10D-017 marney elec analysis 2016ARCHITECT J E F F R E Y S C O T T P E N N 77 Worthington Road, Huntington, MA 01050 tel. 413-667-5230 fax. 413-667-3082 jspsed@verizon.net 8 January 2016 – 3 February 2016 Investigation and Analysis Client: Marney Electric 175 Main Street, Leeds Northampton, MA 01053 General The former Alternative Recycling Systems offices shall be occupied by Marney Electric as their new headquarters. No additions are proposed, but some interior modifications shall be made to facilitate occupancy. These modifications shall meet relevant codes. The building is a steel framed building with insulated steel siding, interior CMU and wood-framed walls, thus Use Group B with some storage S-2 and Type III B construction. I have reviewed IEBC 2009, Chapter 3 Prescriptive Compliance Method. There are no exterior modifications proposed except installation of a cantilevered entry canopy and the lot has extensive existing paved parking and 20 feet wide access around the building. Here I will list relevant sections from code. IEBC 2009 301.2 – materials = existing (no dangerous conditions noted); new shall meet code 303 – alterations 303.1 exception 1 – existing stairway may remain in use where existing space and conditions constrain alteration (offices stair to remain) 303.5 – voluntary seismic improvements = the steel building is well braced and new interior walls shall be independent of the main structure; any steel alterations shall be carefully considered to increase bracing 306.1 – glass replacement = shall meet code as new 310 – accessibility – no modifications proposed; accessible path provided from main entry thru public areas to rest room (not modified or compliant; could be made compliant in the future) 310.7 – alterations affecting a primary function – the addition of walls in the office area shall maintain clear passage and existing door approaches with new features compliant. 310.8.1 – entrances = the main entrance shall be compliant 310.8.4 – stairs where none existed = the new stair to the new second level of the east portion shall be compliant with proper width, rise, run and handrails 310.8.11 – toilet rooms – currently provide 2 with non-compliant door width and without grab bars; no modifications proposed. one poorly constructed raised lavatory is to be removed. Request Code Compliance Alternative to allow continued use of existing lavatories. 310.8.14 – maximum threshold of 3/4” = exceeded between center and east garage bay at the first level; within business storage and staging area nonpublic and able-bodied requirement for employment IBC 2009 304 – Use Group B with additional storage S-2 406.2.8 – door to mechanical from parking only if ignition higher than 18” above floor Table 503 – max. 3 story 19,000sf (have 2 story, 3600sf footprint) Table 508.2.5 – Furnace room requires 1hr if furnace is over 400,000 BTUH or boiler 15psi + 10hp; or for storage of liq. Electrolyte batteries over 50gal. Or lithium ion over 1000lbs 508.3 – non-separated occupancies – since each (B and S-2) type of occupancy is well below allowed thresholds, there is no plan to fully separate occupancies 602.3 – Type III construction B, unprotected Table 601 – IIIB 0hr exterior; bearing walls 2hr – 2 layers of 5/8” type X gypsum shall protect the new 10” wall to support the new second floor and the stair wall Table 803 – interior finishes – exit elements Class A; corridors Class B; rooms Class C 906 – portable Fire Extinguishers = 1. in B occupancies near main entrance. 3. in areas where flammable or combustible liquids are stored – shall comply 907.2.2 – group B manual fire alarm not required Table 1004.1.1 – occupancy floor allowances = B 100 sf/person; Storage Stock and Shipping = 300 sf/person (B = 2886/100=29 + 2672/300 = 9; total 38 people) (B = 1227sf/100 = 13 + 4331sf/300 = 15; total 28 people) – the designated areas were incorrect; the Storage and Showroom and Flexible Space – Staging will be employee only Staging areas and were so designated in order to bring the public to the rear restroom which does not work as the restroom is not accessible and requires noncompliant level change 1005.1 – egress width .3 x 38 = 11 1/2” (at 1018.2 = 36”) shall provide 44” 1009.1 – stairway width 44” (exception under 50 occ = 36”; make 44”) 1009.4.2 – riser and tread = max. 7” rise, min. 11” tread (new to comply, existing to accept) Table 1015.1 – spaces with one exit; B = max 49 occ (have 38 total) 1018.2 – corridor width 44” (exception under 50 occ = 36”; make 44”) Table 1021.2 – stories with one exit; 2nd fl B = max 29 occ/75' travel (have 15occ tot 2nd fl /60' farthest point of travel); 1st fl B = max 49 occ/75' travel (have 38 occ total/65' farthest point of travel) – note: three existing exits from 1st fl; one proposed from each second fl, one additional at south center bay Plumbing Chapter 29 see 248 CMR Table 2902.1 – required fixtures – B = 1 wc/25 = 2; 1 lav male and female/40 = 1; 1 drinking fountain/100 = 1; 1 service sink (have two public lavatories) Code Compliance Alternatives Proposed accept existing stair in office area accept existing lavatories for continued use