ComCheck-17105 signedCOMcheck Software Version 4.1.0.0
Envelope Compliance Certificate
Project Title:
780 CMR Massachusetts State Building Code, 9th Edition, Energy Efficiency
Project Type:New Construction
Vertical Glazing / Wall Area:15%
Location:Northampton, Massachusetts
Climate Zone:5a
Construction Site:
55 Damon Rd
Northampton, MA 01060
Owner/Agent:
Emanuel Sardinha
625 East Main Street
Westfield, MA 01085
(413) 246-9676
vfcdonuts@aol.com
Designer/Contractor:
Jackie Brousseau
Aharonian & Associates, Inc. -
Architects
310 George Washington Hwy
Suite 100
Smithfield, RI 02917
401-232-5010
jbrousseau@arch-eng.com
Project Information
Energy Code:
Dunkin' Donuts
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations.
Additional Efficiency Package(s)
Building Area Floor Area
1-Dining: Cafeteria/Fast Food : Nonresidential 2550
Envelope Assemblies
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Roof 1: Insulation Entirely Above Deck, [Bldg. Use 1 - Dining:
Cafeteria/Fast Food]
2550 ---30.0 0.032 0.032
Floor 1: Slab-On-Grade:Unheated, Vertical 3 ft., [Bldg. Use 1 - Dining:
Cafeteria/Fast Food] (c)
218 ---10.0 0.510 0.540
NORTH
Exterior Wall 2: Wood-Framed, 16" o.c., [Bldg. Use 1 - Dining:
Cafeteria/Fast Food]
553 21.0 0.0 0.062 0.064
F2: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product ID
PPG Glass, SHGC 0.32, [Bldg. Use 1 - Dining: Cafeteria/Fast Food] (b)
9 ------0.370 0.380
F5: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product ID
PPG Glass, SHGC 0.32, [Bldg. Use 1 - Dining: Cafeteria/Fast Food] (b)
112 ------0.370 0.380
F3: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product ID
PPG Glass, SHGC 0.32, [Bldg. Use 1 - Dining: Cafeteria/Fast Food] (b)
40 ------0.370 0.380
Door 5: Glass (> 50% glazing):Metal Frame, Entrance Door, Perf.
Specs.: Product ID na, SHGC 0.25, [Bldg. Use 1 - Dining:
Cafeteria/Fast Food] (b)
42 ------0.690 0.770
EAST
Exterior Wall 3: Wood-Framed, 16" o.c., [Bldg. Use 1 - Dining:
Cafeteria/Fast Food]
1111 21.0 0.0 0.062 0.064
F6: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product ID
PPG Glass, SHGC 0.32, [Bldg. Use 1 - Dining: Cafeteria/Fast Food] (b)
7 ------0.370 0.380
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
241 ofPage
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
F7 (x2): Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID PPG Glass, SHGC 0.32, [Bldg. Use 1 - Dining: Cafeteria/Fast
Food] (b)
32 ------0.370 0.380
SOUTH
Exterior Wall 4: Wood-Framed, 16" o.c., [Bldg. Use 1 - Dining:
Cafeteria/Fast Food]
553 21.0 0.0 0.062 0.064
Door 4: Insulated Metal, Swinging, [Bldg. Use 1 - Dining: Cafeteria/Fast
Food]
27 ------0.500 0.370
WEST
Exterior Wall 1: Wood-Framed, 16" o.c., [Bldg. Use 1 - Dining:
Cafeteria/Fast Food]
1111 21.0 0.0 0.062 0.064
F4 (x2): Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID PPG Glass, SHGC 0.32, [Bldg. Use 1 - Dining: Cafeteria/Fast
Food] (b)
150 ------0.370 0.380
F2: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product ID
PPG Glass, SHGC 0.32, [Bldg. Use 1 - Dining: Cafeteria/Fast Food] (b)
9 ------0.370 0.380
Door 1: Glass (> 50% glazing):Metal Frame, Entrance Door, Perf.
