10D-017 UL Listing Report AND 723 Test
January 03, 2007
Mr. Danny French
Contego International
334 Greyhound Pass West
Carmel, IN 46032
Our Reference: R25382 / 06CA51291
Subject: Report Of Surface Burning Characteristics Tests On Fire Retardant
Coating As Submitted By Contego International
Dear Mr. French
This Report summarizes the results of tests conducted under an investigation identified as
Assignment No. 06CA51291.
METHOD:
Each test was conducted in accordance with Standard ANSI/UL723, ninth edition; dated
August 29, 2003, "Test for Surface Burning Characteristics of Building Materials" (ASTM
E84).
The test determines the Surface Burning Characteristics of the material, specifically the flame
spread and smoke developed indices when exposed to fire.
The maximum distance the flame travels along the length of the sample from the end of the
igniting flame is determined by observation. The Flame Spread Index of the material is
derived by plotting the progression of the flame front on a time-distance basis, ignoring any
flame front recession, and using the equations described below:
A. CFS = 0.515 AT when AT is less than or equal to 97.5 minute-foot.
B. CFS = 4900/(195-AT) when AT is greater than 97.5 minute-foot.
Where AT = total area under the time distance curve expressed in minute-foot.
The Smoke Developed Index (SDI) is determined by rounding the Calculated Smoke
Developed (CSD) as described in UL 723. The CSD is determined by the output of
photoelectric equipment operating across the furnace flue pipe. A curve is developed by
plotting the values of light absorption (decrease in cell output) against time. The CSD is
January 03, 2007
Page 2
Contego International 06CA51291.Doc
derived by expressing the net area under the curve for the material tested as a percentage of the
area under the curve for untreated red oak.
The CSD is expressed as:
CSD = (Am/Aro) x 100
Where:
CSD = Calculated Smoke Developed
Am = The area under the curve for the test material.
Aro = The area under the curve for untreated red oak.
SAMPLES:
Sample Description
Test No. System
1 blank doug fir.
2 Fire Barrier coated doug fir.
3 Fire Barrier coated doug fir.
4 Fire Barrier coated doug fir.
Each test sample consisted of three 8 by 2 ft wide coated douglas fir decks butted end-
to-end to form the required 24 ft. long surface.
RESULTS:
The results are tabulated below are considered applicable only to the specific samples tested.
Data sheets and graphical plots of flame travel versus time and smoke developed versus time
are also enclosed.
January 03, 2007
Page 3
Contego International 06CA51291.Doc
Table 1: Test Summary
Test
No. Test Code Sample Description
CFS
Calculated
Flame
Spread
FSI
Flame
Spread
Index
CSD
Calculated
Smoke
Developed
SDI
Smoke
Developed
Index
1 12190606 blank doug fir. 62.74 65 68.9 70
2 12190607 Fire Barrier coated doug fir. 0.00 0 1.4 0
3 12190609 Fire Barrier coated doug fir. 1.77 0 28.2 30
4 12190610 Fire Barrier coated doug fir. 0.09 0 12.1 10
The Classification Marking of Underwriters Laboratories Inc. on the product is the only
method provided by Underwriters Laboratories Inc. to identify products, which have been
produced under its Classification and Follow-Up Service.
SURFACE BURNING CHARACTERISTICS CLASSIFICATION:
Based on the above test results, the following Classification is being established for the
product submitted.
SURFACE BURNING CHARACTERISTICS
Douglas
Surface Fir
Flame Spread 0
Smoke Developed 0-30
Number of Preliminary Coats None
Rate Per Coat (ft2/gal) -
Number of Fire Retardant Coats 2
Rate Per Coat (ft2/gal) 145
Number of Overcoats None
Rate Per Coat (ft2/gal) -
We are currently in the process of conducting various supplemental tests to establish
specifications in the Follow-Up Service Procedure for periodic follow-up tests at our
Northbrook facility. Upon completion of this work we will close the project.
January 03, 2007
Page 4
Contego International 06CA51291.Doc
Should you have any questions on the above, please contact the undersigned.
Very truly yours, Reviewed by:
Robert S Kiefer (ext. 42014) James F. Smith (ext. 42666)
Senior Engineering Associate Staff Engineering Associate
Fire Protection Division Fire Protection Division
Underwriters Laboratories Inc.
Project: 06CA51291 File: R25382 Test Code: 12190606
Tested by: HISLOP Engineer: KIEFER Date: 12/19/06
Employee #: 7036 Emp. #: 98874
TEST METHOD: The test was conducted in accordance with UL 723, 9th Edition
Client Name: Contego International
Test Duration 10 Minutes Test No.: 1 Hot Test: No
Mounting: Self Test Type: Classification Burn-Out Required: No
Test Sample: blank doug fir.
FLAME SPREAD RESULTS
Flame Spread Data
Distance
(Feet)
Time
(Sec)
Distance
(Feet)
Time
(Sec)
Ignition 40 9 150
0.5 52 10 178
1 60 11 202
2 68 12 232
3 82 13 242
4 88 14 272
5 100 15 316
6 104 16 440
7 132 16.5 500
8 142 17 576
Calculated Flame Spread (CFS): 62.74
Flame Spread Index (FSI): 65
Time to Ignition (sec): 40
Maximum Flame Spread (ft): 17.0
Area Under the Flame Spread Curve (ft.-min): 116.9
SMOKE RESULTS
Calculated Smoke Developed (CSD): 68.9
Smoke Developed Index (SDI): 70
Area Under the Smoke Curve (sq. in.): 2.98
Area Under Red Oak Curve (sq. in.): 4.32
Flame Spread / Smoke Results Contego International blank doug fir. 0102030405060708090100012345678910Time (Minutes)Obscuration (%)02468101214161820Flame Spread (feet)% ObscurationFlame Spread Test No. 1 Flame Spread Index: 65 06CA51291 / R25382 Smoke Developed Index: 70 12190606 Max. Flame Spread: 17.0
Underwriters Laboratories Inc.
