Loading...
31D-134 221mainstreet Construction Control Affidavit.pdf Main Street Cleaners Code Review.pdfMain Street Cleaners Code Review Thomas Douglas Architects Inc Main Street Cleaners 221 Main St. 196 Pleasant St. Northampton, MA Northampton, MA 413-585-0641 1 of 8             CODE  REVIEW             April  4,  2014   Main  Street  Cleaners   221  Main  Street   Northampton,  MA     Applicable  Building  Code:  MA  780  CMR  Eighth  Addition   IBC,  IEBC  International  EXISTING  Building  Code,  2009   ZONING  DISTRICT:  CB       PROPOSED  RENOVATIONS:   PROJECT  DESCRIPTION:   • Update  the  former  retail  space.  Remove  the  non-­‐structural  sheetrock  walls.   Expose  the  existing  original  metal  ceiling.  Install  dry  cleaning  equipment.   Install  a  new  glass,  metal  and  wood  storefront/entry.  Install  new  step  at  the   exterior  entry  to  the  2nd  floor.   •   Use  Groups   • Existing:  This  is  a  former  M  use  group.     • Proposed:  Business  Group  B,  Dry  Cleaning  and  Laundry   • This  business  is  not  classified  as  a  Group  H  –  high  hazard  occupancy.     • The  presence  of  hazardous  materials  is  not  greater  than  those  listed  in   IBC  table  307.1(1).  This  table  governs  the  maximum  allowable  quantity   per  control  area  of  hazardous  materials  poising  a  physical  hazard.  This   Business  will  not  store  more  than  120  gallons  of  combustible  class  II   liquids.  (the  proposed  use  has  a  maximum  of  55  gallons  of  Hydrocarbon   solvent  cleaning  fluid  on  site  a  1  time)   • This  business  qualifies  for  the  exceptions  to  a  Hazardous  Use  Group  by   meeting  307  High  Hazard  Group  H  exception  4:  Cleaning   establishments  that  utilize  combustible  liquid  solf3nts  having  a  flash   point  of  140  F  or  higher  in  closed  systems  employing  equipment  listed   by  an  approved  testing  agency,  provided  that  this  occupancy  is   separated  from  all  other  areas  of  the  building  by  1-­‐hour  fire  barriers   constructed  in  accordance  with  section  707  or  1-­‐hour  horizontal   assemblies  constructed  in  accordance  with  section  712  or  both.   • The  hydro  carbon  cleaning  solvent  is  Exxon  Mobile  DF  2000:   Code Review Thomas Douglas Architects Inc Main Street Cleaners 221 Main St. 196 Pleasant St. Northampton, MA Northampton, MA 413-585-0641 2 of 8 DF-2000 Fluid is within the NFPA 32 Class III A solvent classification. This classification is based on the flash point of the solvent being within the range of 140°F and 200°F. Because of this classification, the drycleaning plant using DF-2000 Fluid is governed by NFPA 32 guidelines for Class III A plants. Electrical wiring of a Type III A plant should be in accordance with NFPA 70 (National Electrical Code) for ordinary locations. There may be more stringent requirements for distillation and drying equipment. Separation requirements for Type III A Dry-cleaning Plants are outlined in Section 6.1.2.1 of NFPA 32 which is quoted below. Automatic sprinklers are required for such plants unless the conditions of Exception No. 2 below are met1. NFPA has just released an errata for NFPA 32 where Section 6.1.2.1 Exception 2 should read as follows: "(a) Features that limit oxygen concentrations to less than 8 percent by volume."   