31B-311 Fire Protection Performance Spec 02-02-09PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 1 of 17
SECTION 15300 - FIRE PROTECTION
PART 1 - GENERAL
1.01 RELATED DOCUMENTS
A. Include General Conditions, Supplementary General Conditions, applicable parts of
Division 1, and conditions of the Contract as part of this Section.
B. Examine all other Sections of the Specifications for requirements, which affect work
under this, Section whether or not, such work is specifically mentioned in this
Section.
C. Co-ordinate work with that of all other trades affecting, or affected by the work of
this Section. Co-operate with such trades to assure steady progress of all work under
the Contract.
1.02 SCOPE OF WORK
A. Furnish all labor, materials, appurtenances and services necessary for, and
reasonably incidental to, the complete design and installation of all fire protection
work specified herein including, but not limited to, the following:
1. Fire protection renovation to the existing wet pipe and dry pipe located in the
ground floor, first floor, and second floor and attic to accommodate new
room layouts. Provide a fully sprinkled building.
2. The Fire Protection Subcontractor shall furnish all labor and materials
required for his own hoisting, rigging, and scaffolding during the entire
course of the project.
3. Disconnect and remove all existing sprinkler heads and piping made obsolete
by or interfering with new construction.
4. Submit plans and calculations to the City’s Insurance Underwriter for review
and approval.
5. Provide design drawings stamped by a registered professional engineer in the
State of Massachusetts.
B. Related work, to be performed under other sections of his Specification shall include
the following:
1. Wiring of flow switches, tamper switches, electric bell and control panel
back to the fire alarm panel shall be by the Electrical Subcontractor,
coordinated and as directed by the Fire Protection Subcontractor.
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 2 of 17
2. Cutting and patching.
1.03 SYSTEM DESIGN
A. The Fire Protection Subcontractor shall perform a water flow test, and with this
information, shall calculate pipe sizes and sprinkler head configuration and orifice
sizes in accordance with NFPA 13.
B. Sprinkler head and pipe run locations shall be determined by the Fire Protection
Engineer. The Fire Protection Subcontractor shall produce a design based on actual
available water pressure and submit it to the Architect for approval before beginning
fabrication and installation.
C. Design Criteria: Location of piping and heads shall be coordinated with all other
trades. Actual pipe sizing, types of heads, and layout shall be based on a
hydraulically designed system in accordance with the requirements of NFPA 13, the
Northampton Fire Department, and the Insurance Underwriter (I.R.I.). Location of
sprinkler heads, in relation to the ceiling light hazard occupancy. The Fire Protection
Subcontractor shall prepare working drawings and hydraulic calculations per NFPA
13 and shall obtain Northampton Fire Department and the Colleges Insurance Under-
writer approval prior to start of work. The Fire Protection Subcontractor shall
perform water flow tests or obtain water flow data in writing from local authority.
Co-ordinate work of this Section with all trades to avoid interference with ductwork,
HVAC and plumbing, piping, electrical work, structure, etc. Final sprinkler head
locations shall be subject to Architect's approval.
The number of heads and pipe sizes may be increased or reduced due to hydraulic
calculations or the installation of revised heads, provided the revised heads are UL
listed and F.M. approved and meet NFPA 13, Northampton Fire Department, and
(IRI) Insurance Underwriter's criteria. Additionally, all heads shall be in accordance
with NFPA 13 recommendations.
1.04 QUALITY ASSURANCE
A. Manufacturers: Firms regularly engaged in manufacture of fire protection piping
systems products, of types, materials, and sizes required, whose products have been
in satisfactory use in similar service for not less than five (5) years.
B. NFPA Code: Comply with ANSI/NFPA 13, "Installation of Sprinkler System".
C. FM Compliance: Comply with Factory Mutual "Approval Guide".
D. FM Labels: Provide sprinkler products bearing FM approval labels.
E. UL Labels: Provide fire sprinkler piping products, which have been approved and
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 3 of 17
labeled by Underwriters Laboratories.
F. Local Fire Department/Marshall Regulations: Comply with governing regulations
pertaining to fire sprinkler piping. Review proposed system with said officials prior
to commencing work.
G. Final installation of system is subject to approval by Owner's insurer's rating
organization and local Fire Department.
H. Equality of materials or articles other than those named or described in this Section
will be determined in accordance with the provisions of the General Requirements,
except that substitutions will only be considered for items where the words, "or
equal" appear in the product specification.
1.05 CODES, ORDINANCES AND INSPECTIONS
A. All materials and the installation thereof shall conform to the requirements of the
Massachusetts State Building Code, Electrical Code, Fuel Gas and Plumbing Code
and local laws, rules, regulations, and codes pertaining thereto. Where provisions of
the Contract Documents conflict with any codes, rules or regulations, the latter shall
govern.