Project: 06CA51291 File: R25382 Test Code: 12190607
Tested by: HISLOP Engineer: KIEFER Date: 12/19/06
Employee #: 7036 Emp. #: 98874
TEST METHOD: The test was conducted in accordance with UL 723, 9th Edition
Client Name: Contego International
Test Duration 10 Minutes Test No.: 2 Hot Test: No
Mounting: Self Test Type: Classification Burn-Out Required: No
Test Sample: Fire Barrier coated doug fir.
FLAME SPREAD RESULTS
Flame Spread Data
Distance
(Feet)
Time
(Sec)
Ignition 346
Calculated Flame Spread (CFS): 0.00
Flame Spread Index (FSI): 0
Time to Ignition (sec): 346
Maximum Flame Spread (ft): 0.0
Area Under the Flame Spread Curve (ft.-min): 0.0
SMOKE RESULTS
Calculated Smoke Developed (CSD): 1.4
Smoke Developed Index (SDI): 0
Area Under the Smoke Curve (sq. in.): 0.06
Area Under Red Oak Curve (sq. in.): 4.32
Flame Spread / Smoke Results Contego International Fire Barrier coated doug fir. 0102030405060708090100012345678910Time (Minutes)Obscuration (%)02468101214161820Flame Spread (feet)% ObscurationFlame Spread Test No. 2 Flame Spread Index: 0 06CA51291 / R25382 Smoke Developed Index: 0 12190607 Max. Flame Spread: 0.0
Underwriters Laboratories Inc.
Project: 06CA51291 File: R25382 Test Code: 12190609
Tested by: HISLOP Engineer: KIEFER Date: 12/19/06
Employee #: 7036 Emp. #: 98874
TEST METHOD: The test was conducted in accordance with UL 723, 9th Edition
Client Name: Contego International
Test Duration 10 Minutes Test No.: 3 Hot Test: No
Mounting: Self Test Type: Classification Burn-Out Required: No
Test Sample: Fire Barrier coated doug fir.
FLAME SPREAD RESULTS
Flame Spread Data
Distance
(Feet)
Time
(Sec)
Distance
(Feet)
Time
(Sec)
Ignition 366 3.5 570
0.5 542 4 574
1 550 4.5 580
1.5 554 5 592
2 556 5.5 598
3 558 6 600
Calculated Flame Spread (CFS): 1.77
Flame Spread Index (FSI): 0
Time to Ignition (sec): 366
Maximum Flame Spread (ft): 6.0
Area Under the Flame Spread Curve (ft.-min): 3.4
SMOKE RESULTS
Calculated Smoke Developed (CSD): 28.2
Smoke Developed Index (SDI): 30
Area Under the Smoke Curve (sq. in.): 1.22
Area Under Red Oak Curve (sq. in.): 4.32
Notes: After fire barrier coat charred up it fell ( late in the test ) resulting in the flame spread. In the first
test the charred coat did not fall.
Flame Spread / Smoke Results Contego International Fire Barrier coated doug fir. 0102030405060708090100012345678910Time (Minutes)Obscuration (%)02468101214161820Flame Spread (feet)% ObscurationFlame Spread Test No. 3 Flame Spread Index: 0 06CA51291 / R25382 Smoke Developed Index: 30 12190609 Max. Flame Spread: 6.0
Underwriters Laboratories Inc.
Project: 06CA51291 File: R25382 Test Code: 12190610
Tested by: HISLOP Engineer: KIEFER Date: 12/19/06
Employee #: 7036 Emp. #: 98874
TEST METHOD: The test was conducted in accordance with UL 723, 9th Edition
Client Name: Contego International
Test Duration 10 Minutes Test No.: 4 Hot Test: No
Mounting: Self Test Type: Classification Burn-Out Required: No
Test Sample: Fire Barrier coated doug fir.
FLAME SPREAD RESULTS
Flame Spread Data
Distance
(Feet)
Time
(Sec)
Ignition 339
0.5 595
Calculated Flame Spread (CFS): 0.09
Flame Spread Index (FSI): 0
Time to Ignition (sec): 339
Maximum Flame Spread (ft): 0.5
Area Under the Flame Spread Curve (ft.-min): 0.2
SMOKE RESULTS
Calculated Smoke Developed (CSD): 12.1
Smoke Developed Index (SDI): 10
Area Under the Smoke Curve (sq. in.): 0.52
Area Under Red Oak Curve (sq. in.): 4.32
Flame Spread / Smoke Results Contego International Fire Barrier coated doug fir. 0102030405060708090100012345678910Time (Minutes)Obscuration (%)02468101214161820Flame Spread (feet)% ObscurationFlame Spread Test No. 4 Flame Spread Index: 0 06CA51291 / R25382 Smoke Developed Index: 10 12190610 Max. Flame Spread: 0.5