Code Review Thomas Douglas Architects Inc Main Street Cleaners 221 Main St. 196 Pleasant St. Northampton, MA Northampton, MA 413-585-0641 3 of 8 • This  project  will  meet  the  requirements  of  exception  No.  2  above  (less   than  330  gal)  and  the  proposed  fire  separation  will  be  1  hour  between   this  tenant  and  those  above.     • We  believe  the  existing  ceiling  is  plaster  with  a  decorative  metal  finish.   We  believe  it  will  meet  the  requirements  of  IBC  Table  720.1(3)  floor   assembly  item  number  13-­‐1.2  which  is  rated  as  a  1  hour  ceiling   construction.  Further  analysis  will  be  compeleted  by  the  builder  to   confirm  the  existing  conditions.     • The  components  of  item  number  13-­‐1.2  are:   • Double  wood  floor  over  wood  joists  spaced  16”  on  center   • 5/8”  cement  or  gypsum  plaster  on  metal  lath.  Lath  fastended  with  1   ½”  by  No.  11  guage  by  7/16”  head  barbed  shank  roofing  nails  spaced   5”  on  center.  Plaster  mixed  1:2  for  scratch  coat  and  1:3  for  brown  coat   by  weight,  cement  to  sand  agreggate.     • The  current  level  of  safety  or  sanitation  will  NOT  be  reduced  and  the   portions  altered  shall  conform  to  the  requirements  of  the  IBC,  including   interior  finishes,  interior  floor  finishes,  and  interior  trim.     Construction  Type   • 3B     Sprinkler  System   • No  sprinkler  systems  exist  in  the  building.  No  new  systems  are  proposed.       704.4  Fire  alarm  and  detection:   • There  is  a  fire  alarm  system  in  the  tenant  space  with  pull  stations.  The   system  will  be  modified  as  needed.     OCCUPANCY Occupant Load Calculation (1004.4.1) Former M use B use Occupants Approximately 60 10     According  to  the  IEBC  this  renovation  is  being  reviewed  as:   Work  Area  Method,  Chapter  4   Compliance  with  Chapter  6-­‐  Alterations  Level  1-­‐  new  finishes  and  fixtures   Chapter  7-­‐  Alterations  Level  2  -­‐  Construction  of  the  new  entry.  Reconfiguration  of   HVAC.  Structural  work  in  basement  and  1st  floor.     Code Review Thomas Douglas Architects Inc Main Street Cleaners 221 Main St. 196 Pleasant St. Northampton, MA Northampton, MA 413-585-0641 4 of 8 Fire  Resistive  Required  Types  of   Construction,  Table  601  IBC   Building  Element Type  3B Primary  Structural   Frame   0 Bearing  walls,  Exterior 2 Bearing  walls,  Interior 0 Nonbearing  walls  and   partitions,  exterior 0 Nonbearing  walls  and   partitions,  interior 0 Floor  construction  and   secondary  members 0 Roof  construction  and   secondary  members 0     Work  Area  Method  Calculations   The  existing  tenant  space  is:     First  story:  1,426  square  feet   Basement:  1,426   Total  tenant  area:  2,852   The  new  work  area  is  840  square  feet   The  work  area  is  29%  of  the  aggregate  area  of  tenant  space.     Total  Area  of  existing  building:  5,570  square  feet   The  tenant  space  represents  51  %  of  the  total  building   The  work  area  represents  15%  of  the  total  building.     