22-0486 Parsons House NarrativeFIRE PROTECTION SYSTEMS NARATIVE REPORT
BASIS (METHODOLOGY) OF DESIGN
TIER ONE CONSTRUCTION DOCUMENT
A: Basic of design, Sequence of operations and Testing Criteria
(i.) Existing Building – Dormitory R-2; Type IIIB Construction – The highest
point 58’ to attic ridge above finished floor.
One (1) partial crawl space below lower level but in-filled under scope of
work for this project.
Approximate usable total square footage is as follows:
Lower Level – 4,835 square feet
First Floor – 4,888 square feet
Second Floor – 4,835 square feet
Third Floor – 4,267 square feet
Attic Level – 2,834 square feet
Total: 21,659 square feet
Applicable Laws, Regulations and Standards
The following codes and standards apply to the design and installation of
sprinkler system and fire alarm system installations in the subject building:
a. 780 CMR, IBC (2015) as adopted and modified by the Massachusetts
State Building Coe (9th edition), Chapter 9, Fire Protection Systems
b. Massachusetts IEBC (2015) as adopted and modified by MA
c. 527 CMR, NFPA 1 (2015) as adopted and modified by Massachusetts
Comprehensive Fire Safety Code
d. NFPA 13, Standard for the Installation of Sprinkler Systems (2013)
e. NFPA 70, National Electrical code (2020)
f. NFPA 72, National Fire Alarm and Signaling Code (2013)
g. FM Global Pamphlet 1-12
h. FM Global Pamphlet 3-26
Design Responsibility for the Fire Protection Systems
JFV Engineering, LLC. develops a full system layout, design criteria and calculations and
certifies the system installation for code compliance at completion.
(.ii) Sequence of Operation
Fire Alarm System General
a. FACP and Alarm Sequence: When the FACP receives a signal from a
fire alarm initiating device, and audible and visible alarm signal will
broadcast throughout the building. An alarm signal is transmitted to
the Fire Department via transmitter and central station service as
determined by Smith College. Additionally, all supervisory and trouble
signals are transmitted to the off-site monitoring service and
transmitted to the owner’s contact representative.
b. General Area Smoke Detectors (If Required): When smoke detectors
sense smoke, a signal is sent to the FACP, which starts the alarm
sequence
c. Duct Smoke Detectors: When duct smoke detectors sense smoke, a
signal is transmitted to the FACP associated AHU’s shutdown, and the
condition is transmitted to the offsite monitoring station for
dissemination
d. Manual Fire Alarm Pull Boxes: When a pull station is manually
activated, a signal is sent to the FACP, which starts the alarm
sequence.
e. Valve Supervisory Switches: If a sprinkler control valve is improperly
closed, a signal is sent to the FACP. The FACP broadcasts and audible
and visible trouble signal locally at the panel and the condition is
transmitted to the offsite monitoring station for dissemination.
f. Water Flow Switches: Actuation of any sprinkler in the building shall
activate the water flow switch associated with the activated zone. A
signal is sent to the FACP, which starts the alarm sequence.
Wet sprinkler system specific:
System operates automatically upon the fusing of a single fire sprinkler.
Operational Sequence:
Wet System – Alarm Initiation – Water through a single sprinkler head
operates a contact on the wet system flow switch. Closed contact on the
flow switch will provide alarm signal to the FACP and activate the local
audible visual alarms. System alarm will be transmitted to Central Station
and to the Northampton Fire Department.
Wet System – Supervisory Initiation - Upon closing of control valve,
tamper switch will initiate supervisory signal to the FACP and activate
supervisory audible signal. System supervisory signal is transmitted to
Central Station and to the authorized owner’s contact representative.
Dry System – Alarm Initiation - Water through a single sprinkler head
operates a contact on the dry system pressure alarm switch. Closed
contact on the switch will provide alarm signal to the FACP and activate
the local audible visual alarms. System alarm will be transmitted to
Central Station and to the Northampton Fire Department.
Dry System – Supervisory Initiation - Upon closing of control valve or
activation of the low/high air pressure switch will initiate supervisory
signal to the FACP and activate supervisory audible signal. System
supervisory signal is transmitted to Central Station and to the authorized
owner’s contact representative.
