Loading...
approval letter December 20, 2010December 20, 2010 John Zieminski 8 Woodridge Circle Hatfield, MA 01038 Subject Property: 138 Oak Street Northampton, MA 01062 Mr. Zieminski The plans for the 16 x 32 addition dated 12-18-10 have been approved as noted; Engineering for truss and LVL submitted before rough inspection. Structure must conform to 780 CMR 7th addition 1 and 2 family with 2009 IECC. Ceilings R-38 insulation after air ceiling. Walls R-20 cavity insulation or R-13 cavity and R-5 continuous. Existing walls exposed without insulation add R-3 per inch of wall. Floors R-30 or fill the cavity, but R-19 minimum. Push up rods 2’ O.C. Basement walls R-13 cavity or R-10 continuous. Slab R-10 for 2’ at perimeter, add R-5 at edge if radiant heated floor. Windows .35 U-Value. Smoke and CO per code, plan and as noted. A smoke and CO detector at the bottom of the stairs and a heat detector in the garage. Charles Miller Assistant Commissioner of Buildings