Specs.: Product ID na, SHGC 0.25, [Bldg. Use 1 - Dining:
Cafeteria/Fast Food] (b)
91 ------0.690 0.770
(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(c) Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 780 CMR Massachusetts State Building Code, 9th Edition, Energy Efficiency requirements in COMcheck
Version 4.1.0.0 and to comply with any applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Envelope PASSES: Design 2% better than code
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
242 ofPage
Jackie Brousseau - Project Manager 7/19/18
COMcheck Software Version 4.1.0.0
Interior Lighting Compliance Certificate
Project Title:
780 CMR Massachusetts State Building Code, 9th Edition, Energy Efficiency
Project Type:New Construction
Construction Site:
55 Damon Rd
Northampton, MA 01060
Owner/Agent:
Emanuel Sardinha
625 East Main Street
Westfield, MA 01085
(413) 246-9676
vfcdonuts@aol.com
Designer/Contractor:
Jackie Brousseau
Aharonian & Associates, Inc. -
Architects
310 George Washington Hwy
Suite 100
Smithfield, RI 02917
401-232-5010
jbrousseau@arch-eng.com
Project Information
Energy Code:
Dunkin' Donuts
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations.
Additional Efficiency Package(s)
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-Common Space Types:Dining Area - Cafeteria/Fast Food 886 0.59 523
2-Common Space Types:Food Preparation 733 1.09 799
3-Common Space Types:Restrooms 121 0.88 106
4-Common Space Types:Office - Enclosed 35 1.00 35
5-Common Space Types:Storage >=50 - <=1000 sq.ft.600 0.57 342
1805Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
1-Common Space Types:Dining Area - Cafeteria/Fast Food
LED 1: LED-4: 2x2 FOH: LED Panel 33W:1 16 32 512
Track lighting 1: C: Wattage based on 6 feet of track 0 0 180 180
Incandescent 1: P4: Pendant: Incandescent 60W:1 3 60 180
2-Common Space Types:Food Preparation
LED 3: LED-7: 2x2 BOH: LED Panel 36W:1 5 32 160
LED 6: LED-1: Downlight: LED PAR 11W:1 7 11 77
LED 7: LED-6: 2x4 BOH: LED Other Fixture Unit 50W:1 4 49 196
3-Common Space Types:Restrooms
LED 1: LED-4: 2x2 FOH: LED Panel 33W:1 2 32 64
4-Common Space Types:Office - Enclosed
LED 3: LED-7: 2x2 BOH: LED Panel 36W:1 1 32 32
5-Common Space Types:Storage >=50 - <=1000 sq.ft.
LED 3: LED-7: 2x2 BOH: LED Panel 36W:1 2 32 64
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
243 ofPage
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
LED 7: LED-6: 2x4 BOH: LED Other Fixture Unit 50W:1 5 49 245
LED 9: Walk-in: Other:1 3 30 90
1800Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 780 CMR Massachusetts State Building Code, 9th Edition, Energy Efficiency requirements in COMcheck
Version 4.1.0.0 and to comply with any applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES: Design 0.3% better than code
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
244 ofPage
Jackie Brousseau - Project Manager 7/19/18
COMcheck Software Version 4.1.0.0
Exterior Lighting Compliance Certificate
Project Title:
780 CMR Massachusetts State Building Code, 9th Edition, Energy Efficiency
Project Type:New Construction
Construction Site:
55 Damon Rd
Northampton, MA 01060
Owner/Agent:
Emanuel Sardinha
625 East Main Street
Westfield, MA 01085
(413) 246-9676
vfcdonuts@aol.com
Designer/Contractor:
Jackie Brousseau
Aharonian & Associates, Inc. -
Architects
310 George Washington Hwy
Suite 100
Smithfield, RI 02917
401-232-5010
jbrousseau@arch-eng.com
Project Information
Energy Code:
Dunkin' Donuts
4 (High activity metropolitan commercial district)Exterior Lighting Zone
Allowed Exterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable
Wattage
E
Allowed Watts
(B X C)
Other door (not main entry)4 ft of door 20 Yes 80
Drive-up windows/doors 1 windows 400 No 400
Main entry 3 ft of door 30 Yes 90
Main entry 3 ft of door 30 Yes 90
Illuminated area of facade wall or surface 3649 ft2 0.2 No 730
Parking area 80459 ft2 0.13 Yes 10460
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
10720
11850
1300
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 1300 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Other door (not main entry) (4 ft of door width): Tradable Wattage
LED 4: G: Wall Pack: LED Linear 10W:1 1 10 10
Drive-up windows/doors (1 windows or doors): Non-tradable Wattage
LED 2: LED-2: Canopy Lights: LED PAR 20W:1 3 20 60
Main entry (3 ft of door width): Tradable Wattage
LED 2: LED-2: Canopy Lights: LED PAR 20W:1 2 20 40
LED 2: LED-2: Canopy Lights: LED PAR 20W:1 2 20 40
Illuminated area of facade wall or surface (3649 ft2): Non-tradable Wattage
