Y '`- 103E ! . r�'� e, r,'\ITCHEN T - - - T - - - - - �/ - - � '� � � � 103B � oI 00 I -_ - - �� � � Q'• 0 � � ao @ i T 1 %" UP TO SECOND T O> �� _ - _ _ = T�co 1%" UP T SECOND - a AND TH FLOOR LINEN , C ty 1 I AND THIRD FLOORS ,�'E 113a 4- f ?; I - - - - - I - - - - - - l A - I -AO D ' 3 1" DR FLEX r-228- i yLJ-3 4 9 ` ` 3 q 2-5 3� 3 - 9 4 2 10 CC)CLOSF7 HALL ,�'� �� oo l Z - -1 1 - 77 '�- c� ct tisl i" ° PE NT SP ' ERVYlose i 1 ^2A t C LINEN , 0 1-1 O ! I IL 14-7h '• 3-71 9- 1 Q 4-6 >\ o- I_ 11sc „3G �8'-6' AF I '• I T1 WJD I '� N - _ - 100C r-cri - 1''J `•+ �1 -11l 0 4- 3-7 I HALL I S'-6" AF 4 AI + 9'-5" AF - , , , 4-1 -1 T x DEN �I I i p �-' HALL 06 $ -Fi AF IDEA sosA C$�-6 AF � - � CID �s'-6 AF ERv iDBc 8'-6 AF] 105A 9'-S" AF]-- �_ CL z s'-lu $HWH , -o 9'-5" AF CID LO CL Is 9'-5" AF I l � 4_ o' 14" UP TO SECOND s - - FLOOR. y0 8'-I0 BATH _ ✓J, 57 .ft. CLOSET 107A 111A 8-1U BEDROOM -------- 1 i0A �'-10 DEN , -lQ �$ 1- 4 -=_ --- c CLOSET CLOSET 105E 5BATH CLOSET 112B 3� ---- 1078 111B BEDROOM i Eia i I-- '-10 110E -10 BEDROOM - BATH _ FIRST FLOOR PIPE SIZING IS BASED ON THE THIRD 11oc 58 .IL 2,-113, EN FLOOR HYDRAULIC CALCULATIONS. 107c 4 1U5C SPRINKLER ROOM 1UDC FIRPLI 20A T URN MA Tel P1 NOL tJ l� 1 1 �1 tl y L/iJ'li PIKE INDUSTRIAL ROAD, WESTFIELD, MA 01085 413---642-3287 - Fax 413-642-3792 SS LTC# SC105360 CT LTC# F11499 www.hampshiref2rellc. corm FIRST FLOOR PLAN SCALE: 3/16" =III WATER Static pressure 0 SUPPLY DATA psi Residual pressure 0 psi Flow gpm Location - Elevation - Date Time Information- by TROD RING SURGE RESTRA- -- A-,, I INSTALLED PER NFPA-13 1. AT THE END SPRINKLER ON A BRANCPLINE Z- ON ARMOVERS SUPPLYING SPRINKLERS IN THE PENDENT POSITION INSTALLED BELOW A CEILING: GREATER TPIAN 24" ON SYSTEMS LESS THAN 100 PSI GREATER TFIAN 12" ON SYSTEMS GREATER THAN 100 PSI SURGE RESTAINER NOT TO SCALE J „e O 1J N N N 1 1/2tr � o ©' `11 RB1 RB2 RB3 13 O N a FIRST FL. ELEV: 0'-0" ( l RISER DETAIL SCALE: l/2" = P-0" if l�1✓iC tSl1UlYM>✓1V 1 Jl:tiC.1JULr, i 2" COPPER WATER SERVICE. BY OTHERS. 2" GROOVED ELL WITH 1 1/2" REDUCER 1 I/2" AMES 2000B DOUBLE CHECK BACKFLOW WITH BALL VALVES W/ TAMPER SWITCH. 4 1" MAIN DRAIN ANGLE VALVE. l 1/2" FLOW SWITCH. Q I " AGF MODLE 1011 A TEST& DRAIN W/ RELIEF VALVE. (2) WATER GAGE KIT- 1 1/2" GRV'D CHECK VALVE. 9 1 1/2"NORMALLY CLOSED BUTTERFLY VALVE W/TAMPER SWITCH. 1 1/2" FEED TO WET SPRINKLER SYSTEM. 11 1 n MAIN DRAIN. 1 1/2" FEED TO THE 2 1/2" FIRE DEPARTMENT CONNECTION. 