Greene, Leanne Planset
76 North Meadowbrook Drive
Scott E. Wyssling, PE Alpine, UT 84004
Coleman D. Larsen, SE, PE office (201) 874-3483
Gregory T. Elvestad, PE swyssling@wysslingconsulting.com
July 24, 2023
Current Insight
2852 W. Amini Way
South Jordan, UT 84095
Re: Engineering Services
Greene Residence
30 Water Street, Northampton MA
5.460 kW System
To Whom It May Concern:
We have received information regarding solar panel installation on the roof of the above referenced
structure. Our evaluation of the structure is to verify the existing capacity of the roof system and its ability
to support the additional loads imposed by the proposed solar system.
A. Site Assessment Information
1. Site visit documentation identifying attic information including size and spacing of framing
for the existing roof structure.
2. Design drawings of the proposed s ystem including a site plan, roof plan and connection
details for the solar panels. This information will be utilized for approval and construction
of the proposed system.
B. Description of Structure:
Roof Framing: Assumed 2x6 dimensional lumber at 16” on center.
Roof Material: Composite Asphalt Shingles
Roof Slope: 15 and 25 degrees
Attic Access: Inaccessible
Foundation: Permanent
C. Loading Criteria Used
• Dead Load
o Existing Roofing and framing = 7 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 10 PSF
• Dead Load
o Existing Roofing and framing = 7 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 10 psf
• Live Load = 20 psf (reducible) – 0 psf at locations of solar panels
• Ground Snow Load = 40 psf
• Wind Load based on ASCE 7-10
o Ultimate Wind Speed = 117 mph (based on Risk Category II)
o Exposure Category C
Analysis performed of the existing roof structure utilizing the above loading criteria is in accordance
with the 2015 IRC, including provisions allowing existing structures to not require strengthening if
the new loads do not exceed existing design loads by 105% for gravity elements and 110% for
seismic elements. This analysis indicates that the existing framing will support the additional panel
loading without damage, if installed correctly.
Page 2 of 2
D. Solar Panel Anchorage
1. The solar panels shall be mounted in accordance with the most recent Ironridge installation manual.
If during solar panel installation, the roof framing members appear unstable or deflect non -
uniformly, our office should be notified before proceeding with the installation.
2. The maximum allowable withdrawal force for a 5/16” lag screw is 229 lbs per inch of penetration as
identified in the National Design Standards (NDS) of timber construction specifications. Based on
a minimum penetration depth of 2½”, the allowable capacity per connection is greater than the
design withdrawal force (demand). Considering the variable factors for the existing roof framing
and installation tolerances, the connection using one 5/16” diameter lag screw with a minimum of
2½” embedment will be adequate and will include a sufficient factor of safety.
3. Considering the wind speed, roof slopes, size and spacing of framing members, and condition of
the roof, the panel supports shall be placed no greater than 48” on center.
Based on the above evaluation, this office certifies that with the racking and mounting specified, the existing
roof system will adequately support the additional loading imposed by the solar system. This evaluation is in
conformance with the 2015 IRC, current industry standards, and is based on information supplied to us at the
time of this report.
Should you have any questions regarding the above or if you require further information do not hesitate to
contact me.