704  Fire  Protection:   704.2,  912.2.1  Automatic  sprinkler  systems   Automatic  sprinkler  systems  are  NOT  required  in  this  project  because  of  the   exceptions  in  704.2.2  and  MGL  148  26G   The  following  conditions  are  present:  (IEBC)   The  Level  2  work  area  does  not  exceed  50%  of  the  building  floor  area     MGL  148  26G:     Sprinklers  are  required  if:  The  overall  building  area  is  greater  than  7,500  square  feet.     • The  total  building  area  for  this  building  is  less  than  7,500  square  feet   (5,570  square  feet).   Major  alterations  are  work  which  is  “major”  in  scope  or  expenditure,  and  which   results  in  changes  affecting  a  substantial  portion  of  the  building”  as  defined  in  MGL   148  26G     Code Review Thomas Douglas Architects Inc Main Street Cleaners 221 Main St. 196 Pleasant St. Northampton, MA Northampton, MA 413-585-0641 5 of 8 • The  reconfigurations  in  the  work  area  do  not  rise  to  the  level  of  “major   alterations”   Major  alterations  or  modifications  are  reasonably  considered  major  in  scope  when   such  work  affects  33%  or  more  of  the  total  gross  square  footage  of  the  building,   calculated  in  accordance  with  26G.     • The  work  area  for  this  project  is  less  than  33%  of  the  total  gross  square   footage  of  the  building.     Major  alterations  or  modifications  are  reasonably  considered  major  in  scope  or   expenditure  when  the  total  cost  of  the  work  (excluding  costs  relating  to  sprinkler   installation)  is  equal  to  or  greater  than  33%  of  the  assessed  value  of  the  subject   building,  as  of  the  date  of  permit  application.     • The  costs  for  this  project  are  less  than  33%  of  the  assessed  value  of  the   building.       Level  1  work  requirements:   The  removal  and  replacement  or  the  covering  of  existing  materials,   elements,  equipment  or  fixtures  using  new  materials,  elements,  equipment   or  fixtures  that  serves  the  same  purpose   This  project  will  repair  and  refinish  the  existing  plaster  walls  and  metal  ceilings   602.1  Interior  finishes:  All  newly  installed  wall  and  ceiling  finishes  shall  comply  with   the  IBC     603  Fire  Protection:   Alterations  shall  be  done  in  a  manner  that  maintains  the  level  of  fire  protection   provided.  This  Project  will  not  affect  the  level  of  fire  protection  that  is  currently   provided.       See  the  “Use  Group”  section  for  detailed  information  about  required  fire   separations.       604  Means  of  Egress   Repairs  shall  be  made  in  a  manner  that  maintains  the  level  of  protection  provided  for   the  means  of  egress.     606  Structural:   Structural  changes  are  proposed:  The  rear  brick  wall  of  the  building  is  damaged   and  new  steel  is  being  installed  to  repair  the  brick.  See  structural  drawings.       607  Energy  Conservation:     See  711  below         Code Review Thomas Douglas Architects Inc Main Street Cleaners 221 Main St. 196 Pleasant St. Northampton, MA Northampton, MA 413-585-0641 6 of 8 Level  2  work  requirements:   The  reconfiguration  of  space,  the  addition  or  elimination  of  any  door  or   window,  the  reconfiguration  or  extension  of  any  system,  or  the  installation   of  any  additional  equipment.     Alterations  Level  2  -­‐  Construction  of  the  new  entry.  Reconfiguration  of  HVAC.   