13 NEW PIPE STAND. ® 12 HEAD SPARE HEAD BOX. © 6" 120 VOLT ELECTRIC BELL. POSITIONING OF SPRINKLERS TO AVOID POSITIONING OF SPRINKLERS TO AVOID OBSTRUCTIONS TO DISCI-1ARGE(Residential Upright/Pendents) OBSTRUCTIONS TO DISCHARGE (SSU/SSP) )istance from Sprinklers to Maximum Allowable Distance Distance from Sprinklers to Maximum Allowable Distance ride of Obstructions of Deflector Above Bottom side of Obstructions of Deflector Above Bottom of Obstruction (in.) of Obstruction (in.) Less than I ft. 0 Less than I ft. 0 1 ft to less than I ft 6 in 0 1 ft to less than I ft 6 in 2 1/2 1 ft 6 in to less than 2 ft 1 I ft 6 into less than 2 ft 3 1/2 2 ft to less than 2 ft 6 in 1 2 ft to less than 2 ft 6 in 5 1/2 2 ft 6 in to less than 3 ft I 2 ft 6 into less than 3 ft 7 1/2 3 ft to less than 3 ft 6 in 3 3 ft to less than 3 ft 6 in 9 1/2 3 ft 6 in to less than O ft 3 3 ft 6 into less than 4 ft 12 4 ft to less than 4 ft 6 in 5 4 ft to less than 4 ft 6 in 14 4 ft 6 into less than 5 ft 7 4 ft 6 in to less than 5 ft 16 1/2 5 ft to less than 5 ft 6 in 7 5 It to less than 5 ft 6 in 18 5 ft 6 in to less than 6 ft 7 5ft6intoless than6ft 20 6 ft to less than 6 ft 6 in 9 6 ft to less than 6 ft 6 in 24 6 ft 6 into less than 7 ft 11 6 i t 6 in to less than 7 ft 30 7 ft to less than 7 ft 6 in 14 7 ft to less than 7 ft 6 in 35 GENERAL NOTES FOR RESIDENTIAL BUILDINGS: 1. SYSTEM INSTALLATION TO CONFORM TO NFPA-13R, 2013 EDITION. 2. OWNER IS REQUIRED TO PROVIDE HEAT THROUGHOUT THE BUILDING TO MAINTAIN A MINIMUM TEMPERATURE OF 40" FAHRENHEIT FOR ALL AREAS PROTECTED WITH A WET PIPE SPR24KLER SYSTEM, THE SYSTEM IS TO BE MAINTAINED BY THE OWNER AS REQUIRED BY NFPA-25. 3. MAIN PIPING: 3.1. NEW EXPOSED MAIN PIPING 1 1/2" AND 2" TO BE SCHEDULE 40 OR 10 BLACK PIPING WITH SHOP WELDED OUTLETS OR FIELD INSTALLED MECHANICAL TEES AND GROOVED ENDS AND FITTINGS IN AREA WITH EXPOSED PIPE. 4. BRANCHLINE PIPING: 4.1. NEW EXPOSED BRANCHLINE PIPING 1 1/2" & SMALLER, ARMOVERS, AND DROPS/SPRIGS TO NEW SPRINKLERS TO BE SCHEDULE 40 BLACK PIPING WITH THREADED ENDS AND CAST IRON FITTINGS WERE PIPING IS TO BE EXPOSED. 4.2. NEW WET SYSTEM CPVC BRANCHLINE PIPING AND FITTINGS 1 1/2" & SMALLER ARE TO BE USED IN AREAS WERE THE PIPING IS RUNNING ABOVE CEILINGS IN WALLS OR SOFFITS. 5, PIPING TO BE SUPPORTED AS REQUIRED BY NFPA-13 & 13R. HANGERS ARE TO BE FIELD LOCATED TO BEST SUPPORT THE PIPE. 6. STRUCTURAL LOAD BEARING ANALYSIS OF THE FIRE SPRINKLER SYSTEM AND ITS RELATED COMPONENTS HAVE NOT BEEN INCLUDED AS PART OF THIS CONTRACT. 