LED 5: WSCX-2: Signlite: LED Other Fixture Unit 50W:1 11 50 550
LED 6: WSC-2: Wall Sconce: LED Other Fixture Unit 25W:1 15 25 375
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
245 ofPage
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Parking area (80459 ft2): Tradable Wattage
LED 7: VIF: See Site Plan: LED Roadway-Parking Unit 54W:1 11 55 605
LED 8: VIF: See Site Plan: LED Roadway-Parking Unit 54W:1 5 55 275
970Total Tradable Proposed Watts =
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 780 CMR Massachusetts State Building Code, 9th Edition, Energy Efficiency requirements in COMcheck
Version 4.1.0.0 and to comply with any applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Exterior Lighting PASSES: Design 92% better than code
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
246 ofPage
Jackie Brousseau - Project Manager 7/19/18
COMcheck Software Version 4.1.0.0
Mechanical Compliance Certificate
Project Title:
780 CMR Massachusetts State Building Code, 9th Edition, Energy Efficiency
Project Type:New Construction
Location:Northampton, Massachusetts
Climate Zone:5a
Construction Site:
55 Damon Rd
Northampton, MA 01060
Owner/Agent:
Emanuel Sardinha
625 East Main Street
Westfield, MA 01085
(413) 246-9676
vfcdonuts@aol.com
Designer/Contractor:
Jackie Brousseau
Aharonian & Associates, Inc. -
Architects
310 George Washington Hwy
Suite 100
Smithfield, RI 02917
401-232-5010
jbrousseau@arch-eng.com
Project Information
Energy Code:
Dunkin' Donuts
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations.
Additional Efficiency Package(s)
Mechanical Systems List
Quantity System Type & Description
Heating: 1 each - Central Furnace, Gas, Capacity = 73 kBtu/h
Proposed Efficiency = 82.00% Et, Required Efficiency: 80.00 % Et or 78% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 73 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 12.00 EER, Required Efficiency: 11.00 EER + 12.6 IEER
Fan System: FAN SYSTEM 1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 2400 CFM, 1.7 motor nameplate hp, 0.0 fan efficiency grade
1 HVAC System 1 (6) (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 73 kBtu/h
Proposed Efficiency = 82.00% Et, Required Efficiency: 80.00 % Et or 78% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 73 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 12.00 EER, Required Efficiency: 11.00 EER + 12.6 IEER
Fan System: FAN SYSTEM 1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 2400 CFM, 1.7 motor nameplate hp, 0.0 fan efficiency grade
1 HVAC System 2 (6) (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 98 kBtu/h
Proposed Efficiency = 82.00% Et, Required Efficiency: 80.00 % Et or 78% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 89 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 12.00 EER, Required Efficiency: 11.00 EER + 12.6 IEER
Fan System: FAN SYSTEM 2 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 2 Supply, Constant Volume, 3000 CFM, 2.4 motor nameplate hp, 0.0 fan efficiency grade
1 HVAC System 3 (7.5) (Single Zone):
Gas Instantaneous Water Heater, Capacity: 9 gallons, Input Rating: 75 kBtu/h
Proposed Efficiency: 0.67 EF, Required Efficiency: 0.60 EF
1 Water Heater 1:
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
247 ofPage
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 780 CMR Massachusetts State Building Code, 9th Edition, Energy Efficiency requirements in COMcheck
Version 4.1.0.0 and to comply with any applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
248 ofPage
Jackie Brousseau - Project Manager 7/19/18
Inspection Checklist
Requirements: 100.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.0.0
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 780 CMR Massachusetts State Building Code, 9th Edition,
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR1]1
Plans and/or specifications provide all
information with which compliance
can be determined for the building
envelope and document where
exceptions to the standard are
claimed. Completed COMcheck
Envelope certificate and Plan Review
Checklist will be submitted with
application.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C103.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks. Completed COMcheck
Mechanical certificate and Plan
Review Checklist will be submitted
with application.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C103.2
[PR3]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the service water
heating systems and equipment and
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide. Completed COMcheck
