Simonette - Revised Plan Set 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 VICINITY MAP AERIAL MAP PV-1 REV #1: REV #2: REV #3: DATE: 1/19/2023 DRAWN BY: AN COVER PAGE GRACE SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 AHJ: CITY OF NORTHAMPTON PV-1 - COVER PAGE PV-2 - PROPERTY PLAN PV-3 - SITE PLAN PV-3.1 - ROOF PLAN PV-4 - 1-LINE DIAGRAM PV-4.1 - 3-LINE DIAGRAM PV-5 - MOUNTING DETAILS AND BOM PV-6 - LABELS PV-7 - STRING MAP PV-8 - DATASHEETS PV-9 -PLACARD SHEET INDEX: GOVERNING CODES ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK SHALL COMPLY WITH THE FOLLOWING APPLICABLE CODES: · · · · · · ·IEEE STANDARD 929 ·OSHA 29 CFR 1910.269 ·WHERE APPLICABLE, RULES OF THE PUBLIC UTILITIES COMMISSION REGARDING SAFETY AND RELIABILITY ·THE AUTHORITY HAVING JURISDICTION ·MANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS ·ANY OTHER LOCAL AMENDMENTS 2017 NATIONAL ELECTRIC CODE 2015 INTERNATIONAL BUILDING CODE 2017 INTERNATIONAL RESIDENTIAL CODE 2015 INTERNATIONAL PLUMBING CODE 2015 INTERNATIONAL FIRE CODE 2015 INTERNATIONAL MECHANICAL CODE GENERAL 1. UTILITY SHALL BE NOTIFIED BEFORE ACTIVATION OF PHOTOVOLTAIC SYSTEM. 2. 110.2 APPROVAL: ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH ADMINISTRATION 3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO INITIATING CONSTRUCTION. 4. CONTRACTOR SHALL REVIEW ALL MANUFACTURER INSTALLATION DOCUMENTS PRIOR TO INITIATING CONSTRUCTION. 5. ALL EQUIPMENT AND ASSOCIATED CONNECTIONS, ETC, AND ALL ASSOCIATED WIRING AND INTERCONNECTIONS SHALL BE INSTALLED ONLY BY QUALIFIED PERSONNEL. 6. THE CONTRACTOR OR OWNER MUST PROVIDE ROOF ACCESS (LADDER TO ROOF) FOR ALL THE REQUIRED INSPECTIONS. LADDERS MUST BE OSHA APPROVED, MINIMUM TYPE I WITH A 250LB. RATING, IN GOOD CONDITION AND DESIGNED FOR ITS INTENDED USE. 7. CONTRACTOR SHALL VERIFY THAT THE ROOF STRUCTURE WILL WITHSTAND THE ADDITIONAL LOADS. 8. LAG SCREWS SHALL PENETRATE A MINIMUM 2" INTO SOLID SAWN STRUCTURAL MEMBERS AND SHALL NOT EXCEED MANUFACTURER RECOMMENDATIONS FOR FASTENERS INTO ENGINEERED STRUCTURAL MEMBERS. 9. AN ACCESS POINT SHALL BE PROVIDED THAT DOES NOT PLACE THE GROUND LADDER OVER OPENINGS SUCH AS WINDOWS OR DOORS ARE LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION AND IN LOCATIONS WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES, OR SIGNS. 10. WHERE DC CONDUCTORS ARE RUN INSIDE BUILDING, THEY SHALL BE CONTAINED IN A METAL RACEWAY; THEY SHALL NOT BE INSTALLED WITHIN 10" OF THE ROOF DECKING OR SHEATHING EXCEPT WHERE COVERED BY THE PV MODULES AND EQUIPMENT. 