7, WORK IS LIMITED TO SPRINKLER SCOPE INDICATED ON THESE DRAWINGS. 8. SPRINKLER SCOPE TO START AT THE 2" COPPER SERVICE IN RISER ROOM BY OTHERS. 9. ALL EXPOSED CPVC PIPING TO BE COVERED WITH SOFFITS BY OTHERS. 10. NEW PIPE DIMENSIONS ARE APPROXIMATE. INSTALLER TO VERIFY PIPE LENGTH IN FIELD. 11. OWNER TO MAINTAIN 18" OF CLEARANCE FROM SPRINKLER DEFLECTOR TO TOP OF PENDENT LIGHT FIXTURES & STORAGE. SURFACE MOUNTEI) LIGHT FIXTURE DEPTH SHALL NOT EXCEED 1" DEEP. 12. P DENOTES HYDRAULIC REFERENCE POINTS, 13. SYSTEM NOTES: 14- BUILDING CONSTRUCTION:COMBUSTIBLE WOOD FRAME RESIDENTIAL BUILDING. 15. OCCUPANCY: LIGHT HAZARD - APARTMENT BUILDING, USE GROUP R-2. 16. PER NFPA 13R SECTION 6.6.2 SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS OF 55 SQ- FT. AND LESS. 17. PER NFPA 13R SECTION 6.6.3 SPRINKLERS SHALL NOT BE REQUIRED IN CLOTHES CLOSETS, LINEN CLOSETS, AND PANTRIES WITHIN DWELLING UNITS THAT MEET ALL OF THE FOLLOWING CONDITIONS: (1) THE AREA OF THE SPACE DOES NOT EXCEED 24 FT. SQ. (2) THE LEAST DIMENSION DOES NOT EXCEED 3 FT. (3) THE WAILS AND CEILINGS ARE SURFACED WITH NONCOMBUSTIBLE OR LIMITED - COMBUSTIBLE MATERIALS AS DEFINED IN NFPA 220. 18. PER NFPA 13R SECTION 6.6.6 SPRINKLERS SHALL NOT BE REQUIRED IN ATTICS PENTHOUSE EQUIPMENT ROOMS, ELEVATOR MACHINE ROOMS, CONCEALED SPACES DEDICATED EXCLUSIVELY TO AND CONTAINING ONLY DWELLING UNIT VENTILATION EQUIPMENT, CRAWL SPACES,FLOOR/CEILING SPACES, NON COMBUSTIBLE ELEVATOR SHAFTS WHERE THE ELEVATOR CARS COMPLY WITH ANSI Al7.1 AND OTHER CONCEALED SPACES THAT ARE NOT USED OR INTENDED FOR LIVING PURPOSES OR STORAGE AND DO NOT CONTAIN FUEL -FIRED EQUIPMENT. 19. PER NFPA 13R SECTION 6.6.7 SPRINKLERS SHALL NOT BE REQUIRED IN CLOSETS (REGARDLESS OF SIZE) ON EXTERIOR BALCONIES AND EXTERIOR BREEZEWAYS/CORRIDORS-REGARDLESS OF SIZE, AS LONG AS THE CLOSET DOES NOT HAVE DOORS OR UNPROTECTED PENETRATIONS DIRECTLY INTO THE DWELLING UNITS. 20. DESIGN CRITERIA: 20.1 HYDRAULIC CALCULATIONS FOR APARTMENT IS BASED ON A 4 SPRINKLER HEAD CALCULATION AT A 0.05 DENSITY WITH 100 GPM HOSE STREAM & 80 GPM DOMESTIC USAGE. 