Structural  work  in  basement  and  1st  floor.     701.3  Compliance   New  electrical  equipment  must  comply  with  section  708   Length  of  dead  end  corridors,  comply  with  705.6  There  are  no  proposed  dead  end   corridors.   Minimum  ceiling  height  of  newly  created  habitable  and  occupied  spaces  shall  be  7   feet.  There  are  no  newly  created  spaces.     705  Means  of  Egress   The  proposed  tenant  space  will  include  2  means  of  egress.  One  is  on  the  1st  floor.   One  is  in  the  basement     705.4.4  Panic  Hardware   In level 2 work areas, Panic hardware is only required for A uses with occupancies over 100. This project does not have this occupancy count or use.   705.7  Means  of  Egress  lighting   All  means  of  egress  shall  have  compliant  exit  signs.     705.7  Exit  Signs   The  tenant  space  shall  have  compliant  egress  lighting     711  and  607  Energy  Conservation:     Level  1  and  2  alterations  are  permitted  without  requiring  the  entire  building  to   comply  with  the  International  Energy  Conservation  Code.  Alterations  (new   construction)  shall  comply  with  the  International  Energy  Conservation  Code.     A  building  that  undergoes  Level  2  alterations  is  required  to  meet  a  certain  level  of   energy  compliance.   Where  there  are  reconfigurations  of  the  space  or  new  doors  or  windows,  any  such   new  element  is  required  to  meet  the  International  Energy  Conservation  Code.   Elements  within  the  building  that  are  not  being  affected  do  not  heed  to  be  evaluated   and  do  not  nee  to  comply  with  the  energy  provisions.  Essentially  the  entire  building   is  not  required  to  meet  the  energy  provisions;  only  a  degree  of  possible  improvement   in  the  energy  performance  of  the  building  is  intended  to  be  achieved  by  making  the   new  elements  meet  the  IECC.  In  certain  cases  where  the  reconfiguration  of  the  space   might  have  resulted  in  the  creation  of  new  spaces  the  newly  created  space  should  be   evaluated  as  a  whole  for  compliance  with  the  energy  provisions  even  though  some  of   Code Review Thomas Douglas Architects Inc Main Street Cleaners 221 Main St. 196 Pleasant St. Northampton, MA Northampton, MA 413-585-0641 7 of 8 the  element  within  the  space  might  actually  not  have  been  altered.  Likewise,  in  a   case  where  an  existing  mechanical  system  is  being  extended  to  other  areas  or  new   ductwork  is  being  installed  to  reconfigure  and  reroute  the  ducts  to  various  spaces,  it   is  only  required  to  have  the  new  elements  meet  the  energy  provisions  and  not  the   entire  system.   Any  new  replacement  windows  will  have  a  maximum  U  value  of  0.4   Any  new  entrance  doors  will  have  a  maximum  U  value  of  0.8   None  of  the  existing  exterior  walls  or  the  roof  are  being  altered,  so  no  new   insulation  is  required.       806  Accessibility   CMR  521       Valuation  of  Project:   • This  project’s  construction  costs  are:  $85,000   • The  assessed  value  of  the  building  is:  $340,500   • The  cost  of  the  project  is  27%  of  the  assessed  valuation  of  the  tenant   space.     3.3.1  b.  