11. ALL FIELD -INSTALLED JUNCTION, PULL AND OUTLET BOXES LOCATED BEHIND MODULES SHALL BE ACCESSIBLE DIRECTLY OR BY DISPLACEMENT OF A MODULE SECURED BY REMOVABLE FASTENERS. ELECTRICAL 1. WIRING MATERIALS SHALL COMPLY WITH MAXIMUM CONTINUOUS CURRENT OUTPUT AT 25°C AND MAXIMUM VOLTAGE AT 600V; WIRE SHALL BE WET RATED AT 90°C. 2. EXPOSED PHOTOVOLTAIC SYSTEM CONDUCTORS ON THE ROOF WILL BE USE 2 OR PV-TYPE WIRE. 3. PHOTOVOLTAIC SYSTEM CONDUCTORS SHALL BE IDENTIFIED AND GROUPED. THE MEANS OF IDENTIFICATION SHALL BE PERMITTED BY SEPARATE COLOR-CODING, MARKING TAPE, TAGGING OR OTHER APPROVED MEANS. 4. ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL BE RAIN-TIGHT AND APPROVED FOR USE IN WET LOCATIONS. 5. ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE BONDED AND ELECTRICALLY CONTINUOUS. 6. WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, CONTRACTOR SHALL SIZE THEM ACCORDING TO APPLICABLE CODES. 7. REMOVAL OF A UTILITY-INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BUILDING CONNECTION BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE PV SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTOR. 8. FOR GROUNDED SYSTEMS, THE PHOTOVOLTAIC SOURCE AND OUTPUT CIRCUITS SHALL BE PROVIDED WITH A GROUND-FAULT PROTECTION DEVICE OR SYSTEM THAT DETECTS A GROUND FAULT, INDICATES THAT FAULT HAS OCCURED AND AUTOMATICALLY DISCONNECTS ALL CONDUCTORS OR CAUSES THE INVERTER TO AUTOMATICALLY CEASE SUPPLYING POWER TO OUTPUT CIRCUITS. 9. FOR UNGROUNDED SYSTEMS, THE INVERTER IS EQUIPPED WITH GROUND FAULT PROTECTION AND A GFI FUSE PORT FOR GROUND FAULT INDICATION. 10. PV MODULE FRAMES SHALL BE BONDED TO RACKING RAIL OR BARE COPPER GEC/GEC PER THE MODULE MANUFACTURER'S LISTED INSTRUCTION SHEET. 11. PV MODULE RACKING RAIL SHALL BE BONDED TO BARE COPPER GEC VIA WEEB LUG, ILSCO GBL-4DBT LAY-IN LUG, OR EQUIVALENT LISTED LUG. 12. THE PHOTOVOLTAIC INVERTER WILL BE LISTED AS UL 1741 COMPLIANT. 13. RACKING AND BONDING SYSTEM TO BE UL2703 RATED. 14. ANY REQUIRED GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AS BUS BARS WITHIN LISTED EQUIPMENT. 15. WHEN BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION, THE BREAKERS SHALL NOT READ "LINE AND LOAD". 16. WHEN APPLYING THE 120% RULE, THE SOLAR BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. 17. THE WORKING CLEARANCE AROUND THE EXISTING ELECTRICAL EQUIPMENT AS WELL AS THE NEW ELECTRICAL EQUIPMENT WILL BE MAINTAINED. CODE 9TH EDITION ·780 CMR 51 MASSACHUSETTS RESIDENTIAL SIMONETTE RESIDENCE PHOTOVOLTAIC SYSTEM 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 SYSTEM SIZE: 5.60 kW-DC | 5.00 kW-AC MODULE: (14) HANWHA Q CELLS : Q.PEAK DUO BLK ML-G10+ [400W] INVERTER: (1) SOLAREDGE SE50000H-US [240V] N 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 LEGEND: PROPERTY LINE: DATE: 1/19/2023 DRAWN BY: AN PROPERTY PLAN PV-2 DRIVEWAY: APN: NHAMM031CB0035L0002 GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 AHJ: CITY OF NORTHAMPTON SCALE: 3/32"=1'-0" PROPERTY LINE ---MUSANTE DRIVE---DRIVEWAY MAIN HOMEGARAGE90'-6" 66'-9" 93'-9" 66'-9" 2'-9" 32'-3" 13'-3" VENT NEED TO BE RELOCATED 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 N SYSTEM LEGEND UM MP AC MAIN SERVICE METER AND SERVICE POINT MAIN SERVICE PANEL UTILITY AC DISCONNECT SCALE: 1/8" = 1'-0" CONDUIT TO BE RUN IN ATTIC IF POSSIBLE, OTHERWISE CONDUIT BLOCKS MIN. 1"/MAX 6" ABOVE ROOF SURFACE, CLOSE TO RIDGE LINES, AND UNDER EAVES; TO BE PAINTED TO MATCH EXTERIOR/EXISTING BACKGROUND COLOR OF ITS LOCATION; TO BE LABELED AT MAX 10' INTERVALS. CONDUIT RUNS ARE APPROXIMATE AND ARE TO BE DETERMINED IN THE BY THE INSTALLERS CONDUIT RUN (14) HANWHA Q CELLS : Q.PEAK DUO BLK ML-G10+ [400W] WITH SOLAREDGE P401 POWER OPTIMIZERS MOUNTED UNDER EACH MODULE ROOF TYPE: ASPHALT SHINGLE ROOF DETAIL ROOF SECTION 1: 5 MODULES AZIMUTH: 186° PITCH: 38° ROOF SECTION 2: 3 MODULES AZIMUTH: 96° PITCH: 33° ROOF SECTION 3: 3 MODULES AZIMUTH: 276° PITCH: 32° ROOF SECTION 4: 3 MODULES AZIMUTH: 276° PITCH: 22° 1 2 3 4 DATE: 1/19/2023 DRAWN BY: AN SITE PLAN PV-3 JUNCTION BOX AND CONDUIT GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 AHJ: CITY OF NORTHAMPTON I (1) SOLAREDGE SE50000H-US [240V] INVERTER WITH INTEGRATED DC DISCONNECT PHOTOVOLTAIC SYSTEM: DC SYSTEM SIZE: 5.60 kW AC SYSTEM SIZE: 5.00 kW INSTALLER NOTES: AC DISCONNECT INSTALLED WITHIN 5 FEET OF UTILITY METER. 4 FAC FUSED AC DISCONNECT 1 2 3 MP UMAC FAC I VENT NEED TO BE RELOCATED 3' 1'-6"1'-6" 3' 1'-6" 3' 1'-6" 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 N SYSTEM LEGEND SCALE: 1/8" = 1'-0" ROOF TYPE: ASPHALT SHINGLE ROOF DETAIL ROOF SECTION 1: 5 MODULES AZIMUTH: 186° PITCH: 38° ROOF SECTION 2: 3 MODULES AZIMUTH: 96° PITCH: 33° ROOF SECTION 3: 3 MODULES AZIMUTH: 276° PITCH: 32° ROOF SECTION 4: 3 MODULES AZIMUTH: 276° PITCH: 22° 1 2 3 4 ROOF ATTACHMENT POINT DATE: 1/19/2023 DRAWN BY: AN ROOF PLAN PV-3.1 GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 ROOF FRAMING (RAFTERS/TRUSS) RACKING AHJ: CITY OF NORTHAMPTON MODULE MECHANICAL SPECIFICATIONS DESIGN WIND SPEED 117 MPH DESIGN SNOW LOAD 40 PSF # OF STORIES 2 ROOF PITCH 38°,33°, 32° & 22° TOTAL ARRAY AREA (SQ. FT)294.84 TOTAL ROOF AREA (SQ. FT)2565 ARRAY SQ. FT / TOTAL ROOF SQ. FT 11.49% 4 STRUCTURAL ATTACHMENT MODULE ASPHALT SHINGLE TRUSS:2"X4": @24" O.C. 1 23 4' TYP. VENT NEED TO BE RELOCATED 3' 3'3' 1'-6"1'-6" 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 PHOTOVOLTAIC SYSTEM: DC SYSTEM SIZE: 5.600 kW AC SYSTEM SIZE: 5.000 kW INVERTER: (1) SOLAREDGE SE50000H-US [240V] MODULE: (14) HANWHA Q CELLS : Q.PEAK