(.iii) Testing Criteria
All tests to be witnessed by Northampton Building Department and Fire Department
which includes hydrostatic pressure testing of the wet and dry pipe system at 200 psi for
2 hours in accordance with NFPA 13, 2013 and FM Global Pamphlet 1-12 & 3-26.
A modified existing 6” Underground sprinkler water service will be relocated to the
mechanical on the first floor from underneath the existing stair. This service supply pipe
originates on Henshaw Avenue. The new relocated portion of the 6” supply shall be
installed, tested, and flushed in accordance with NFPA 13, 2013 and the Northampton
Water Department. Contractor’s material and test certificates for above ground and
underground shall be provided by the installing contractor(s) other requirements shall
include the following.
1. Full forward flow test of the backflow preventer at Highest Sprinkler
demand rate in GPM.
3. 2" main drain test shall be conducted and record static and residual
pressures on the test certificates.
4. System operational and alarm test on the system from the
inspector's test connection in accordance with NFPA 13, 2013.
5. NFPA 72 “Records of Completion by Fire Alarm Contractor.
6. Central station verification that the alarm and supervisory signals are
appropriately received and transmitted to the Northampton Fire
Department.
Testing Equipment and Tools
Fire Sprinkler Specific:
a. Manufacturer's instructions
b. Approved narrative report, sequence of operations section
c. Flow measuring devices- pitot tube for backflow preventer full forward
flow test
d. Gauges- main riser for 2" drain and hydrostatic testing
e. Fire hose if required to direct backflow flushing
Fire Alarm Specific:
a. Fire alarm system technician authorized by the manufacturer to
program and test the fire alarm system
b. Fire Alarm system and sprinkler system testing notification
announcements to the occupants of the building
c. Construction documents and shop drawings
d. Approved sequence of operations
e. Voltage meters
f. Simulated smoke
g. Applicable panel and pull station keys
Approval Requirements
a. Certification from JFV Engineering, LLC stating that the fire
protection sprinkler system has been installed in accordance with the
approved fire protection construction documents and that he has reviewed
the as-built drawings for conformance to 780 CMR 901.7.4 and has
identified deviations if any, from the approved fire protection construction
documents.
b. Confirmation by the building owner/developer or authorized
representative that they have received the as-built sprinkler system shop
drawings from the installing contractor
c. Material Test, Performance and Completion Certificates, properly
executed by the installing contractor in accordance with the applicable
NFPA Standards.
d. Satisfactory functional test of all fire protection systems witnessed by the
Building official and the head of the fire department or their designees.
e. Fire Service Group is in charge of setting up and conducting the testing of
the work under their scope. Fire Service Group will provide test
certificates to authorities having jurisdiction for FSG’s scope of work.
B: Building Site Access
Building site access is from Henshaw Avenue.
C: Fire Hydrants Locations & Water supply Info
1.1 There are existing Hydrants on Henshaw Avenue and on access ways
throughout the immediate area. These hydrants are available for hose stream allowances
and Fire Department operational requirements.
1.2 A Water flow test on Henshaw Avenue on June 29, 2022, which yielded the
following: 90 PSI Static, 76 PSI Residual with 1203 GPM flowing. The 6” supply is
more than sufficient to adequately support the sprinkler system needed for the
building.
D: Type/description and design layout of the automatic sprinkler system
1.1 The sprinkler systems shall be a wet system throughout the building except for
the cupola. There will be a dry system installed at the attic level just below the
cupola and penetrate the roof to access the space.
1.2 The NFPA 13 2013 and FM Global hazard classifications are: adjusted
design area ordinary hazard Group 2 occupancy for Mechanical spaces on the
first-floor level, Light hazard residential design as required by FM Global
Pamphlet 3-26 shall be designed for the dormitory rooms and adjacent
spaces, and the unused attic space is designed for light hazard density over the
most remote 1500 square feet.
1.3 Water supply will be the modified 6” service connected to the existing water
main in Henshaw Avenue.
1.4 4” Storz fire department connection provided on new system riser in
accordance with the Northampton Fire Department.