If  the  work  costs  $100,000  or  more,  then  the  work  being  performed  is  required   to  comply  with  521  CMR.  In  addition,  an  accessible  public  entrance  and  an  accessible   toilet  room  shall  be  provided.     3.3.2  If  the  work  performed,  including  the  exempted  work,  amounts  to  30%  or  more   of  the  full  and  fair  cash  value  of  the  building,  the  entire  building  is  required  to  comply   with  521  CMR.   3.3.3  Alterations  by  a  tenant  do  not  trigger  the  requirements  of  3.3.1B  and  3.3.2  for   other  tenants.     This  project’s  construction  costs  are  less  than  30%  of  the  assessed  value  of  the   building  and  less  than  $100,000.     We  have  received  a  variance  from  the  AAB  for  the  non-­‐complying  entry  door.       This  door  does  not  have  the  required  level  spaces  on  either  side  of  it.     Existing  access  to  this  level  of  the  building  is  from  the  sidewalk  via  a  ramp.  The   entry  door  is  located  on  the  ramp.  We  propose  to  relocate  the  entry  door  from  the   end  of  the  ramp  to  the  middle  of  the  ramp.  Because  we  do  not  have  a  level  space   on  either  side  of  the  entry  door,  we  propose  a  power  door  operator  as  a  compliance   alternative.  We  will  provide  new  handrails  on  both  sides  of  the  ramp.       We  have  received  approval  from  the  DPW  for  a  new  granite  step  at  the  entry  to  the   2nd  floor  stair/landing.   Code Review Thomas Douglas Architects Inc Main Street Cleaners 221 Main St. 196 Pleasant St. Northampton, MA Northampton, MA 413-585-0641 8 of 8       End  of  Document   Permit drawings.pdfmainstreetcleaners2.3.14.v2014 Architects 196 Pleasant Street, Suite 202 Northampton, MA 01060 413-585-0641 http://www.tdouglasarchitects.com REGISTERED ARCHITECT, COMMONWEALTH OF MASSACHUSETTS This drawing is not intended nor shall it be used for construction purposes unless the Signed professional seal of a registered architect employed by Thomas Douglas Architects is affixed in the space below. The Architect shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. THOMAS DOUGLAS Rev Date Description Project Title 221 Main Street Northampton, MA 01060 Issue Date: Drawn By: Checked By: Project ID: Drawing No. Project North 1 10/21/2013 Progress Sheet Title Scale: 10/08/2013 EB TD #### AS NOTED REVISIONS: 4/7/2014 2 1/21/2014 Progress 3 2/6/2014 Code review 4 4/7/2014 Demo Permit PROPOSED A-100 UP 14 HOT WATER 16 DRY VAC 15 AIR COMPRESSOR 1,417 square feet RE-USE EXISTING BOILER VENTING FAN. RETURN TANK BLOW DN RE-USE EXISTING RE-USE EXISTING ELEC GAS GAS GWB SOFFIT TO REMAIN HVAC DUCT 36X36X12 CONCRETE PAD SEE STRUCTURALS NEW WALL AT REMOVED BRICK WALL TOILET ROOM TO REMAIN TYPICAL GAS BOLIER DIRECT VENTING NOTE: VENTING FANS FOR FRESH AIR INTAKE ONLY. ALL PROPOSED EQUIPMENT FOLLOWS STATE ENVIRONMENTAL PROJECTION REQUIREMENTS. 