DUO BLK ML-G10+ [400W] NOTES: 1.MODULES ARE BONDED TO RAIL USING UL 2703 RATED BONDING SYSTEM - INTEGRATED BONDING MID-CLAMPS + DIRECT-BURIAL LAY-IN-LUGS; SEE ATTACHED FOR SPECIFICATIONS IF APPLICABLE 2.PV DC SYSTEM IS UNGROUNDED 3.PV ARRAY WILL HAVE A GROUNDING ELECTRODE SYSTEM IN COMPLIANCE WITH NEC 250.58 AND 690.47(A) 4.PV SOURCE, OUTPUT, AND INVERTER INPUT CIRCUIT WIRING METHODS SHALL COMPLY WITH NEC 690.1(G) 5.BACKFED PV BREAKER WILL BE INSTALLED AT OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE INSTALLED PER SYSTEM SIGNAGE, PAGE 6.BARE COPPER IS TRANSITIONED TO THWN-2 VIA IRREVERSIBLE CRIMP; WHEN PRESENT, THE GEC TO BE CONTINUOUS 7.INVERTER(S) TO BE COMPLIANT WITH UL 1741 SUPPLEMENT A 8.CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS 9.CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UPSIZING AS REQUIRED BY FIELD CONDITIONS. DATE: 1/19/2023 DRAWN BY: AN 1-LINE DIAGRAM & CALCULATIONS PV-4 GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 CONDUCTOR AND CONDUIT SCHEDULE TAG WIRE TYPE WIRE SIZE # OF CONDUCTORS CONDUIT TYPE MIN. CONDUIT SIZE 1 PV WIRE #10 2 - L1 L2 FREE AIR N/A 1 BARE COPPER #6 1 - BARE FREE AIR N/A 2 THWN-2 #10 2 - L1 L2 EMT 3/4" 2 THWN-2 EGC #6 1 - GND EMT 3/4" 3 THWN-2 #10 3 - L1 L2 N EMT 3/4" 3 THWN-2 EGC #6 1 - GND EMT 3/4" 4 THWN-2 #6 3 - L1 L2 N EMT 3/4" 4 THWN-2 EGC #6 1 - GND EMT 3/4" PV MODULE ELECTRICAL SPECIFICATIONS MODULE TYPE HANWHA Q CELLS : Q.PEAK DUO BLK ML-G10+ [400W] POWER MAX (PMAX)400W OPEN CIRCUIT VOLTAGE (VOC)45.30V SHORT CIRCUIT CURRENT (ISC)11.14A MAX POWER VOLTAGE (VMP)37.13V MAX POWER CURRENT (IMP)10.77A SERIES FUSE RATING 20A AHJ: CITY OF NORTHAMPTON INVERTER ELECTRICAL SPECIFICATIONS INVERTER TYPE SOLAREDGE SE5000H-US MAX INPUT DC VOLTAGE 480V MAX INPUT CURRENT 13.5A NOMINAL DC INPUT VOLTAGE 380V MAXIMUM OUTPUT POWER 5000H NOMINAL AC OUTPUT VOLTAGE 240V MAXIMUM CONT. OUTPUT CURRENT 21A CEC EFFICIENCY 99% OVER-CURRENT PROTECTION DEVICE (OCPD) CALCULATIONS INVERTER TYPE SOLAREDGE 5000H-US # OF INVERTERS 1 MAX CONTINUOUS OUTPUT CURRENT 21A (# OF INVERTERS) X (MAX CONT. OUTPUT CURRENT) X 125% <= OCPD RATING (1 x 21A x 1.25)= 26.25A <= 30A, OK POWER OPTIMIZER ELECTRICAL SPECIFICATIONS OPTIMIZER TYPE SOLAREDGE P401 RATED INPUT DC POWER 401W MAXIMUM INPUT VOLTAGE (VOC)80V MAXIMUM SHORT CIRCUIT CURRENT (ISC)10.1A MAXIMUM OUTPUT CURRENT 15A MAXIMUM OUTPUT VOLTAGE 60V MINIMUM STRING LENGTH 8 MAXIMUM POWER PER STRING 5700W (6000W WITH SE7600- SE11400) NOTE: ALL DC CONNECTOR TO MODULES OR INVERTERS MUST BE OF MATCHING MANUFACTURING BRAND AND STYLE. DO NOT USE 'COMPATIBLE' CONNECTORS WHICH HAVE NOT BEEN UL TESTED FOR COMPATIBILITY. PERFORMANCE AND FIRE DAMAGE MAY RESULT FROM MISMATCHED