Hydraulic Calculation Summaries:
Area 1 – Attic Wet System: .10 over the most remote 1950 square feet –
739.31 GPM at 67.35 psi at the source. Flow includes 250 GPM hose stream
allowance.
Area2 – 3rd Floor Dormitory: 4 Residential Sprinklers – 331.31 at 56.60 psi
at the source. Flow includes 250 GPM hose stream allowance.
Area 3 – 2nd Floor Dormitory: 4 Residential Sprinklers – 340.59 GPM at
75.27 psi. Flow includes 250 GPM hose stream allowance.
Area 4 – Lower-Level Mechanical Spaces – 835.16 GPM at 62.96 psi at the
source. Flow includes 250 GPM hose stream allowance.
E: Automatic sprinkler system control equipment location
The sprinkler control equipment will be located in mechanical room on the first floor
mechanical space level. Sprinkler control valves and equipment shall accessible and
clearly marked for the fire department. Fire Department Connection and Access location
identification lettering shall be verified with the Northampton Fire Department and shall
comply with the Massachusetts Building Code CMR 780.
F: Type/Description and design layout of the standpipe system
Based on the architectural code analysis dated May 24, 2022 for Alterations Level 3,
standpipes are not required per section 804.3 of the Massachusetts IEBC - …where
the work area is located more than 50 feet above….the fire department access. The
4th floor is 41 feet above grade.
G: Standpipe Hose valves
Not Required (See Item F: above)
H: Fire department connection type and location
a. A new fire department connection will be located so to be accessible from Henshaw
Avenue. Final Location shall be confirmed with the Northampton Fire
Department.
b. The fire department connection will be a 4”storz connection per Northampton
Fire Department.
I: Type/Description and design layout of fire protection signaling system
Fire alarm systems and components- audio and visual appliances installed throughout in
accordance with NFPA 72 by a MA licensed fire alarm contractor.
1.1 The system shall be installed and programmed so upon actuation of an alarm, trouble
or supervisory signal at the fire alarm control unit, a corresponding signal shall be
reported to the supervising station.
1.2 The protected premises will be monitored by a listed central station service in
compliance with NFPA 72.
1.3 The system shall be installed so that it is complaint with the 2013 edition of the
NFPA 72, National Fire Alarm and signaling code, NFPA 1, ADA, 521 CMR, and
the Mass. Amendments to 2015 International Building Code.
J: Fire protection signaling control equipment and remote annunciator location
The Fire Alarm control Panel shall be located in accordance with NFPA 72 and the
Northampton Fire Department. Depending on the location of the FACP, a remote
annunciator may be required at a location acceptable the Northampton Fire
Department.
K: Type/Description and design layout of the smoke control or exhaust systems
Not Required
L: Smoke control or exhaust systems control equipment location
Not Required
M: Building Life safety features (auxiliary functions) required to be integrated into fire
protective signaling system.
Not Applicable
N: Type/Description and design layout of the fire extinguishing systems.
Fire extinguishers are to be provided per NFPA 10 and acceptable the Northampton
Fire Department.
O: Fire extinguishing systems control location.
Not Applicable
P: Fire Protection System equipment room location
1.1 The fire protection equipment room will be located in the mechanical space
located on the first-floor level.
1.2 The Fire Alarm control Panel located in accordance with NFPA 72 and the
Northampton Fire Department.
Q: Fire protection systems equipment identification and operation signs
To be provided per NFPA 13 and NFPA 72
R: Fire protection systems alarm/supervisory signal transmission method and location
The fire alarm control panel will transmit all fire alarm system signals to a listed
central station monitoring service in accordance with NFPA 72, which reports all
alarm signals to the Northampton fire department. Supervisory signals from tamper
switches and the low air pressure switch will be forwarded to the building owner
representative by the central station monitoring service.
S: Fire Command center location
Not Required
T: Type/description and the location of emergency alarm systems
Not Required
U: Type/description and the location of any alternative fire suppression system or
protection
Not Required
V: Type/description and the location of any carbon monoxide protection
As Required by the Northampton Fire Department
W: Emergency responder radio coverage type/location.
To be determined by actual Northampton Fire Department radio testing
within the Dormitory and all parts therein. It is advised that NFD conduct
this test as soon as possible as BDA equipment typically has a significant lead
time.