3'-0" 3'-0" 1'-4" 3'-0" 3'-0" PORTION OF EXISTING BRICK WALL TO REMAIN 1'-4" REMOVE COLUMNS AND LINTEL NO WORK IN THIS AREA RETAIN ALL EXIT AND EMERGENCY LIGHTING ALTER FLOOR JOISTS ABOVE FOR EXTENDED RAMP REINFORCE FLOOR JOISTS ABOVE FOR DC MACHINE RETAIN ALL EXIT AND EMERGENCY LIGHTING RETAIN ALL EXIT AND EMERGENCY LIGHTING 17'-2" RELOCATED FURNACE GWB SOFFIT TO REMAIN NOTE: USE FIRE CAULKING AT ALL PENETRATIONS IN BRICK PARTY WALL TO ACHIEVE 2 HOUR FIRE-RATING EXISTING BRICK WALL 2 HOUR FIRE RATING 1 HOUR FIRE RATING AT EXISTING CEILINGS PROPOSED BASEMENT FLOOR 1/4" = 1'-0"3 FRONT COUNTER NEW HANDRAIL NEW HANDRAIL EXISTING RAMPED AREA EXISTING RAMPED AREA 3'-0" KNOX BOX 23'-10 5/8" 3'-0" FRONT COUNTER 2'-0" x 4'-8" SWEATER 2'-7" X 5'-2" WASHER 36" X 48" LEGGER PRESSER 4' X 6' SUZE 5' X 1'-6" JAMES PRESSER 6' X 4'-0" SPOTTING 4' X 2' DC MACHINE 5' X 6' NEW H/C DOOR BUTTON NEW ALUMINUM STOREFRONT REMOVE EXISTING STONE, INSTALL WATERPROOF MEMBRANE. INSTALL NEW FLOOR SURFACES CERAMIC TILE FLOOR INTERIOR. CONCRETE EXTERIORØ 5'-0" 5'-0" 2'-6" SHIRT COUNTER 2'-0" x 9'-2" NEW COUNTER 3'-4" 3'-0" 3'-11" 3'-0" SMALL WASHER 27" X 27" DRYER 26" X 29" 1,460 square feet 10 OCCUPANTS MAX NEW STEEL COLUMN AND BEAM REMOVE FURRED OUT WALL PATCH, SKIM COAT AND PAINT ORIGINAL PLASTER WALL. REMOVE FURRED OUT WALL PATCH, SKIM COAT AND PAINT ORIGINAL PLASTER WALL. RE-USE EXISTING CLOTHES CONVEYOR. CONFIRM DIMENSIONS FIX EXISTING WINDOWS CLOSED FIX EXISTING WINDOWS CLOSED REMOVE FURRED OUT WALL NEW OPERABLE WINDOW IN LOCATION OF EXISTING OPENING 18'-1" 2'-6" 2'-6" 2" 3'-0" 1'-0" FRONT COUNTER 2'-0" x 5'-0" ASSEMBLE TABLE 2'-1" X 5'-0" 3'-5" 11'-0" 1'-0" CUFF PRESS 40" X 24.5" EXISTING DUCT TO BSMT TO REMAIN. REMOVE FRAMING AROUND IT 1 1 0 / 2 1 / 2 0 1 3 P r o g r e s s FLOOR MOUNTED CONVEYER: PROVIDE ADDITIONAL POSTS AND FLOOR STRUCTURE FLOOR MOUNTED CONVEYER: PROVIDE ADDITIONAL POSTS AND FLOOR STRUCTURE NEW H/C DOOR BUTTON REINFORCE EXISTING FLOOR JOISTS BELOW NEW EXTENDED RAMP AREA REMOVE EXISTING FLOOR JOISTS AND INSTALL NEW SLOPED JOISTS NO CHANGES TO STAIR 1'-0 1/2" UP CARPET ON UNDERLAYMENT SHEET VINYL ON UNDERLAYMENT 4" 25'-0" 8'-8 5/8" PIONEER CONTRACTOR TO RELOCATE CLOTHES HANGING BARS FROM FORMER LOCATION TO THIS AREA NEW HAND SINK 3'-8" SHIRT PRESS 6'-0" X 4'-6" 8" UP EXISTING BASEMENT BELOW 1'-0" 1'-0" NEW CONCRETE HALF WALL WITH STONE CAP AND CONTINUOUS METAL HAND RAILING. 11" METAL HAND RAILING. 1'-0" 3'-6 1/2" 8" 1'-4" 5'-0"9'-0 1/2" 2 A-501 1'-11" 5'-4" NEW ALUMINUM HANDRAIL 1 A-501 REMOVE EXISTING STONE, INSTALL WATERPROOF MEMBRANE. INSTALL NEW FLOOR SURFACES CERAMIC TILE FLOOR INTERIOR. CONCRETE EXTERIOR 69'-8" NEW ONE-PIECE GRANITE STEP. DOWEL INTO SIDEWALK. ±1'-1" 3'-0" 1 1 0 / 2 1 / 2 0 1 3 P r o g r e s s P2 P2 P2 P2 P2 EXISTING EL= 7'-8" A.F.F. NEW EL = 11'-9" A.F.F. EXIST EL= 9'-11 1/2" A.F.F. NEW EL = 11'-9" A.F.F. EXISTING EL= 7'-5 3/4" A.F.F. NEW EL = 11'-9" A.F.F. EXISTING EL= 10'-5 1/2" A.F.F. NEW EL = 11'-9" A.F.F. DEMO GWB CEILING DEMO GWB CEILING DEMO GWB CEILING DEMO GWB CEILING RE-USE EXISTING CLOTHES CONVEYOR. CONFIRM RELOCATION WITH EQUIPMENT VENDOR. EXISTING RECESSED LIGHTS TO REMAIN. TO REMAIN AS CONDO'S "COMMON-SPACE." EXISTING RECESSED LIGHTS TO REMAIN. TO REMAIN AS CONDO'S "COMMON-SPACE." CURRENT SWITCHING TO REMAIN. REMOVE 2 "COMMON SPACE" RECESSED LIGHTS. REMOVE EXISTING "COMMON SPACE" WIRING. ALL NEW LIGHTS WILL BE WIRED TO TENANT'S ELECTRICAL METER. REMOVE 2 "COMMON SPACE" RECESSED LIGHTS. REMOVE EXISTING "COMMON SPACE" WIRING. ALL NEW LIGHTS WILL BE WIRED TO TENANT'S ELECTRICAL METER. P1 P1 SMOKE SMOKE EXIT EMERGENCY P EMERGENCY P1 P1 ROUND SPIRAL HVAC DUCT. SIZE TO BE DETERMINED. NEW BEAM. P1 P3 NEW POWER DOOR OPENER OPENER BUTTON EMERGENCY NEW H/C DOOR BUTTON PROPOSED