CONNECTOR USAGE. INSTALLER NOTES: AC DISCONNECT INSTALLED WITHIN 5 FEET OF UTILITY METER. (N) AC DISCONNECT 240V/30A NEMA 3R FUSIBLE W/ 30A FUSES, VISIBLE-LOCKABLE LABELED (N) AC DISCONNECT 240V/30A NEMA 3R NON-FUSIBLE, VISIBLE-LOCKABLE LABELED STRING 1: 14 MODULES - HANWHA Q CELLS : Q.PEAK DUO BLK ML-G10+ [400W] = = = = = = 13 SOLAREDGE P401 OPTIMIZER UTILITY INTERACTIVE SINGLE PHASE INVERTER SOLAREDGE SE50000H-US [240V] INTEGRATED DC DISCONNECT UL1741 CERTIFIED NEMA3R RATED JUNCTION BOX: SHALL COMPLY W/ NEC 110.3 & 314.6 1 (E) LOADS 100A MAIN DISCONNECT UTILITY SERVICE 120/240V SINGLE PHASE (E)100A RATED MAIN SERVICE PANEL FACILITY GROUND (E) GROUND ROD N-G SUPPLY SIDE TAP - ILSCO GTA-250-0-W/C PARALLEL TAP CONNECTOR 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 DATE: 1/19/2023 DRAWN BY: AN 3-LINE DIAGRAM & CALCULATIONS PV-4.1 GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 NOTES: 1.MODULES ARE BONDED TO RAIL USING UL 2703 RATED BONDING SYSTEM - INTEGRATED BONDING MID-CLAMPS + DIRECT-BURIAL LAY-IN-LUGS; SEE ATTACHED FOR SPECIFICATIONS IF APPLICABLE 2.PV DC SYSTEM IS UNGROUNDED 3.PV ARRAY WILL HAVE A GROUNDING ELECTRODE SYSTEM IN COMPLIANCE WITH NEC 250.58 AND 690.47(A) 4.PV SOURCE, OUTPUT, AND INVERTER INPUT CIRCUIT WIRING METHODS SHALL COMPLY WITH NEC 690.1(G) 5.BACKFED PV BREAKER WILL BE INSTALLED AT OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE INSTALLED PER SYSTEM SIGNAGE, PAGE 6.BARE COPPER IS TRANSITIONED TO THWN-2 VIA IRREVERSIBLE CRIMP; WHEN PRESENT, THE GEC TO BE CONTINUOUS 7.INVERTER(S) TO BE COMPLIANT WITH UL 1741 SUPPLEMENT A 8.CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS 9.CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UPSIZING AS REQUIRED BY FIELD CONDITIONS. AHJ: CITY OF NORTHAMPTON PHOTOVOLTAIC SYSTEM: DC SYSTEM SIZE: 5.600 kW AC SYSTEM SIZE: 5.000 kW INVERTER: (1) SOLAREDGE SE50000H-US [240V] MODULE: (14) HANWHA Q CELLS : Q.PEAK DUO BLK ML-G10+ [400W] INSTALLER NOTES: AC DISCONNECT INSTALLED WITHIN 5 FEET OF UTILITY METER. (N) AC DISCONNECT 240V/30A NEMA 3R FUSIBLE W/ 30A FUSES, VISIBLE-LOCKABLE LABELED (N) AC DISCONNECT 240V/30A NEMA 3R NON-FUSIBLE, VISIBLE-LOCKABLE LABELED STRING 1: 14 MODULES - HANWHA Q CELLS : Q.PEAK DUO BLK ML-G10+ [400W] = = = = = = 13 SOLAREDGE P401 OPTIMIZER UTILITY INTERACTIVE SINGLE PHASE INVERTER SOLAREDGE SE50000H-US [240V] INTEGRATED DC DISCONNECT UL1741 CERTIFIED NEMA3R RATED JUNCTION BOX: SHALL COMPLY W/ NEC 110.3 & 314.6 PV MODULE ELECTRICAL SPECIFICATIONS MODULE TYPE HANWHA Q CELLS : Q.PEAK DUO BLK ML-G10+ [400W] POWER MAX (PMAX)400W OPEN CIRCUIT VOLTAGE (VOC)45.30V SHORT CIRCUIT CURRENT (ISC)11.14A MAX POWER-POINT VOLTAGE (VMP)37.13V MAX POWER-POINT