B. The Fire Protection Subcontractor shall comply with the Local Code Enforcement
Officials' instructions at no additional cost to the Owner. Review proposed system
with said officials prior to commencing work.
1.06 INSTALLATION REQUIREMENTS
A. The Fire Protection Subcontractor shall employ only competent and experienced
workmen at a regular schedule in harmony with the other tradesmen on the job. He
shall also exercise care and supervision of his employees in regard to proper and
expeditious laying out of his work.
B. The Fire Protection Subcontractor shall be held responsible for any injuries or
damage done to the building premises or adjoining property or to other Subcontrac-
tors' work resulting from the execution of his part of the work in any manner
whatsoever; and in case of dispute arising as to the extent or share of responsibility
incurred by the Fire Protection Subcontractor, it is agreed between the Owner and the
Fire Protection Subcontractor that such liability and extent of damage shall be finally
determined by the Architect whose decision shall be final and binding on both parties
to the Contract for the work in question.
C. The Fire Protection Subcontractor shall co-operate to the fullest extent with all other
trades in order to expedite the progress of the work. He shall furnish all information
pertaining to his materials as to sizes, locations, and means of support, to all other
trades requiring such information. The Fire Protection Subcontractor shall also
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 4 of 17
furnish all sleeves, frames, beams, supports, inserts, etc., hereinafter specified so that
the General Contractor may build them in place. In case of failure on the part of the
Fire Protection Subcontractor to give proper information, as above, he will be
required to bear the extra expense involved due to such failure.
D. The arrangement of all piping, ductwork, conduit, wire and cable indicated on the
drawings is diagrammatic only, and indicates the minimum requirements of this
work. Conditions at the building shall determine the actual arrangement of runs,
bends, offsets, etc.
E. The Fire Protection Subcontractor shall lay out all his work and be responsible for
the accuracy thereof. Conditions at the building shall be the determining factor for
all measurements. In no case shall piping be installed laterally in thickness of slab or
deck.
F. All work shall be laid out and installed so as to require the least amount of cutting
and patching. Drilling of all holes required for the installation of pipes, conduit, and
cable runs shall be performed by the Subcontractor installing such items. All piping
shall be installed concealed in finished spaces.
G. The Fire Protection Subcontractor shall be responsible for the proper protection of
his work and materials from injury or loss at the hands of others and shall make good
such loss or injury at his own expense. All pipes left open during the progress of the
work shall be capped or plugged at all times. All instruments and operating
apparatus shall be protected by suitable means.
H. The Fire Protection Subcontractor shall be responsible for all equipment and
materials installed under this Section until the final acceptance of the project by the
Owner.
I. The Fire Protection Subcontractor shall check all of the Architectural Plans and
Specifications and shall field verify all existing conditions before ordering any
materials and the installation of work. Any discrepancies shall be called to the
attention of the Architect before proceeding with the work.
1.07 PRODUCTS
A. With the exception of items specifically noted otherwise, all materials used shall be
U.S. made, new, full weight, and first class in every respect, without defects, and
designed to function properly in that portion of the work for which they are intended,
and with the same brand of manufacturers for each class of material or equipment.
Electrical materials and equipment of types for which there are Underwriters
Laboratories standard requirements, listings, or labels shall conform to their
requirements and be so labeled.
1.08 SUBMITTALS
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 5 of 17
A. Before ordering materials shipped to the job, the Fire Protection Subcontractor shall
submit to the Architect eight (8) sets of catalogue cuts or manufacturers' data sheets,
giving all details, dimensions, capacities, etc. of all materials to be furnished.
B. Submit hydraulic calculations and scaled layout drawings for fire protection pipe and
fittings including, but not necessarily limited to, pipe and tube sizes, locations,
elevations and slopes of horizontal runs, wall and floor penetrations, and
connections. Show interface and spatial relationship between piping and proximate
equipment.
1. Shop Drawings are subject to review and will require approval by Owner's
insurer's rating organization and the Northampton Fire Department prior to
submitting to the Architect for approval.
2. It is expected that the contractor shall provide the Architectural design team
with a set of contract drawings stamped by a professional engineer registered
within the Commonwealth of Massachusetts for permit and construction. For
estimating purposes, the contractor shall use the guidelines described herein
for sizing and selecting the system components.