Mechanical certificate and Plan
Review Checklist will be submitted
with application.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C103.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices. Completed COMcheck
Inteiror Lighting certificate and Plan
Review Checklist will be submitted
with application.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
249 ofPage
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR8]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the exterior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices. Completed COMcheck
Exteiror Lighting certificate and Plan
Review Checklist will be submitted
with application.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C402.4.1
[PR10]1
The vertical fenestration area <= 30
percent of the gross above-grade wall
area.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C402.4.1
[PR11]1
The skylight area <= 3 percent of the
gross roof area.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: N/A
C402.4.2
[PR14]1
In enclosed spaces > 2,500 ft2
directly under a roof with ceiling
heights >15 ft. and used as an office,
lobby, atrium, concourse, corridor,
storage, gymnasium/exercise center,
convention center, automotive
service, manufacturing, non-
refrigerated warehouse, retail store,
distribution/sorting area,
transportation, or workshop, the
following requirements apply: (a) the
daylight zone under skylights is >=
half the floor area; (b) the skylight
area to daylight zone is >= 3 percent
with a skylight VT >= 0.40; or a
minimum skylight effective aperture
>= 1 percent.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M1.1 for requirements / Design-
Build
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2410 ofPage
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C402.3
[PR17]3
Rooftop Solar Readiness: 1)
Construction documents indicate the
solar ready zone where applicable, 2)
the total solar-ready zone area
consists of an area >= 1,600 square
feet, or 50% of the roof area that is
either flat or oriented between 110
degrees and 270 degrees of true
north, exclusive of mandatory access
or set back areas as required by 527
CMR: Board of Fire Prevention
Regulations, 3) Solar-ready zones
consist of an area free from
obstructions, 4) the structural design
loads for roof dead load and roof live
load are indicated on the construction
documents, 5) documents indicate
pathways for routing of conduit or
plumbing from the solar-ready zone to
the electrical service panel or service
hot water system, 6) main electrical
service panel has a reserved space to
allow installation of a dual pole circuit
breaker for future solar electric
installation and is labelled “For Future
Solar Electric.”
Complies
Does Not
Not Observable
Not Applicable
Exception: Assembly Group A-2 and A-3, and High Hazard
Group H buildings.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2411 ofPage
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C303.2
[FO4]2
Slab edge insulation installed per
manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C303.2.1
[FO6]1
Exterior insulation protected against
damage, sunlight, moisture, wind,
landscaping and equipment
maintenance activities.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C402.2.5
[FO3]2
Slab edge insulation R-value.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.6
[FO12]3
Radiant heating systems panels
insulated to >=R-3.5 on face opposite
space being heated.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Envelope Assemblies table for values.
C403.2.4.
5,
C403.2.4.
6
[FO9]3
Snow/ice melting system sensors for
future connection to controls. Freeze
protection systems have automatic
controls installed.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2412 ofPage
Section
#
& Req.ID
Framing / Rough-In Inspection Complies?Comments/Assumptions
C303.1.3
[FR12]2
Fenestration products rated in
accordance with NFRC.
Complies
Does Not
Not Observable
Not Applicable
Exception: Default values are used.
C303.1.3
[FR13]1
Fenestration products are certified as
to performance labels or certificates
provided.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C402.4.3
[FR10]1
Vertical fenestration SHGC value.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.4.3,
C402.4.3.
4
[FR8]1
Vertical fenestration U-Factor.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.4.4
[FR14]2
U-factor of opaque doors associated
with the building thermal envelope
meets requirements.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.5.1.