Very truly yours,
Scott E. Wyssling, PE
MA License No. 50507
Massachusetts COA # 1629764
GENERAL NOTES1.1.1PROJECT NOTES:1.1.2THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE NATIONAL ELECTRICCODE (NEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING AND INSTALLATIONINSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITYHAVING JURISDICTION’S (AHJ) APPLICABLE CODES.1.1.3THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEMINSPECTED PRIOR TO PARALLEL OPERATION1.1.4ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVE INVERTERS, ANDSOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE INPHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC 690.4: PV MODULES: UL1703,IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIRE INVERTERS: UL 1741 CERTIFIED,IEEE 1547, 929, 519 COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY1.1.5MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMPCOEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATEDACCORDING TO NEC 690.7.1.1.6ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AND SOURCECIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILLBE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D). SHALL BEINSTALLED ACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING [NEC110.3].1.1.7ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. IFEXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGEWILL BE INSTALLED AS REQUIRED BY THE NEC AND AHJ.1.2.1 SCOPE OF WORK:1.2.2PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OFTHE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BERESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN,SPECIFY, AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THEPHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT.1.3.1 WORK INCLUDES:1.3.2PV ROOF ATTACHMENTS - IRONRIDGE FLASH VUE1.3.3PV RACKING SYSTEM INSTALLATION - IRONRIDGE AIRE RAIL A11.3.4PV MODULE AND INVERTER INSTALLATION - REC SOLAR REC420AA PURE-R / TESLASOLAR INVERTER 7.6 kW1.3.5PV EQUIPMENT GROUNDING1.3.6PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX1.3.7PV LOAD CENTERS (IF INCLUDED)1.3.8PV METERING/MONITORING (IF INCLUDED)1.3.9PV DISCONNECTS1.3.10PV FINAL COMMISSIONING1.3.11(E) ELECTRICAL EQUIPMENT RETROFIT FOR PV1.3.12SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE*NEC2020ISCOPE OF WORKSYSTEM SIZE: STC: 13 X 420W = 5.460kWPTC: 13 X 397.9W = 5.173kW(13) REC SOLAR REC420AA PURE-R(1) TESLA SOLAR INVERTER 7.6 kWATTACHMENT TYPE: IRONRIDGE FLASH VUEMSP UPGRADE: NOPROJECT INFORMATION:-SERVICE PHASE: SINGLE-SERVICE SIZE (AMPS): 200A-DISTANCE FROM UTILITY METER TO TRANSFORMER: 45 FT.-CONNECTIVITY TYPE: OVERHEAD-UTILITY METER NUMBER: #23593295SCOPE OF WORK:-INVERTER: (1) TESLA SOLAR INVERTER 7.6 kW-PANELS: (13) REC SOLAR REC420AA PURE-R-DC-STC RATING OF SYSTEM: 5.460 kWp-AC SYSTEM DESIGN CAPACITY (NOMINAL): 7.600 kWp-AC SYSTEM DESIGN CAPACITY (MAXIMUM): 7.600 kWp30 WATER STNORTHAMPTON, MA 01053ASSESSOR'S #: 10B-072-001NEW PV SYSTEM: 5.460 kWpLEANNE GREENE RESIDENCEOWNERNAME: LEANNE GREENEPROJECT MANAGERNAME:PATRICK RONDEAU PHONE:413-588-8185CONTRACTORNAME: VALLEY SOLAR LLCPHONE: 413-584-8844AUTHORITIES HAVING JURISDICTIONBUILDING: CITY OF NORTHAMPTONZONING: CITY OF