CURRENT (IMP)10.77A SERIES FUSE RATING 20A INVERTER ELECTRICAL SPECIFICATIONS INVERTER TYPE SOLAREDGE SE5000H-US MAX INPUT DC VOLTAGE 480V MAX INPUT CURRENT 13.5A NOMINAL DC INPUT VOLTAGE 380V MAXIMUM OUTPUT POWER 5000H NOMINAL AC OUTPUT VOLTAGE 240V MAXIMUM CONT. OUTPUT CURRENT 21A CEC EFFICIENCY 99% OVER-CURRENT PROTECTION DEVICE (OCPD) CALCULATIONS INVERTER TYPE SOLAREDGE 5000H-US # OF INVERTERS 1 MAX CONTINUOUS OUTPUT CURRENT 21A (# OF INVERTERS) X (MAX CONT. OUTPUT CURRENT) X 125% <= OCPD RATING (1 x 21A x 1.25)= 26.25A <= 30A, OK POWER OPTIMIZER ELECTRICAL SPECIFICATIONS OPTIMIZER TYPE SOLAREDGE P401 RATED INPUT DC POWER 401W MAXIMUM INPUT VOLTAGE (VOC)80V MAXIMUM SHORT CIRCUIT CURRENT (ISC)10.1A MAXIMUM OUTPUT CURRENT 15A MAXIMUM OUTPUT VOLTAGE 60V MINIMUM STRING LENGTH 8 MAXIMUM POWER PER STRING 5700W (6000W WITH SE7600- SE11400) NOTE: ALL DC CONNECTOR TO MODULES OR INVERTERS MUST BE OF MATCHING MANUFACTURING BRAND AND STYLE. DO NOT USE 'COMPATIBLE' CONNECTORS WHICH HAVE NOT BEEN UL TESTED FOR COMPATIBILITY. PERFORMANCE AND FIRE DAMAGE MAY RESULT FROM MISMATCHED CONNECTOR USAGE. CONDUCTOR AND CONDUIT SCHEDULE TAG WIRE TYPE WIRE SIZE # OF CONDUCTORS CONDUIT TYPE MIN. CONDUIT SIZE 1 PV WIRE #10 2 - L1 L2 FREE AIR N/A 1 BARE COPPER #6 1 - BARE FREE AIR N/A 2 THWN-2 #10 2 - L1 L2 EMT 3/4" 2 THWN-2 EGC #6 1 - GND EMT 3/4" 3 THWN-2 #10 3 - L1 L2 N EMT 3/4" 3 THWN-2 EGC #6 1 - GND EMT 3/4" 4 THWN-2 #6 3 - L1 L2 N EMT 3/4" 4 THWN-2 EGC #6 1 - GND EMT 3/4" (E) LOADS 100A MAIN DISCONNECT UTILITY SERVICE 120/240V SINGLE PHASE (E)100A RATED MAIN SERVICE PANEL FACILITY GROUND (E) GROUND ROD L2 L1 N G N-G SUPPLY SIDE TAP - ILSCO GTA-250-0-W/C PARALLEL TAP CONNECTOR 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 DATE: 1/19/2023 DRAWN BY: AN PV-5 GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 MOUNTING DETAILS AND BOM ATTACHMENT TYPE: SNAPNRACK ULTRA RAIL COMP KIT WITH IRONRIDGE AIRE A1 RAIL MOUNTING ROOF TYPE: ASPHALT SHINGLE , ROOF TILT: 38°,33°, 32° & 22° MODULE WEIGHT: 48.5 LBS MODULE DIMENSIONS: 6.16' X 3.42' MODULE WEIGHT/ SQ. FOOT: 2.30 LBS TOTAL NO. OF MODULES: 14 TOTAL MODULE WEIGHT: 679 LBS ATTACHMENT DETAILS (N.T.S.) 1 AHJ: CITY OF NORTHAMPTON MODULE FRAME MID CLAMPEND CLAMP MODULE FRAME SOLAR CELLS SNAPANRACK RAIL TOP VIEW TOP VIEW SIDE VIEW SIDE VIEW MODULE FRAME END CLAMP IRONRIDGE RAILS IRONRIDGE RAILS MODULE FRAME MID CLAMP SOLAR CELLS SIDE VIEW SOLAR MODULE END CLAMP (E) TRUSS IRONRIDGE AIRE A1 RAIL (E) ASPHALT SHINGLE IRONRIDGE AIRE A1 RAIL COMP KIT 3 1/2" x 5/16 WITH 4" MIN LAG SCREW EMBEDMENT BILL OF MATERIAL EQUIPMENT MAKE QUANTITY MODULE HANWHA Q CELLS : Q.PEAK DUO BLK ML-G10+ [400W]14 INVERTER SOLAREDGE SE50000H-US [240V]1 END CLAMPS MODULE END CLAMP STANDARD 24 MID CLAMPS MODULE MIDDLE CLAMP SET STANDARD(INTEGRATED GROUNDING)16 MOUNTING POINTS SNAPNRACK ULTRA RAIL COMP KIT 43 MOUNTING RAILS IRONRIDGE AIRE A1 RAIL 10 UTILITY AC DISCONNECT PV SYSTEM UTILITY AC DISCONNECT 30A RATED 1 FUSED AC DISCONNECT PV SYSTEM FUSED AC DISCONNECT 30A RATED WITH 30A FUSES 1 OPTIMIZERS SOLAREDGE P401 OPTIMIZER 14 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 DATE: 1/19/2023 DRAWN BY: AN PV-6 LABELS ARE NOT DRAWN TO SCALE GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 ! WARNING ! DUAL POWER SOURCES. SECOND SOURCE IS PV SYSTEM LABEL 7 PHOTOVOLTAIC AC DISCONNECT OPERATING CURRENT: 21.0 A AC OPERATING VOLTAGE: 240 V AC LABEL 5 AT POINT OF INTERCONNECTION, MARKED AT DISCONNECTING MEANS [NEC 690.54] ! WARNING ! ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. LABEL 3 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT [NEC 690.13 AND 690.15] PHOTOVOLTAIC DC DISCONNECT UTILITY AC DISCONNECT LABEL 10 AT EACH DC DISCONNECTING MEANS [NEC 690.13(B)] LABEL 12 AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. [NEC 690.31(G)] LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE [IFC 605.11.1.1] LABEL 13 AT EACH AC DISCONNECTING MEANS [NEC 690.13(B)] ! CAUTION ! PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED ! WARNING ! POWER SOURCE OUTPUT CONNECTION - DO NOT RELOCATE THIS OVERCURRENT DEVICE LABEL 14 AT POINT OF INTERCONNECTION OVERCURRENT DEVICE [NEC 705.12(B)(2)(3)(B)] LABEL 9 AT UTILITY METER [NEC 690.56(B)] LABEL 4 AT EACH DC DISCONNECTING MEANS [NEC 690.53] LABEL 11 AT RAPID SHUTDOWN SWITCH [NEC 690.56(C)]. LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE [IFC 605.11.1.1] LABEL 8 AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 7 OR LABEL 8 MUST IDENTIFY PHOTOVOLTAIC SYSTEM [NEC 705.12(B)(4)] TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY LABEL 1 AT RAPID SHUTDOWN SYSTEM [NEC 690.56(C)(1)(A)]. ! WARNING ! ELECTRIC SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLIGHT LABEL 2 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT [NEC 690.15] MAXIMUM VOLTAGE: 480 V DC MAXIMUM CIRCUIT CURRENT:13.5 A DC MAX RATED OUTPUT CURRENT OF THE CHARGE CONTROLLER OR DC-TO-DC CONVERTER (IF INSTALLED):13.5 A DC LABEL 6 AT RAPID SHUTDOWN DISCONNECT SWITCH [NEC 690.56(C)(3)]. #03-359 LOCAL CODES BI-DIRECTIONAL METER WARNING: PHOTOVOLTAIC POWER SOURCE PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS WARNING THIS SERVICE METER IS ALSO SERVED BY A PHOTOVOLTAIC SYSTEM ELECTRICAL LABELS & ELEVATION LABELING NOTES 1.1 LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z535 1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. 