Engler_Letter_SSVSE Project Number: U1898.0162.231 March 30, 2023 PV Squared 311 Wells St. Ste. B Greenfield, MA 01301 REFERENCE: Engler Residence: 117 Olander Drive, Northampton, MA 01060 PV Squared Project: ENNO17012023R Solar Array Installation To Whom It May Concern: We have reviewed the existing structure at the above referenced site.The purpose of our review was to determine the adequacy of the existing structure to support the proposed installation of solar panels on the roof as shown on the panel layout plan. Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel installation. Design Parameters Code: Massachusetts State Residential Code (780 CMR Chapter 51, 9th Edition (2015 IRC)) Risk Category: II Design wind speed, Vult: 117 mph (3-sec gust) Wind exposure category: C Ground snow load, Pg: 40 psf Flat roof snow load, Pf: 35 psf Existing Roof Structure Roof structure: 2x4 manufactured trusses @ 24" o.c. Roof pitch: 7:12 Conclusions Based upon our review,we conclude that the existing structure is adequate to support the proposed solar panel installation. The glass surface of the solar panels allows for a lower slope factor per ASCE 7,resulting in reduced design snow load on the panels.The gravity loads,and thus the stresses of the structural elements,in the area of the solar array are either decreased or increased by no more than 5%.Therefore,the requirements of Section 807.4 of the 2015 IEBC as referenced in 780 CMR Chapter 34, 9th Edition are met and the structure is permitted to remain unaltered. The solar array will be flush-mounted (no more than 10"above the roof surface)and parallel to the roof surface.Thus,we conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible. Increases in lateral forces less than 10%are considered acceptable.Thus the existing lateral force resisting system is permitted to remain unaltered. 651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com VSE Project Number: U1898.0162.231 Engler - Northampton Residence 3/30/2023 Limitations Installation of the solar panels must be performed in accordance with manufacturer recommendations.All work performed must be in accordance with accepted industry-wide methods and applicable safety standards.The contractor must notify Vector Structural Engineering,LLC should any damage,deterioration or discrepancies between the as-built condition of the structure and the condition described in this letter be found.The use of solar panel support span tables provided by others is allowed only where the building type,site conditions,site-specific design parameters,and solar panel configuration match the description of the span tables.Connections shall be staggered so as not to overload any existing structural member.The design of the solar panels,solar racking (mounts,rails,etc.),the connection of the racking to the roof and electrical engineering is the responsibility of others.Waterproofing around the roof penetrations is the responsibility of others.Vector Structural Engineering assumes no responsibility for improper installation of the solar array.Vector Structural Engineering shall be notified of any changes from the approved layout prior to installation. VECTOR STRUCTURAL ENGINEERING, LLC 03/30/2023 _______________________________________________________ Wells Holmes, S.E. MA License: 54240 - Expires: 06/30/2024 Project Engineer Enclosures WLH/crs 03/30/2023 651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com VECTOR STRUCTURAL ENGINEERS JOB NO.:U1898.0162.231 SUBJECT:GRAVITY LOADS PROJECT:Engler Residence GRAVITY LOADS Roof Pitch: 7.0 :12 ROOF DEAD LOAD (D) Increase due to pitch Material weight [psf] Composite Shingles 1.16 2.0 1/2" Plywood 1.16 1.0 Framing 1.00 3.0 Insulation 1.00 0.5 1/2" Gypsum Clg.1.16 2.0 M, E & Misc 1.00 6.5 Total Existing Roof DL PV Array DL 1.16 3 DL:1.16 ROOF LIVE LOAD (Lr) Existing Design Roof Live Load [psf]20 ASCE 7-10 Table 4-1 Roof Live Load With PV Array [psf]20 SNOW LOAD (S):w/ Solar Array Roof Slope [x:12]:7.0 Roof Slope [°]:30 Ground Snow Load, pg [psf]:40 ASCE 7-10, Section 7.2 Terrain Category:C ASCE 7-10, Table 7-2 Exposure of Roof:Fully Exposed ASCE 7-10, Table 7-2 Exposure Factor, Ce:0.9 ASCE 7-10, Table 7-2 Thermal Factor, Ct:1.1 ASCE 7-10, Table 7-3 Risk Category:II ASCE 7-10, Table 1.5-1 Importance Factor, Is:1.0 ASCE 7-10, Table 1.5-2 Flat Roof Snow Load, pf [psf]:35 ASCE 7-10, Equation 7.3-1 Minimum Roof Snow Load, pm [psf]:0 ASCE 7-10, Section 7.3.4 Unobstructed Slippery Surface?Yes ASCE 7-10, Section 7.4 Slope Factor Figure:Figure 7-2b ASCE 7-10, Section 7.4 Roof Slope Factor, Cs:0.66 ASCE 7-10, Figure 7-2 Sloped Roof Snow Load, ps [psf]:23 ASCE 7-10, Equation 7.4-1 Design Snow Load, S [psf]:2335 7.0 30 40 C Fully Exposed 0.9 1.1 II 1.0 35 0 No Figure 7-2b 1.00 35 Design material weight [psf] 2.3 1.2 3.0 0.5 2.3 6.5 15.8 3.5 #VALUE! Existing JOB NO.:U1898.0162.231 SUBJECT:LOAD COMPARISON PROJECT:Engler Residence Summary of Loads Existing With PV Array D [psf]16 19 Lr [psf]20 20 S [psf]35 23 Maximum Gravity Loads: Existing With PV Array (D + Lr) / Cd [psf]29 31 ASCE 7-10, Section 2.4.1 (D + S) / Cd [psf]44 37 ASCE 7-10, Section 2.4.1 Maximum Gravity Load [psf]:44 37 Ratio Proposed Loading to Current Loading:84%OK The gravity loads, and thus the stresses of the structural elements, in the area of the solar array are either decreased or increased by no more than 5%. Therefore, the requirements of Section 807.4 of the 2015 IEBC as referenced in 780 CMR Chapter 34, 9th Edition are met and the structure is permitted to remain unaltered. (Cd = Load Duration Factor = 0.9 for D, 1.15 for S, and 1.25 for Lr) VECTOR STRUCTURAL ENGINEERS JOB NO.:U1898.0162.231 SUBJECT:SOLAR LAYOUT PROJECT:Engler Residence