NORTHAMPTONUTILITY: NATIONAL GRIDDESIGN SPECIFICATIONSOCCUPANCY: IICONSTRUCTION: SINGLE-FAMILYZONING: RESIDENTIAL GRID-TIEDGROUND SNOW LOAD: 40 PSFWIND EXPOSURE: CWIND SPEED: 117 MPHAPPLICABLE CODES & STANDARDSBUILDING: MASSACHUSETTS BUILDING CODE, 9TH EDITION, ASAMENDED (780 CMR)RESIDENTIAL:MASSACHUSETTS RESIDENTIONAL BUILDING CODE,9TH EDITION, AS AMENDED (780 CMR)ELECTRICAL: NEC 2023FIRE: MASSACHUSETTS COMPREHENSIVE FIRE SAFETYCODE (527 CMR 1.00)NFPA 1 FIRE CODE - 2021PROJECT INFORMATIONBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONST-001.00COVER PAGE(SHEET 1)PLAT MAP02SCALE: NOT TO SCALEAERIAL PHOTO01SCALE: NOT TO SCALENEWSSHEET LIST TABLESHEET NUMBERSHEET TITLET-001COVER PAGEG-001NOTESA-101SITE PLANA-102ELECTRICAL PLANA-103SOLAR ATTACHMENT PLANA-104INSTALLER REFERENCE PAGEE-601LINE DIAGRAME-602DESIGN TABLESE-603PLACARDSS-501ASSEMBLY DETAILSR-001RESOURCE DOCUMENTR-002RESOURCE DOCUMENTR-003RESOURCE DOCUMENTR-004RESOURCE DOCUMENTR-005RESOURCE DOCUMENTWATER STMILL RIV
E
R
Signed 7/24/2023
2.1.1SITE NOTES:2.1.2A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.2.1.3THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITYINTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.2.1.4THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDINGROOF VENTS.2.1.5PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICALEQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.2.1.6ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITHTHIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOFCOVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE.2.2.1EQUIPMENT LOCATIONS2.2.2ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.2.2.3WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATINGTEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLE 310.15 (B)(1).2.2.4JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO NEC690.34.2.2.5ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHINSIGHT OF THE AC SERVICING DISCONNECT.2.2.6ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TONEC APPLICABLE CODES.2.2.7ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHENAPPROPRIATE.2.3.1STRUCTURAL NOTES:2.3.2RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANTINSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES,AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THEARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS.2.3.3JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IFROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS.2.3.4ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/ APPROVEDCHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR.2.3.5ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCESPECIFIED BY THE RACKING MANUFACTURER.2.3.6WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGSTTHE ROOF FRAMING MEMBERS.2.4.1GROUNDING NOTES:2.4.2GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDINGDEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE.2.4.3PV SYSTEMS REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR. ALL METAL ELECTRICALEQUIPMENT AND STRUCTURAL COMPONENTS BONDED TO GROUND, IN ACCORDANCE WITH250.134 OR 250.136(A). ONLY THE DC CONDUCTORS ARE UNGROUNDED.2.4.4PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM NEC TABLE250.122.2.4.5METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURE CONSIDEREDGROUNDED IN ACCORD WITH 250.134 AND 250.136(A).2.4.6EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN INMANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED,MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLESPER THE MANUFACTURERS' INSTALLATION REQUIREMENTS.2.4.7THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVALOF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE.2.4.8GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN ORMARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]2.4.9THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50 THROUGH250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODESYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47 AND AHJ.2.4.10DC PV ARRAYS SHALL BE PROVIDED WITH DC GROUND-FAULT PROTECTION MEETING THEREQUIREMENTS OF 690.41(B)(1) THROUGH (3) TO REDUCE FIRE HAZARDS2.5.1INTERCONNECTION NOTES:2.5.2LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 705.12]2.5.3THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THERATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL NOT EXCEED 120PERCENT OF THE AMPACITY OF THE BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BELOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(3)(2)].2.5.4AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL RATING OF ALLOVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THECOMBINED OVERCURRENT DEVICE MAY BE EXCLUDED ACCORDING TO NEC 705.12 (B)(3)(3).2.5.5FEEDER TAP INTERCONNECTION (LOAD SIDE) ACCORDING TO NEC 705.12 (B)(1) AND (2)2.5.6SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.11 WITH SERVICE ENTRANCECONDUCTORS IN ACCORDANCE WITH NEC 230.422.5.7BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT FROMADDITIONAL FASTENING [NEC 705.12 (E)].2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:2.6.2DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THECONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINESIDE” (TYPICALLY THE UPPER TERMINALS).2.6.3DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE AVISIBLE-BREAK SWITCH.2.6.4BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED. THEREFORE BOTH MUSTOPEN WHERE A DISCONNECT IS REQUIRED, ACCORDING TO NEC 690.13.2.6.5ISOLATING DEVICES OR EQUIPMENT DISCONNECTING MEANS SHALL BE INSTALLED IN CIRCUITSCONNECTED TO EQUIPMENT AT A LOCATION WITHIN THE EQUIPMENT, OR WITHIN SIGHT ANDWITHIN 10 FT. OF THE EQUIPMENT. AN EQUIPMENT DISCONNECTING MEANS SHALL BEPERMITTED TO BE REMOTE FROM THE EQUIPMENT WHERE THE EQUIPMENT DISCONNECTINGMEANS CAN BE REMOTELY OPERATED FROM WITHIN 10 FT. OF THE EQUIPMENT, ACCORDINGTO NEC 690.15 (A).2.6.6PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWNFUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN ACCORDANCE WITH690.12(A) THROUGH (D)2.6.7ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND 240.2.6.8BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED, THEREFORE BOTHREQUIRE OVER-CURRENT PROTECTION, ACCORDING TO NEC 240.21. (SEE EXCEPTION IN NEC690.9)2.6.9IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TONEC 690.11 AND UL1699B.2.7.1WIRING & CONDUIT