1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED. 1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535] PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION [NEC 690.56(B)] WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS. PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED IN BATHROOMS [NEC 690.4(D),(E)] ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHER RESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN PER NEC 110.21(B) AHJ: CITY OF NORTHAMPTON MAIN SERVICE PANEL FOR ILLUSTRATION ONLY (NOT ACTUAL MSP) MAIN SERVICE METER INVERTERJUNCTION BOX (IF USED)4 7 8 92 2 2 1 611 14 3 3 TO SOLAR ARRAY FUSED AC DISCONNECT 5 2 6 3 UTILITY AC DISCONNECT 5 2 6 3 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 FOR INSTALLER USE ONLY DATE: 1/19/2023 DRAWN BY: AN OPTIMIZER & STRING MAP PV-7 GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 AHJ: CITY OF NORTHAMPTON STRING DETAIL SOLAREDGE STRINGS STRING DETAIL SOLAREDGE STRINGS STRING DETAIL SOLAREDGE STRINGS STRING DETAIL SOLAREDGE STRINGS STRING # 1: 14 MODULES STRING DETAIL SOLAREDGE STRINGS STRING -1 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 DATE: 1/19/2023 DRAWN BY: AN MODULE DATASHEET PV-8.1 GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 AHJ: CITY OF NORTHAMPTON 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 DATE: 1/19/2023 DRAWN BY: AN INVERTER DATASHEET PV-8.2 GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 AHJ: CITY OF NORTHAMPTON 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 DATE: 1/19/2023 DRAWN BY: AN OPTIMIZERS DATASHEET PV-8.3 GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 AHJ: CITY OF NORTHAMPTON 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 DATE: 1/19/2023 DRAWN BY: AN ATTACHMENT DATASHEET PV-8.4 GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 AHJ: CITY OF NORTHAMPTON 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 DATE: 1/19/2023 DRAWN BY: AN RACKING DATASHEET PV-8.5 GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 AHJ: CITY OF NORTHAMPTON 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 DATE: 1/19/2023 DRAWN BY: AN RACKING DATASHEET PV-8.6 GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 AHJ: CITY OF NORTHAMPTON 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102N DATE: 1/19/2023 DRAWN BY: AN PLACARD PV-9 GRACE, SIMONETTE 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 AHJ: CITY OF NORTHAMPTON CAUTION POWER TO THIS BUILDING IS SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN !! SERVICE 1 OF 1 82 MUSANTE DRIVE, NORTHAMPTON, MA 01060 SOLAR PV ARRAY MAIN SERVICE PANEL INVERTER UTILITY AC DISCONNECTUTILITY METER FUSED AC DISCONNECT