2.1
[FR19]1
The building envelope contains a
continuous air barrier that is sealed in
an approved manner and material
permeability <= 0.004 dfm/ft2. Air
barrier penetrations are sealed in an
approved manner.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C402.5.2,
C402.5.4
[FR18]3
Factory-built fenestration and doors
are labeled as meeting air leakage
requirements.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C402.5.7
[FR17]3
Vestibules are installed on all building
entrances. Doors have self-closing
devices.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2413 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2414 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2415 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C402.2.6
[ME41]3
Thermally ineffective panel surfaces of
sensible heating panels have
insulation >= R-3.5.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C402.5.5,
C403.2.4.
3
[ME3]3
Stair and elevator shaft vents have
motorized dampers that automatically
close.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C402.5.5,
C403.2.4.
3
[ME58]3
Outdoor air and exhaust systems have
motorized dampers that automatically
shut when not in use and meet
maximum leakage rates. Check
gravity dampers where allowed.
Complies
Does Not
Not Observable
Not Applicable
Exception: Gravity dampers acceptable in buildings 3 stories.
C403.2.13
[ME71]2
Unenclosed spaces that are heated
use only radiant heat.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.3
[ME55]2
HVAC equipment efficiency verified.Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.2.4.
7
[ME113]2
Fault detection and diagnostics
installed with air-cooled unitary DX
units having economizers.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
7
[ME113]2
Fault detection and diagnostics
installed with air-cooled unitary DX
units having economizers.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
7
[ME113]2
Fault detection and diagnostics
installed with air-cooled unitary DX
units having economizers.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.6.
1
[ME59]1
Demand control ventilation provided
for spaces >500 ft2 and >25
people/1000 ft2 occupant density and
served by systems with air side
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.6.
2
[ME115]3
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 50% or less of design capacity.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.7
[ME57]1
Exhaust air energy recovery on
systems meeting Table C403.2.7(1)
and C403.2.7(2).
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.8
[ME116]3
Kitchen exhaust systems comply with
replacement air and conditioned
supply air limitations, and satisfy hood
rating requirements and maximum
exhaust rate criteria.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2416 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.2.9
[ME60]2
HVAC ducts and plenums insulated.
Where ducts or plenums are installed
in or under a slab, verification may
need to occur during Foundation
Inspection.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9
[ME10]2
Ducts and plenums sealed based on
static pressure and location.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.3
[ME62]1
Air economizers provided where
required, meet the requirements for
design capacity, control signal,
ventilation controls, high-limit shut-off,
integrated economizer control, and
provide a means to relieve excess
outside air during operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.3
[ME62]1
Air economizers provided where
required, meet the requirements for
design capacity, control signal,
ventilation controls, high-limit shut-off,
integrated economizer control, and
provide a means to relieve excess
outside air during operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.3
[ME62]1
Air economizers provided where
required, meet the requirements for
design capacity, control signal,
ventilation controls, high-limit shut-off,
integrated economizer control, and
provide a means to relieve excess
outside air during operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2417 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C408.2.2.
1
[ME53]3
Air outlets and zone terminal devices
have means for air balancing.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2418 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.1
[EL15]1
Lighting controls installed to uniformly
reduce the lighting load by at least
50%.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.1
[EL18]1
Occupancy sensors installed in
required spaces.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.1,
C405.2.2.
3
[EL23]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.2.
1
[EL22]2
Automatic controls to shut off all
building lighting installed in all
buildings.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.3
[EL16]2
Daylight zones provided with
individual controls that control the
lights independent of general area
lighting.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.2.3,
C405.2.3.
1,
C405.2.3.
2
[EL20]1
Primary sidelighted areas are
equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.2.3,
C405.2.3.
1,
C405.2.3.