NOTES:2.7.2ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT ANDWIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANTTO LIMIT UP-SIZING.2.7.3ALL CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.2.7.4EXPOSED PV SOURCE CIRCUITS AND OUTPUT CIRCUITS SHALL USE WIRE LISTED ANDIDENTIFIED AS PHOTOVOLTAIC (PV) WIRE [690.31 (C)]. PV MODULES WIRE LEADS SHALLBE LISTED FOR USE ON PV ARRAYS, ACCORDING TO NEC 690.31 (A).2.7.5PV WIRE BLACK WIRE MAY BE FIELD-MARKED WHITE [NEC 200.6 (A)(5)].2.7.6MODULE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY.2.7.7ACCORDING TO NEC 200.7, UNGROUNDED SYSTEMS DC CONDUCTORS COLORED OR MARKEDAS FOLLOWS: DC POSITIVE-RED, OR OTHER COLOR EXCLUDING WHITE, GRAY AND GREENDC NEGATIVE- BLACK, OR OTHER COLOR EXCLUDING WHITE, GRAY AND GREEN2.7.8AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE*, OR OTHER CONVENTION NEUTRAL- WHITE OR GRAY*IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKEDORANGE [NEC 110.15].*NEC2020I BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONSG-001.00NOTES(SHEET 2)Signed 7/24/2023
A-101.00SITE PLAN(SHEET 3)ENTRANCEBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONS01/24" = 1'-0"SITE PLAN0112'24'NEWSNEWSAREA OF WORKPROPERTY LINEGENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGEWATER STUTILITY METERCUSTOMER OWNED PV METERMILL RIVER64'-9"6'-2"138'-6"58'-11"AC DISCONNECTSigned 7/24/2023
MODULE:REC SOLARREC420AA PURE-R420 WATTS44"68.1"BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONSA-102.00ELECTRICAL PLAN(SHEET 4)01/8" = 1'-0"ELECTRICAL PLAN014'8'AMODULE STRINGINGBMODULE STRINGINGGENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGE(N) (1) JUNCTION BOXFIRE CLEARANCESQUARE FOOTAGE OF ROOF: 1932.21 SQ. FT.SQUARE FOOTAGE OF ARRAY: 270.51 SQ. FT.PERCENTAGE OF ROOF COVEREDBY THE ARRAYS: 14%A(N) (1) BREAKER BOXINTERIOR PV EQUIPMENTARRAY 1 - 3.360[x8] (N) MODULESTILT: 15 DEGREESROOF PITCH: 3:12AZIMUTH: 83 DEGREESEXTERIOR PV EQUIPMENT(E) (1) UTILITY METER(E) (1) MAIN ELECTRICAL PANEL(N) (1) INVERTER(N) (1) CUSTOMER OWNED PV METERNEWS3 FT. FIRE ACCESS PATH3 FT. FIRE ACCESS PATH18 IN. FIRE ACCESS PATH18 IN. FIRE ACCESS PATH(N) (1) AC DISCONNECTAAAAAAABBBBBARRAY 2 - 2.100[x5] (N) MODULESTILT: 25 DEGREESROOF PITCH: 6:12AZIMUTH: 173 DEGREES
MODULE:REC SOLARREC420AA PURE-R420 WATTS44"68.1"BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONSA-103.00SOLAR ATTACHMENT PLAN(SHEET 5)01/8" = 1'-0"SOLAR ATTACHMENT PLAN014'8'ROOF RAFTERSGENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGEFLUSH MOUNT SOLAR MODULESATTACHED TO ROOF SURFACE (SEESHEET S-501 FOR MOUNTING DETAILS)ROOF MATERIAL IS ASPHALT SHINGLENEWS17'-0"14'-8"Signed 7/24/2023
BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONSA-104.00INSTALLER REFERENCEPAGE(SHEET 6)INSTALLER REFERENCE PAGE01SCALE: NOT TO SCALEGENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGESigned 7/24/2023