RCP 1/4" = 1'-0"2 PROPOSED GROUND FLOOR 1/4" = 1'-0"1 0 4 8 12 16 SIDEWALK 7'-11 3/8" 11'-0" 7'-5 3/4" 7'-9 3/4" 7'-3" NEW STEEL FRAME 221 MAINS STREET NORTHAMPTON, MA 01060 JACOB SMITH ENGINEERING AND DESIGN 5- NOTE: THIS IS A PRELIMINARY DRAWING FOR PRICING - NOT FOR CONSTRUCTION 17'-2" 7'-9 3/4" NEW SPIRAL DUCT REMOVE FURRED-OUT WALLS TO ORIGINAL PLASTER WALLS REMOVE GWB CEILINGS AND SOFFITS TO ORIGINAL TIN CEILING PROP BLDG SECTION AT EXISTING REAR BRICK WALL 1/4" = 1'-0"1 Architects 196 Pleasant Street, Suite 202 Northampton, MA 01060 413-585-0641 http://www.tdouglasarchitects.com REGISTERED ARCHITECT, COMMONWEALTH OF MASSACHUSETTS This drawing is not intended nor shall it be used for construction purposes unless the Signed professional seal of a registered architect employed by Thomas Douglas Architects is affixed in the space below. The Architect shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. THOMAS DOUGLAS Rev Date Description Project Title 221 Main Street Northampton, MA 01060 Issue Date: Drawn By: Checked By: Project ID: Drawing No. Project North 1 10/21/2013 Progress Sheet Title Scale: 10/08/2013 EB TD #### AS NOTED REVISIONS: 4/7/2014 2 1/21/2014 Progress 3 2/6/2014 Code review 4 4/7/2014 Demo Permit A-300 SECTIONS BUILDING SECTION 1/4" = 1'-0"2 STOREFRONT ELEVATION 1/2" = 1'-0"3 Architects 196 Pleasant Street, Suite 202 Northampton, MA 01060 413-585-0641 http://www.tdouglasarchitects.com REGISTERED ARCHITECT, COMMONWEALTH OF MASSACHUSETTS This drawing is not intended nor shall it be used for construction purposes unless the Signed professional seal of a registered architect employed by Thomas Douglas Architects is affixed in the space below. The Architect shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. THOMAS DOUGLAS Rev Date Description Project Title 221 Main Street Northampton, MA 01060 Issue Date: Drawn By: Checked By: Project ID: Drawing No. Project North 1 10/21/2013 Progress Sheet Title Scale: 10/08/2013 EB TD #### AS NOTED REVISIONS: 4/7/2014 2 1/21/2014 Progress 3 2/6/2014 Code review 4 4/7/2014 Demo Permit KAWNEER ALUMINUM STOREFRONT AUTOMATIC DOOR OPENER CONCRETE RAMP. SLOPE TO MATCH EXISTING. 1" RISE TO 12" RUN SLOPE. 1'-0 1/2" 4'-7 1/2" 5'-8 1/2" 1'-8" 7'-11 1/2" HANDRAIL 36" ABOVE RAMP 3'-0" TRIFAB VG 451T (FRONT) ENTRANCE DETAILS OFFSET PIVOT/BUTT HUNG with SURFACE CLOSER 7-1/2" 7-1/2" BOTTOM RAIL OPTIONAL7-1/2" BOTTOM RAIL SINGLE ACTING OPTIONAL BOTTOM DOOR SWEEP DOOR JAMB NOTE: KAWNEER "190" NARROW STILE DOOR SHOWN ON THESE DETAILS. OTHER KAWNEER DOORS MAY BE USED. ENTRANCE DETAIL 7 ENTRANCE DETAIL 6 ENTRANCE DETAIL 5 SINGLE ACTING FOR SURFACE CLOSER DOOR JAMB SINGLE ACTING ENTRANCE DETAIL 9 SINGLE ACTING WITH SIDELITE (1" INFILL) DOOR JAMB ENTRANCE DETAIL 8 TRANSOM BAR (1" Infill) ENTRANCE DETAIL 4 TRANSOM HEAD (1" Infill) AT TRANSOM AREA DOOR OPENING 11/16" FH OD OPTIONAL 2"DLO 2-1/8" DOOR OPENING 3/32" 190 DOOR STILE 1/4" OD FW 2" 2-1/8" 3/32" DOOR OPENING 2-1/4"1/8" 190 Top Rail DOOR OPENING FH OD DLO 1/4" 2" 451T-126 SHIM SUPPORT 451T-VG-001 MULLION 451-VG-524 SHEAR BLOCK PKG. 4 1/2" 450-506 SHEAR BLOCK PKG. 451-VG-022 T-BAR ADAPTER 451-VG-004 GLASS STOP (EXTERIOR) 450-022 GLASS STOP (INTERIOR) 451-502 S/A T-BAR W/ WEATHERING 1 5/16" 2"DLO 451-VG-019 D/A DOOR JAMB 451-VG-019 D/A DOOR JAMB 069-177 DOOR STOP ASS'Y 028-260 #8 x 3/8" AB PHST 