Loading...
LIVE 155 FP1 1-25-17GENERAL NOTES1. SYSTEM INSTALLATION TO CONFORM TO NFPA 13 2013 EDITION.2:1(5,65(48,5('723529,'(+($77+528*+2877+(%8,/',1*720$,17$,1$0,1,0807(03(5$785(2)ƒFAHRENHEIT FOR ALL AREA PROTECTED w/ A WET PIPE SPRINKLER SYSTEM. THE SYSTEM IS TO BE MAINTAINED BY THEOWNER AS REQUIRED BY NFPA- 25.3. MAIN PIPING 1 12" & LARGER TO BE BLACK SCHEDULE 10 PIPE w/ SHOP WELDED OUTLETS OR FIELD INSTALLEDMECHANICAL TEES & GROOVED ENDS & FITTINGS.4. BRANCHLINE PIPING 1 12" & SMALLER, ARMOVERS, & DROPS/SPRIGS TO BE BLACK SCHEDULE 40 PIPE w/ THREADEDENDS & CAST IRON FITTINGS.5. BLAZEMASTER CPVC PIPING 1 12" & SMALLER TO BE INSTALLED WITH CPVC FITTINGS WHEN BRANCHLINES ARERUNNING IN THE TJI SPACES.6. PIPING IS TO BE SUPPORTED AS REQUIRED BY NFPA - 13. HANGERS ARE TO BE FIELD LOCATED TO BEST SUPPORT THEPIPE.7. STRUCTURAL LOAD ANALYSIS OF THE FIRE SPRINKLER SYSTEM AND IT'S RELATED COMPONENTS HAS NOT BEENINCLUDED AS A PART OF THIS CONTRACT.8. WORK IS LIMITED TO SPRINKLER SCOPE INDICATED ON THESE DRAWINGS.9. SPRINKLER SCOPE TO START AT NEW 6" SERVICE INSTALLED BY OTHERS.10. PENDENT SPRINKLERS ARE TO BE INSTALLED IN THE CENTER OF CEILING TILE. (+ -1") AS ALLOWED BY STRUCTURE & CLEARANCE FOR OTHER MECHANICAL/ELECTRICAL EQUIPMENT.11. DENOTES HYDRAULIC REFERENCE POINTS.12. ENGINEERED SEISMIC CALCULATIONS ARE NOT INCLUDED AS A PART OF THIS FIRE SPRINKLER CONTRACT.13. OWNER TO MAINTAIN 18" OF CLEARANCE FROM SPRINKLER DEFLECTOR TO THE TOP OF PENDENT LIGHT FIXTURES &STORAGE.14. PER MASSACHUSETTS GENERAL LAW CHAPTER 112 SECTION 81R STAMPED FIRE SPRINKLERS SHOP DRAWINGS ARENOT REQUIRED.15. DRAIN PIPING SHALL BE LOCATED WITH COORDINATION FROM THE GENERAL CONTRACTOR. DRAIN PIPING IS NOTSHOWN FOR CLARITY OF SPRINKLER PIPING.SYSTEM NOTES:1. BUILDING CONSTRUCTION IS COMBUSTIBLE. SHEET ROCK WILL BE ATTACHED TO THE BOTTOM OF ALL WOOD FLOOR JOISTS & TJI'S BY OTHERS. ALL WOOD THAT IS ABOVE THE CEILING TO BE FIRE RETARDANT TREATED WOOD AS DEFINED BY NFPA 703, STANDARDFOR FIRE RETARDANT -TREATED WOOD & FIRE RETARDANT COATINGS FOR BUILDING MATERIALS.2. OCCUPANCY: APARTMENT BUILDING (LIGHT HAZARD) WITH RETAIL SHOPS ON FIRST FLOOR (ORDINARY HAZARDGROUP II). FIRST FLOOR RETAIL AREA IS DESIGNED IN ACCORDANCE WITH ORDINARY HAZARD GROUP II. DESIGN DENSITY: .20/ 1261 SQ FT. w/ 250 GPM HOSE STREAM. THE REMOTE AREA IS REDUCED PER NFPA #13 SECTION 11.2.3.2.1 & APPROPRIATE CEILING HEIGHT.