G40A3JUNCTIONBOX(5) TESLARAPID SHUTDOWN DEVICEPV SYSTEM EQUIPPED WITH RAPID SHUTDOWNAND COMPLIANT WITH NEC 690.12.TESLASOLAR INVERTER 7.6 kWRATED POWER 7600W(13) REC SOLARREC420AA PURE-R420WAC DISCONNECT60A4(E) GROUNDINGELECTRODEGROUNDROD(E)UTILITYMETERTAPNL2L1NGTO (E)LOADS(E) MAIN ELECTRICAL PANEL240/120 V 1Ø, 3WMAIN BUSS: 200ANOTE:READILY ACCESSIBLE OPEN BLADEAC SYSTEM DISCONNECT VISIBLE FROMAPPROACH TO RESIDENCE 60A 240VLOCATED EXTERIOR ON WALL NEARMETER NEMA 3R"# 23593295TO UTILITYGRID (OH)L2NL1(E)200A/2PAMODULE STRINGINGBMODULE STRINGINGF1-2G40A/2P70А BREAKER BOXCOMPLIES WITH NEC 240.2140ACB1POINT OF CONNECTIONPER NEC 705.11621B5A8L2NGGL1VLINE SIDETOP LUGSLOAD SIDEBOTTOM LUGS5CUSTOWEROWNEDPV METERNOTE:BOTTOM LUGS TO SOLARGENERATION (LOAD) TOP LUGS TOUTILITY (LINE) LOCATED EXTERIORCONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONSIDTYPICALCONDUCTORCONDUITCURRENT-CARRYINGCONDUCTORS IN CONDUITOCPDEGCTEMP. CORR.FACTORCONDUIT FILLFACTORCONT.CURRENTMAX. CURRENT(125%)BASE AMP.DERATEDAMP.TERM. TEMP. RATINGAMP. @ TERMINAL1210 AWG PV WIRE, COPPERFREE AIR2N/A6 AWG BARE, COPPER0.96 (32.7 °C)111.11A13.89A55A52.8A75°C50A2110 AWG THWN-2, COPPER0.5'' DIA EMT4N/A10 AWG THWN-2, COPPER0.96 (32.7 °C)0.811.11A13.89A40A30.72A75°C35A318 AWG THWN-2, COPPER0.75'' DIA EMT240A10 AWG THWN-2, COPPER0.96 (32.7 °C)132A40A55A52.8A75°C50A418 AWG THWN-2, COPPER0.75'' DIA EMT2N/A10 AWG THWN-2, COPPER0.96 (32.7 °C)132A40A55A52.8A75°C50A518 AWG THWN-2, COPPER0.75'' DIA EMT240A10 AWG THWN-2, COPPER0.96 (32.7 °C)132A40A55A52.8A75°C50A616 AWG THWN-2, COPPER0.75'' DIA EMT2N/A6 AWG THWN-2, COPPER0.96 (32.7 °C)132A40A75A72A75°C65AE-601.00LINE DIAGRAM(SHEET 7)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONS
SYSTEM SUMMARYINVERTER #1MPPT #1MPPT #2MODULES IN SERIES85ARRAY VMP400V250VARRAY IMP8.4A8.4AARRAY VOC475.2V297VARRAY MAX VOC533.4V333.4VARRAY ISC8.89A8.89AARRAY STC POWER5,460WARRAY PTC POWER5,173WMAX AC CURRENT32AMAX AC POWER7,600WDERATED (CEC) AC POWER5,044WDISCONNECTSINVERTERSOCPDSMODULESASHRAE EXTREME LOW-25.9°C (-14.6°F), SOURCE: BARNES MUNI (42.16°; -72.72°)ASHRAE 2% HIGH32.7°C (90.9°F), SOURCE: BARNES MUNI (42.16°; -72.72°)REF.QTY.RATED CURRENTMAX VOLTAGECB1140A240VACF1-2240A240VACREF.QTY.MAKE AND MODELRATED CURRENTMAX RATED VOLTAGESW11EATON DG222NRB OR EQUIV.60A240VACREF.QTY.MAKE AND MODELPMAXPTCISCIMPVOCVMPTEMP. COEFF. OF VOCFUSE RATINGPM1-1313REC SOLAR REC420AA PURE-R420W397.9W8.89A8.4A59.4V50V-0.143V/°C (-0.24%/°C)25AREF.QTY.MAKE AND MODELACVOLTAGEGROUNDOCPDRATINGRATEDPOWERMAX OUTPUTCURRENTMAX INPUTCURRENTMAX INPUTVOLTAGECEC WEIGHTEDEFFICIENCYI11TESLA SOLAR INVERTER 7.6 kW240VFLOATING40A7600W32A4x11A600V97.5%BILL OF MATERIALSCATEGORYMAKEMODEL NUMBERREFQTYUNITQTY/UNITDESCRIPTIONMODULEREC SOLARREC420AA PURE-RPM1-1313PIECES1REC SOLAR REC420AA PURE-R 420WINVERTERTESLASOLAR INVERTER 7.6 kWI11PIECE1TESLA SOLAR INVERTER 7.6 kW 7600W INVERTERDISCONNECTEATONDG222NRBSW11PIECE1EATON DG222NRB, FUSED, 2-POLE, 60A, 240VAC OR EQUIVALENTPRODUCTION METERGENERIC MANUFACTURERGEN-METER-80AM11PIECE1ELECTRICAL METER, OWNER APPROVEDWIRINGGEN-10-AWG-PV-WIRE-CUWR1180FEET110 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE)WIRINGGEN-6-AWG-BARE-CUWR190FEET16 AWG BARE, COPPER (GROUND)WIRINGGEN-10-AWG-THWN-2-CU-RDWR240FEET110 AWG THWN-2, COPPER, RED (POSITIVE)WIRINGGEN-10-AWG-THWN-2-CU-BLKWR240FEET110 AWG THWN-2, COPPER, BLACK (NEGATIVE)WIRINGGEN-10-AWG-THWN-2-CU-GRWR2-550FEET110 AWG THWN-2, COPPER, GREEN (GROUND)WIRINGGEN-8-AWG-THWN-2-CU-RDWR3-530FEET18 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-8-AWG-THWN-2-CU-BLKWR3-530FEET18 