451-VG-033 POCKET INSERT 451-VG-019 D/A DOOR JAMB 1/4" 2" OD FW DLO 1/2" 069-177 DOOR STOP ASS'Y 028-260 #8 x 3/8" AB PHST 190 DOOR STILE ELEVATION NOT TO SCALE TRIFAB 451UT (CENTER) SCREW SPLINE ASSEMBLY OUTSIDE GLAZED / GLASS STOPS "UP" (1" INFILL) DETAIL 3 DETAIL 1 DETAIL 2 SILL WITH HP FLASHING DETAIL 2 HEAD DETAIL 1 JAMB DETAIL 3 4 1/2"" FH OD 1/4"" 2"" DLO 4 1/2"" 1/4"" OD FW 2"" DLO 4 1/2"" FH DLO 2" OD 1/2"" 1/4"" 452T-CG-126 SHIM SUPPORT 452T-CG-001 HEAD 452T-CG-037 FLASHING 451-CG-004 GLASS STOP 452T-CG-014 SILL 452T-CG-126 SHIM SUPPORT 452T-CG-001 JAMB DETAIL 7 DETAIL 6 DETAIL 8 DETAIL 4 DETAIL 5 DETAIL 9 ENLARGED STOREFRONT PLAN 1/2" = 1'-0"2 3/4" CDX PLYWOOD DECORATIVE PVC PANEL BATT INSUL, MIN R19 2X6 STUD WALL PT SILL PLATE 1/2" PLYWD SHEATHING ALUM FLASHING PVC TRIM STOREFRONT GLAZING FRAME ICE & WATER SHIELD MIN 8" FLASHING W/ BR & SEALANT PVC TRIM BOARD ICE & WATER SHIELD OVER SILL PLATE VARIES BOLT TO EXISTING FOUNDATION WALL 1X WOOD SILL NEW ALUMINUM STOREFRONT ENLARGEDRAMP MAIN STREET CLEANERS SIGNAGE EXISTING CANVIS AWNING TO REMAIN PEBBLE FACADE TO REMAIN EXISTING CORNICE TO REMAIN NEW SIGNAGE. TBD BY OWNERS. HANDRAIL 36" ABOVE RAMP 8'-0" 8'-0" X 3'-0" DOOR, WIDE STILE WITH SIDELIGHT PVC TRIM AUTOMATIC DOOR OPENER PVC TRIM 7 1/2"1'-0 1/2"3 1/2" 3 1/2" 3 1/2" NEW 7'-0" WIDE STILE DOOR TO SECOND FLOOR BY CONDO ASSOCIATION. NEW METAL HANDRAIL. WRAP AROUND EXTERIOR WALL. NEW STONE RISERS AND TREADS. NEW HALF WALL WITH METAL HANDRAIL ABOVE STOREFRONT DETAILS A-500 NOTE: STOREFRONT TO HAVE THE ABILITY TO BE DISMANTLED AND RECONSTRUCTED FOR FUTURE EQUIPMENT REMOVAL. STOREFRONT INSTALLATION TO BE CORDINATED WITH LARGE EQUIPMENT DELIVERY. EXISTING PEBBLE VENEER TO REMAIN EXISTING METAL ROOF OVER AWNING EXISTING OPERABLE CANVAS AWNING AND ASSOCIATED MECHANISMS TO REMAIN EXISTING GWB CEILING TO REMAIN ESTIMATED LOCATION OF STEEL BEAM. SIZE AND LOCATION TO BE CONFIRMED. 1x WOOD TRIM NEW ALUMINUM STOREFRONT EXISTING METAL STRUCTURE FOR AWNING PROPOSED STOREFRONT DETAIL 1 1/2" = 1'-0"1 Architects 196 Pleasant Street, Suite 202 Northampton, MA 01060 413-585-0641 http://www.tdouglasarchitects.com REGISTERED ARCHITECT, COMMONWEALTH OF MASSACHUSETTS This drawing is not intended nor shall it be used for construction purposes unless the Signed professional seal of a registered architect employed by Thomas Douglas Architects is affixed in the space below. The Architect shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. THOMAS DOUGLAS Rev Date Description Project Title 221 Main Street Northampton, MA 01060 Issue Date: Drawn By: Checked By: Project ID: Drawing No. Project North 1 10/21/2013 Progress Sheet Title Scale: 10/08/2013 EB TD #### AS NOTED REVISIONS: 4/7/2014 2 1/21/2014 Progress 3 2/6/2014 Code review 4 4/7/2014 Demo Permit STOREFRONT DETAILS A-501 8" 6" NEW RAMP 1 1/2" SECTION AT FRONT STAIR LANDING 1/4" = 1'-0"1 REMOVE EXISTING STONE, INSTALL WATERPROOF MEMBRANE. INSTALL NEW FLOOR SURFACES GRANITE STEP 7 1/4"7 1/4" 1/2" CONTINUOUS METAL PIPE HANDRAIL EXISTING STAIR LANDING SECTION AT FRONT STAIR LANDING 1/4" = 1'-0"2 STONE CAP GRANITE 11 1/2" 7 1/4" 2'-0"3" 7 1/4" 1'-2 1/2" STONE CLADDING ON LANDING, RISER CONCRETE HALF WALL WITH STUCCO FINISH 1/2" 1/2" MIN RISE FROM EXTERIOR LANDING TO DOOR THRESHOLD ± 1:25 SLOPE AWAY FROM BUILDING PVC TRIM SIDELIGHT WIDE STILE DOOR 10" 10"