21. SPRINKLER HEAD NOTES: 21.1 FIRST FLOOR FIRES 49 18' X 1S' SPACING, MAXIMUM 9'-0" OFF WALL, MAXIMUM, 18'-0" BETWEEN SPRINKLERS AND XI MINIMUM BETWEEN SPRINKLERS. Model Fi Res49 Residential Sprinkler & Models F1 F2, & FV Escutcheons SIN 113516 Technical Specifications Finishes Style: Pendent and Recessed Pendell (See Table N) Threads: 1/2' NPT or IS07-1 R112 Sensitivity Nominal K-Factor: 4.9 (ii metric) Fast -response Max. Working Pressure; 175 psi (12 bar) Temperature Ratings Material Specifications 176-F (79°C) Thermal Sensor: 3 mm glass -bulb Recessed Escutcheons Sprinkler Frame: Brass Alloy F1 Recessed Button: Copper Alloy F2 Recessed Sealing Assembly: Nickel Alloy with PTFE FV Recessed, Load Screw: Bronze A" Sprinkler Wrenches Deflector. Bronze Alloy Model W2 Model W4 (Recessed) -Note: Mosel ry escuteneons are not for use In posltrvely pressurizea Ceiling plenums. Model F1Res49 Residential Pendent Sprinkler Components and Installation Dimensions Face of 2-1/4" (57mm fitting to 2-1/4" (57mm Face of fitting to DIA. finiaF,ed DIA• finished 1-15/16" c9111n1 1-t5/i6" ceillnq 49mm) DIA. 5/8 49mm} DIA 1/2 (16mm) (13mm) k/- 1/4" ( m) (6 m) 2-1/4 (57) 1-5/8 1-3/4 (41 mm (44mm 1 ) 2-7/a" (72mm) DIA (9mm) -7/8" (72mm) DIA- (II Dimensions FI - Recessed Escutcheon Installation F2 & FV Recessed Escutcheon Installation Model F1Res49 Residential Pendent Sprinkler Hydraulic Design Criteria Minimum Flow and Residual Pressure in Wet Pipe Systems(1) Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (Iimin) Pressure psi (bar) Deflector to Ceiling Distance 12 x 12 (3.7 x 3.7) 13 (49) 7.0 (0.46) 1 to 4 inches (25 to 100 mm) 14 x 14 (4,3 x 4.3) 13 (49) 7.0 (0.48) 16 x 16 (4-9 x 4.9) 13 (49) 7.0 (0.48) 18 x 18 (5.5 x 5.5) 17 (64) 12-0 (0.83) 20 x 20 (6.1 x 6.1) 20 (76) 16.7 (1.15) 12 x 12 (17 x 3.7) 15 (57) 9.4 (0.65) 4 to B inches (100 to 200 mm) 14 x 14 (4.3 x 4.3) 16(61) 10.7(0.74) 16 x 16 (4-9 x 4.9) 17 (54) 12-0 (0.83) 16 x 18 (6,5 x 5.5) 19 (72) 15-0 (1.03) 20 x 20 (6.1 x 6.1) 22 (B3) 20.2 (1-39) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greeter of; (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpmisq ft over the design area of the sprinkler. 2. Far coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. SPRINKLERS Drawing GENERAL NOTES DETAILS AND FIRST FLOOR PLAN Title Project: WILLIAMS STREET APARTMENTS 107 WILLIAMS STREET NORTHAMPTON, MA. Total This Sheet Total This ,lob Symbol Description Contract No. 0 5 5 7 C MA Revisions: Date: 1 PERMIT PLANS 11-22-2022 Drawn By SL 3 Scale AS -NOTED 4 Contract with; FIVE STAR CORPORATION 123 UNION STREET EASTHAMPTON, MA. s Date 11-22-2022 6 Approval By BLDG DEPARTMENT & FIRE DEPARTMENT = JOHN 'F. VIOLA Q FIRE PROTECTION NO. 46515 Li�ZZL ME