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-8-AWG-THWN-2-CU-WHWR3-530FEET18 AWG THWN-2, COPPER, WHITE (NEUTRAL)WIRINGGEN-6-AWG-THWN-2-CU-RDWR610FEET16 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-6-AWG-THWN-2-CU-BLKWR610FEET16 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-6-AWG-THWN-2-CU-WHWR610FEET16 AWG THWN-2, COPPER, WHITE (NEUTRAL)WIRINGGEN-6-AWG-THWN-2-CU-GRWR610FEET16 AWG THWN-2, COPPER, GREEN (GROUND)WIREWAYGEN-EMT-0.5'' DIAWW220FEET1EMT CONDUIT, 0.5'' DIAWIREWAYGEN-EMT-0.75'' DIAWW3-640FEET1EMT CONDUIT, 0.75'' DIAOCPDGENERIC MANUFACTURERGEN-CB-40A-240VACCB11PIECE1BREAKER, 40A, 240VACOCPDGENERIC MANUFACTURERGEN-FU-40A-240VACF1-22PIECES1FUSE, 40A, 240VACTRANSITION BOXGENERIC MANUFACTURERGEN-AWB-TB-4-4XJB11PIECE1TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKSE-602.00DESIGN TABLES(SHEET 8)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONS
FRONTBACK!CAUTION!POWER TO THIS BUILDING IS ALSO SUPPLIEDFROM ROOF MOUNTED SOLAR ARRAYS WITHSAFETY DISCONNECTS AS SHOWN:E-603.00PLACARDS(SHEET 9)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONSPV ARRAYSPV DISCONNECT (EXTERIOR)INVERTER (INTERIOR)MAIN DISTRIBUTIONUTILITY DISCONNECT (INTERIOR)ELECTRICAL SHOCK HAZARDTERMINALS ON THE LINE ANDLOAD SIDES MAY BE ENERGIZEDIN THE OPEN POSITIONWARNINGLABEL 1AT EACH DISCONNECTING MEANS FORPHOTOVOLTAIC EQUIPMENT (2" X 4").[NEC 690.13].POWER SOURCEOUTPUT CONNECTIONDO NOT RELOCATE THISOVERCURRENT DEVICEWARNINGLABEL 2AT POINT OF INTERCONNECTIONOVERCURRENT DEVICE (2" X 4").[NEC 705.12(B)(2)(3)(B)].LABEL 4AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRINGMETHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERESEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,OR FLOORS (5 3/4" X 1 1/8").[NEC 690.31(G)]LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;REFLECTIVE[IFC 605.11.1.1]RAPID SHUTDOWNSWITCH FORSOLAR PV SYSTEMLABEL 5AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2").[NEC 690.56(C)(3)].LABEL 9AT EACH AC DISCONNECTING MEANS(4" X 1").[NEC 690.13(B)].LABEL 10AT EACH DC DISCONNECTING MEANS(4" X 1").[NEC 690.13(B)].SOLAR PV SYSTEMEQUIPPED WITHRAPID SHUTDOWNTURN RAPID SHUTDOWN SWITCH TOTHE "OFF" POSITION TO SHUT DOWNPV SYSTEM AND REDUCE SHOCKHAZARD IN ARRAYSOLAR ELECTRICPV PANELSLABEL 3AT RAPID SHUTDOWN SYSTEM(3 3/4" X 5 1/4"). [NEC 690.56(C)(1)(A)].LABELING NOTES1.1 LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRICAL CODE,INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z5351.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVINGJURISDICTION.1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENTINVOLVED.1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE REDBACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVEYELLOW BACKGROUND. [ANSI Z535]1.6 ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHERRESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN PER NEC 110.21(B)INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTEDPHOTOVOLTAIC SYSTEM DISCONNECT LOCATEDNORTH SIDE OF THE HOUSEDIRECTORYPERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICEDISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTINGMEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8").