1.09 PERMITS, FEES AND INSPECTIONS
A. The Fire Protection Subcontractor shall secure all permits and pay all fees required
for his work. He shall be required to secure all other permits and pay all other fees
and charges incidental to the proper carrying out of the Contract. He is to assume all
responsibility regarding the observance of the rules and regulations so far as they
relate to his part of the work.
B. The Fire Protection Subcontractor shall arrange and pay for all required inspections
of his work.
1.10 PRODUCT HANDLING
A. The Fire Protection Subcontractor shall provide for the delivery of all his materials
and equipment to the building site when required, so as to carry on his work
efficiently and to avoid delaying his work and that of other trades.
1.11 ENVIRONMENTAL CONDITIONS
A. All necessary tools machinery, scaffolding, and transportation for completion of his
Contract shall be provided by the Fire Protection Subcontractor.
B. The Fire Protection Subcontractor shall provide his own portable extension lines and
obtain 120 volt, 60 cycle, single phase electric energy from the General Contractor to
drive his machines and light his work. He shall provide his own light bulbs, plugs,
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 6 of 17
sockets, etc.
C. All broken or waste material, rags, packing, etc., resulting from his work shall be
removed by the individual Subcontractor.
1.12 WORK CONCEALED
A. All piping shall be installed exposed except where piping is to be installed above
new acoustic ceilings. Where ceilings are installed sprinklers shall be installed above
and below the ceiling.
B. Piping containing water shall not be installed concealed in walls having an exterior
exposure above grade.
1.13 OPERATING AND MAINTENANCE MANUALS
A. After all final tests and adjustments have been completed, fully instruct the proper
Owner's representative in all details of operation of equipment installed. Supply
qualified personnel to operate equipment for sufficient length of time to assure that
Owner's representative is properly qualified to take over operation and maintenance
procedures.
B. Furnish the Architect, for his approval, three (3) copies of an Operation and
Maintenance Manual. Inscribe the following identification on the cover: the words,
"Operation and Maintenance Manual", the name and location of the equipment or the
building, the name of the Subcontractor, and the Contract number. The manual shall
have a Table of Contents with tab sheets placed before each section. The instructions
shall be legible and easily read, with large sheets of drawings folded in. The manuals
shall be bound in hard binders or an approved equivalent.
C. The Manual shall include the following information:
1. Description of systems.
2. Description of start-up, operation, and shutdown.
3. Schedule of adjustment, care, and routine maintenance for each item of
equipment.
4. Lubrication chart.
5. Wiring and control diagrams with data to explain detailed operation and
control of each item of equipment.
6. Valve chart.
7. List of recommended spare parts.
8. Copies of all service contracts.
9. Performance curves for pumps, etc.
10. Lists of all names, addresses, and phone numbers of all Subcontractors as
well as the local representative for each item of equipment.
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 7 of 17
1.14 GUARANTEE
A. The Fire Protection Subcontractor shall guarantee the satisfactory operation of his
work in all parts for a period of one (1) year after the date of final acceptance, and
shall agree to promptly repair or replace any items of his work which are found to be
defective during this period.
B. The Fire Protection Subcontractor shall pay for repair of damage to the building
caused by defects in his work and for repair to plaster, wood, and other materials or
equipment caused by replacement or repairs to the entire satisfaction of the Architect.
C. Any part of the work installed under this Contract requiring excessive maintenance
shall be considered as being defective.
1.15 RECORD DRAWINGS
A. Refer to Division 1 for Record Drawings.
B. Record Drawings shall reflect all changes from the Contract Drawings whether by
change order or by field conditions. Principal dimensions shall be indicated of
concealed work, fire protection lines, valves, and zone flow switches. All changes
must be clearly marked with a bubble drawn around the area of work effected by the
change.
PART 2 - MATERIALS
2.01 FIRE PROTECTION PIPING MATERIALS AND PRODUCTS
A. Provide piping materials and factory-fabricated piping products of sizes, types,
pressure ratings, temperature ratings, and capacities as indicated. Where not indicat-
ed, provide proper selection as determined by Installer to comply with installation
requirements. Provide sizes and types matching piping and equipment connections;
provide fittings of materials, which match pipe materials used in fire protection
piping systems. Where more than one type of material or product is indicated,
selection is Installer's option.
B. Basic Identification
1. Subject to compliance with requirements, provide mechanical identification
materials of one of the following:
Allen Systems, Inc.
Brady (W. H.) Co.; Signmark Div.
Industrial Safety Supply Co., Inc.
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 8 of 17
Seton Name Plate Corp.