(14'-0") FIRST FLOOR MECHANICAL SPACES ARE DESIGNED IN ACCORDANCE WITH ORDINARY HAZARD GROUP II. DESIGN DENSITY: .20/983 SQ FT. w/ 250 GPM HOSE STREAM. THE REMOTE AREA IS REDUCED PER NFPA # 13 SECTION 11.2.3.2.1 & APPROPRIATE CEILING HEIGHT. (12'-6") FIRST FLOOR OFFICE SPACES ARE DESIGNED IN ACCORDANCE WITH LIGHT HAZARD. DESIGN DENSITY .10/902 SQ. FT. w/ 100 GPM HOSE STREAM. THE REMOTE AREA IS REDUCED PER NFPA # 13 SECTION 11.2.3.2.1 & APPROPRIATE CEILING HEIGHT. (10'-0") APARTMENT UNITS ARE DESIGNED TO MANUFACTURER'S RESIDENTIAL SPRINKLER REQUIREMENTS OR AT .10 DENSITY WHICHEVER IS HIGHER. 4 RESIDENTIAL SPRINKLERS CALCULATED PER NFPA # 13. FOURTH FLOOR CORRIDOR IS DESIGNED IN ACCORDANCE WITH LIGHT HAZARD. DESIGN DENSITY .10/ 7 SPRINKLERS ON A LINE w/ 100 GPM HOSE STREAM. THE REMOTE AREA IS PER NFPA # 13 11.2.3.4.2. THE STANDPIPE CALCULATION IS PER NFPA # 14, NFPA # 13 & THE 2009 IBC. THE REMOTE AREA IS REDUCED PER NFPA # 13 SECTION 11.2.3.2.1 & APPROPRIATE CEILING HEIGHT. (10'-0") THE STANDPIPE IS SUPPLIED AT THE FIRE DEPARTMENT CONNECTION (F.D.C.) & THE PUMPER TRUCK. A TOTAL OF 1000 GPM AT 150 PSI WILL BE PROVIDED BY THE FIRE DEPT. PUMPER TRUCK AT THE F.D.C. THE STANDPIPE SYSTEM HAS BEEN HYDRAULICALLY CALCULATED TO PROVIDE 250 GPM @ 100 PSI AT THE 2 12" HOSE CONNECTION AT THE MOST REMOTE HOSE CONNECTION, WITH AN ADDITIONAL 250 GPM ADDED @ EACHPOINT ON CONNECTION. FOR THE SECOND HOSE CONNECTION ON THE FIRST STANDPIPE AND 250 GPM AT THE TOP OF THESECOND STANDPIPE. THE DEMAND AT THE F.D.C. IS 1000 GPM @ 143.81 PSI.SITE PLANNTSWATER FLOW TEST INFORMATIONSTATIC-130 PSIRESIDUAL- 122 PSIFLOW- 1220 GPMTIME- 4:30 A.MDATE OF TEST- FEBUARY-4TH-2016FLOW TEST PERFORMED BY:NORTHAMPTON WATER DEPT.6" D.I. FIRE SERVICE6"NEW 6" GATE VALVEU01PLEASANT STREETNEW 6" WATER SERVICE TO BEFURNISHED AND INSTALLEDBY OTHERS.12"12"ELEV=0'-0"FIRST FL.4TH FLOOR CONTROL ASSEMBLY(SEE FP1 FOR DETAIL)2 12" HOSE VALVE W/ 2 12" X 1 12"REDUCER. W/ CAP AND CHAIN(TYPICAL ON ALL 4 FLOORS)14'-0"10'-8"10'-8"9'-2"LEVEL 1LEVEL 2LEVEL 3LEVEL 44'-6" 10'-6" 7'-6" 1'-0"2'-0" 7'-6" 4'-6" 4'-6"3RD FLOOR CONTROL ASSEMBLY(SEE FP1 FOR DETAIL)2ND FLOOR CONTROL ASSEMBLY(SEE FP1 FOR DETAIL)FLEXIBLE COUPLING(TYPICAL ON ALL FLOORS)4" BUTTERFLY VALVE w/ BUILT-INTAMPER SWITCH5"4" FEED FROM CORRIDOR2 12" HOSE VALVE W/ 2 12" X 1 12"REDUCER. W/ CAP AND CHAIN(TYPICAL ON ALL FLOORS)2 12" HOSE VALVE W/ 2 12" X 1 12"REDUCER. W/ CAP AND CHAIN10'-8"10'-8"14'-0"FLEXIBLE COUPLING(TYPICAL ON ALL FLOORS)5"4'-6"4'-6"4'-6"1'-0"1'-0"1'-0"4" FEED FROM CORRIDOR10'-8"10'-8"14'-0"2 12" HOSE VALVE W/ 2 12" X 1 12"REDUCER. W/ CAP AND CHAIN(TYPICAL ON ALL FLOORS)FLEXIBLE COUPLING(TYPICAL ON ALL FLOORS)4'-6"4'-6"4'-6" 9'-8" 4'-6"4" BUTTERFLY VALVE w/ BUILT-INTAMPER SWITCHHORIZONTAL SIDEWALLSPRINKLERS U.N.O.SEE NOTE # 14