3
[EL21]1
Enclosed spaces with daylight area
under skylights and rooftop monitors
are equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.2.4
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.5
[EL25]null
Automatic lighting controls for exterior
lighting installed. Controls will be
daylight controlled, set based on
business operation time-of-day, or
reduce connected lighting > 30%.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2419 ofPage
Section
#
& Req.ID
Insulation Inspection Complies?Comments/Assumptions
C303.1
[IN3]1
Roof insulation installed per
manufacturer’s instructions. Blown or
poured loose-fill insulation is installed
only where the roof slope is <=3 in
12.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C303.1
[IN10]2
Building envelope insulation is labeled
with R-value or insulation certificate
providing R-value and other relevant
data.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C303.2
[IN7]1
Above-grade wall insulation installed
per manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C303.2.1
[IN14]2
Exterior insulation is protected from
damage with a protective material.
Verification for exposed foundation
insulation may need to occur during
Foundation Inspection.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C402.2.1
[IN17]3
Insulation intended to meet the roof
insulation requirements cannot be
installed on top of a suspended
ceiling. Mark this requirement
compliant if insulation is installed
accordingly.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C402.2.3
[IN6]1
Above-grade wall insulation R-value.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.5
[IN8]2
Floor insulation R-value.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.6
[IN18]3
Radiant panels and associated
components, designed for heat
transfer from the panel surfaces to the
occupants or indoor space are
insulated with a minimum of R-3.5.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C402.2.2
[IN2]1
Roof R-value. For some ceiling
systems, verification may need to
occur during Framing Inspection.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.5.1.
1
[IN1]1
All sources of air leakage in the
building thermal envelope are sealed,
caulked, gasketed, weather stripped
or wrapped with moisture vapor-
permeable wrapping material to
minimize air leakage.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2420 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C303.3,
C408.2.5.
3
[FI8]3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C402.5.3
[FI51]3
Where open combustion air ducts
provide combustion air to open
combustion fuel burning appliances,
the appliances and combustion air
opening are located outside the
building thermal envelope or enclosed
in a room, isolated from inside the
thermal envelope. Such rooms are
sealed and insulated.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement is not applicable.
C402.5.6
[FI37]1
Weatherseals installed on all loading
dock cargo doors.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C402.5.8
[FI26]3
Recessed luminaires in thermal
envelope to limit infiltration and be IC
rated and labeled. Seal between
interior finish and luminaire housing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.2
[FI27]3
HVAC systems and equipment
capacity does not exceed calculated
loads.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1.2
[FI38]3
Thermostatic controls have a 5 °F
deadband.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1.3
[FI20]3
Temperature controls have setpoint
overlap restrictions.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2421 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
2
[FI39]3
Each zone equipped with setback
controls using automatic time clock or
programmable control system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
2.1,
C403.2.4.
2.2
[FI40]3
Automatic Controls: Setback to 55°F
(heat) and 85°F (cool); 7-day clock, 2-
hour occupant override, 10-hour
backup
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.3
[FI11]3
Heat traps installed on supply and
discharge piping of non-circulating
systems.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.4
[FI25]2
All piping insulated in accordance with
section details and Table C403.2.10.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.4.1
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
C405.5.1
[FI19]1
Exterior lighting power is consistent
with what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
Complies
Does Not
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values.
C408.2.1
[FI28]1
Commissioning plan developed by
registered design professional or
approved agency.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.3.
1
[FI31]1
HVAC equipment has been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.3.
2
[FI10]1
HVAC control systems have been
tested to ensure proper operation,
calibration and adjustment of controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2422 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C408.2.3.
3
[FI32]1
Economizers have been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.4
[FI29]1
Preliminary commissioning report
completed and certified by registered
design professional or approved
agency.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
1
[FI7]3
Furnished HVAC as-built drawings
submitted within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
1
[FI16]3
Furnished as-built drawings for
electric power systems within 90 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
3
[FI43]1
An air and/or hydronic system
balancing report is provided for HVAC
systems.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
4
[FI30]1
Final commissioning report due to
building owner within 90 days of
receipt of certificate of occupancy.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.3
[FI33]1
Lighting systems have been tested to
ensure proper calibration, adjustment,
programming, and operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2423 ofPage
Project Title:
Data filename:
Dunkin' Donuts
S:\Arch Drawings\DUNKIN' DONUTS\17105 DD Northampton MA\01 Code
Research\ComCheck\ComCheck-17105 LIGHTING.cck
07/19/18Report date:
2424 ofPage