2. Provide manufacturer's standard pre-printed, semi-rigid, snap-on, color-
coded pipe markers, complying with ANSI A13.1.
a. For external diameters less than 6", provide full-band pipe markers,
extending 360o around pipe at each location, fastened as follows:
Snap-on application of pre-tensioned, semi-rigid plastic pipe marker.
b. Lettering: Manufacturer's standard pre-printed no-menclature, which
best describes piping system in each instance, as selected by Ar-
chitect.
c. Locate pipe markers as follows:
(1) Near each valve and control device.
(2) Spaced intermediately at maximum spacing of 50' along each
piping run, except reduce spacing to 25' in congested areas of
piping and equipment.
(3) Branch piping need not be marked.
3. Provide manufacturer's standard solid brass valve tags with printed enamel
lettering, with piping system abbreviation in approximately 3/16" high letters
and sequenced valve numbers approximately 3/8" high, and with 5/32" hole
for fastener. Provide tags on all valves and control devices.
a. Provide 1-1/8" sq. brass tags with black lettering.
b. Provide manufacturer's standard solid brass chain (wire link or
beaded type), or solid brass S-hooks of the sizes required for proper
attachment of tags to valves, and manufactured specifically for that
purpose.
c. Submit valve schedule for piping system, typewritten and reproduced
on 8-1/2" x 11" bond paper. Tabulate valve number, piping system,
system abbreviation (as shown on tag), location of valve (room or
space), and variations for identification (if any). Mark valves, which
are intended for emergency shut-off and similar special uses, by
special "flags", in margin of schedule. In addition to mounted copies,
furnish extra copies for Maintenance Manuals as specified in
Division 1.
d. For each page of valve schedule, provide glazed display frame, with
screws for removable mounting on masonry walls. Provide frames of
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 9 of 17
finished hardwood or extruded aluminum, with SSB-grade sheet
glass.
e. Mount valve schedule frames and schedules in rooms where
indicated or, if not otherwise indicated, where directed by Architect.
f. Furnish complete chart and flow diagram of entire system listing the
valve number, fluid controlled, and zone reference location for all
valves corresponding to the tag numbers. The chart shall be framed
under glass and hung in the Fire Protection Equipment Room where
directed. Furnish two (2) extra copies of the chart to the Architect.
g. Furnish and install a laminated red phenolic plate with engraved
white lettering for each zone control flow switch and isolation valve.
Nameplates shall be located adjacent to all exposed and concealed
valves, approximately 12" below finished ceiling.
2.02 PIPE, TUBE, AND FITTINGS
A. Interior Piping
1. Black Steel Pipe: ASTM A 53, A 106 or A 120: except comply with ASTM
A 53 or A 106 where close coiling or bending is required.
2. Galvanized black steel pipe: ASTM A53.
a. Pipe Weight: Schedule 40.
b. Fittings: Class 125, cast-iron threaded, ANSI B16.4, or flanged,
ANSI B16.1.
c. Fittings: Mechanical grooved pipe couplings and fittings; cut-groove
type for piping 2-1/2" and larger only.
(1) Electric-Resistance-Welded Steel Pipe: ASTM A 135.
(2) Pipe Weight: Schedule 10 for 5" and smaller; 0.134" wall
thickness for 6".
(3) Fittings: Mechanical grooved pipe couplings and fittings;
roll-groove or mechanical locking type.
d. Grooved Piping Products (for use on pipes 2-1/2" and larger)
(1) Coupling Housings: Malleable iron conforming to ASTM A
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 10 of 17
47.
(2) Coupling Housing: Ductile iron conforming to ASTM A 536.
(3) Coupling Housings Description: Grooved mechanical type,
which engages grooved or shouldered pipe ends, encasing an
elastomeric gasket which bridges pipe ends to create seal.
Cast in two or more parts, secure together during assembly
with nuts and bolts. Permit degree of contraction and
expansion as specified in manufacturer's latest published liter-
ature.
(4) Gaskets: Mechanical grooved coupling design, pressure
responsive so that internal pressure serves to increase seal's
tightness, constructed of elastomers having properties as
designated by ASTM D 2000.
(5) Bolts and Nuts: Heat-treated carbon steel, ASTM A 183,
minimum tensile 110,000-psi.
(6) Branch Stub-Ins: Upper housing with full locating collar for
rigid positioning engaging machine-cut hole in pipe, encasing
elastomeric gasket conforming to pipe outside diameter
around hole, and lower housing with positioning lugs,
secured together during assembly with nuts and bolts.
(7) Fittings: Grooved or shouldered end design to accept
grooved mechanical couplings.
Malleable Iron: ASTM A 47.
Ductile Iron: ASTM A 536.
(8) Flanges: Conform to Class 125 cast iron and Class 150 steel
bolt hole alignment.
Malleable Iron: ASTM 47.