[NEC 690.56(B)]WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, ADIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PVSYSTEM DISCONNECTING MEANS.PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED INBATHROOMS[NEC 690.4(D),(E)]PHOTOVOLTAIC SOLARAC DISCONNECTCAUTIONMULTIPLE SOURCES OF POWERLABEL 6AT UTILITY METER (5 3/4" X 1 1/8")[NEC 690.56(B)]WARNINGTRIPLE POWER SUPPLYSOURCES: UTILITY GRID,BATTERY AND PV SOLARELECTRIC SYSTEMLABEL 7AT POINT OF INTERCONNECTION(2 3/4" X 1 5/8").[NEC 705.12(B)(3)]WARNINGSOLAR ELECTRICCIRCUIT BREAKERIS BACKFEDLABEL 8AT POINT OFINTERCONNECTION(2" X 1").[NEC 705.12(B)(3)]PHOTOVOLTAIC SOLARDC DISCONNECTPHOTOVOLTAIC POWER SOURCELABEL 11AT POINT OF INTERCONNECTION, MARKEDAT DISCONNECTING MEANS (4" X 2").[NEC 690.54]AMPSVOLTSAC DISCONNECTPHOTOVOLTAIC SYSTEMPOWER SOURCERATED ACOUTPUT CURRENTNOMINAL OPERATINGAC VOLTAGE32240LABEL 12AT EACH DC DISCONNECTINGMEANS (3" X 4").[NEC 690.53].MAXIMUM VOLTAGEMAX CIRCUIT CURRENTVDCAMPSDIRECT CURRENTPHOTOVOLTAIC POWER SOURCE8.89533.4NEWS
20201212141413131515181822221111S-501D51111332727548252423S-501D421.ROOF MATERIAL: ASPHALT SHINGLE2.ROOF STRUCTURE: SINGLE SPAN RAFTER3.ATTACHMENT TYPE: IRONRIDGE FLASH VUE4.MODULE MANUFACTURER: REC SOLAR5.MODULE MODEL: REC420AA PURE-R6.MODULE LENGTH: 68.1''7.MODULE WIDTH: 44''8.MODULE WEIGHT: 47.4 LBS.9.SEE SHEET A-103 FOR DIMENSION(S)10.FIRE OFFSET: 18" FROM RIDGE 36" FROM EDGE11.RAFTER SPACING: 16 IN. O.C.12.RAFTER SIZE: 2X6 IN. NOMINAL.13.LAG BOLT DIAMETER: BOLT/SCREW SUPPLIED WITH RACKING.14.LAG BOLT EMBEDMENT: 2.5 IN.15.TOTAL # OF ATTACHMENTS: 4016.TOTAL AREA: 270.51 SQ. FT.17.TOTAL WEIGHT: 664.68 LBS.18.WEIGHT PER ATTACHMENT: 16.62 LBS.19.DISTRIBUTED LOAD: 2.46 PSF20.MAX. HORIZONTAL STANDOFF: 48 IN.21.MAX. VERTICAL STANDOFF: IN ACCORDANCE WITH MODULEMANUFACTURER'S INSTRUCTIONS.22.STANDOFF STAGGERING: YES23.RAIL MANUFACTURER (OR EQUIV.): IRONRIDGE24.RAIL MODEL (OR EQUIVALENT): AIRE A1 RAIL25.RAIL WEIGHT: 0.42 PLF26.MAX. RAFTER SPAN: N/A.27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.SHEET KEYNOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGEGENERAL NOTESROOF SLOPE 991010101066212177BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONSRACKING DETAIL (TRANSVERSE)D1SCALE: NOT TO SCALERACKING DETAIL (LONGITUDINAL)D2SCALE: NOT TO SCALERACKING DETAIL (TOP)D3SCALE: NOT TO SCALEDETAIL (LONGITUDINAL)D5SCALE: NOT TO SCALEDETAIL (TRANSVERSE)D4SCALE: NOT TO SCALES-501.00ASSEMBLY DETAILS(SHEET 10)Signed 7/24/2023
BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONSR-001.00RESOURCE DOCUMENT(SHEET 11)
BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONSR-002.00(SHEET 12)RESOURCE DOCUMENT
BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONSR-003.00(SHEET 13)RESOURCE DOCUMENT
BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONSR-004.00(SHEET 14)RESOURCE DOCUMENT
BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 5.460 kWpENGINEER OF RECORDDESIGN BY:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORPHONE:LIC. NO.:DATE:CHECKED BY:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 0102730 WATER STNORTHAMPTON, MA 01053APN: 10B-072-001LEANNEGREENERESIDENCE186338664A1413-584-8844M.V.V.G.07.18.2023REVISIONSR-005.00(SHEET 15)RESOURCE DOCUMENT