Ductile Iron: ASTM A 536.
(9) Grooves: Conform to the following:
Standard Steel: Square cut.
Lightweight Steel: Roll grooved.
(10) Manufacturer: Subject to compliance with requirements,
provide grooved piping products of the following:
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 11 of 17
ITT Grinnell Corp.
Victaulic Co.
B. Piping above ground and within the building shall conform to all requirements of
NFPA 13 and shall be as follows:
1. Exposed sprinkler piping, subject to vandalism (stair halls and similar areas),
shall be Schedule 40 galvanized steel pipe, welded, suitable for 175 psi.
working water pressure.
2. All concealed piping and all exposed sprinkler piping in Mechanical
Equipment Rooms 1-1/2" and smaller, shall be at the option of the Fire
Protection Subcontractor, either Schedule 40 galvanized steel pipe with
screwed fittings or standard weight roll grooved pipe with grooved fittings.
3. All exposed sprinkler piping, 1-1/2" and smaller, shall be Schedule 40
galvanized steel pipe with screwed fittings.
4. Schedule 40 seamless red brass pipe with brass screwed fittings suitable for
175 psi. working water pressure.
5. Type "L" seamless drawn hard copper tubing with solder-joint pressure
fittings, where noted on the drawings.
C. Install pipes and pipe fittings in accordance with recognized industry practices which
will achieve permanently leak proof piping systems, capable of performing each
indicated service without piping failure. Install each run with minimum joints and
couplings, but with adequate and accessible unions for disassembly and
maintenance/replacement of valves and equipment. Reduce sizes (where indicated)
by use of reducing fittings. Align piping accurately at connections, within 1/16" mis-
alignment tolerance. Comply with ANSI B31 Code for Pressure Piping.
D. Locate piping runs, except as otherwise indicated, vertically and horizontally
(pitched to drain) and avoid diagonal runs wherever possible. Orient horizontal runs
parallel with walls and column lines. Locate runs as shown or described by dia-
grams, details and notations or, if not otherwise indicated, run piping in shortest route
which does not obstruct usable space or block access for servicing building and its
equipment.
Hold piping close to walls, overhead construction, columns and other structural and
permanent-enclosure elements of building. Wherever possible in finished and
occupied spaces, conceal piping from view, by locating in column enclosures, in
hollow wall construction or above suspended ceilings; do not encase horizontal runs
in solid partitions, except as indicated.
E. Electrical Equipment Spaces: Do not run piping through transformer vaults, Elevator
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 12 of 17
Machine Room, and other electrical or electronic equipment spaces and enclosures
unless unavoidable. Install drip pan under piping that must be run through electrical
spaces. Any piping intended to be run through electrical spaces shall be reviewed by
the Architect prior to installation.
F. Thread pipe in accordance with ANSI B2.1; cut threads full and clean using sharp
dies. Ream threaded ends to remove burrs and restore full inside diameter. Apply
pipe joint compounder pipe joint tape (Teflon) where recommended by pipe/fitting
manufacturer, on male threads at each joint and tighten joint to leave not more than 3
threads exposed.
G. Flanged Joints: Match flanges within piping system, and at connections with valves
and equipment. Clean flange faces and install gaskets. Tighten bolts to provide
uniform compression of gaskets.
H. Grooved Pipe Joints: Comply with fitting manufacturer's instructions for making
grooves in pipe ends. Remove burrs and ream pipe ends. Assemble joints in
accordance with manufacturer's instructions.
I. Clean exterior surfaces of installed piping systems of superfluous materials, and
prepare for application of specified coatings (if any).
J. Provide temporary equipment for testing, including pump and gages. Test each
natural section of each piping system independently, but do not use piping system
valves to isolate sections where test pressures exceed valve pressure rating. Fill each
section with water and pressurize for indicated pressure and time.
1. Pipe Sleeves: Provide pipe sleeves of one of the following:
a. Steel Pipe: Fabricate from schedule 40 galvanized steel pipe; remove
burrs.
b. Sleeve Seals: Provide sleeve seals for sleeves located in foundation
walls below grade, or in exterior walls, caulked between sleeve and
pipe.
c. Install pipe sleeves of types indicated where piping passes through
walls, floors, ceilings and roofs. Do not install sleeves through
structural members of work, except as detailed on drawings, or as
reviewed by Architect. Install sleeves so that piping will have free
movement in sleeve, including allowance for thermal expansion; but
not less than 2 pipe sizes larger than piping run. Install length of
sleeve equal to thickness of surface; except floor sleeves. Extend
floor sleeves 1/4" above level floor finish, and 3/4" above floor finish
sloped to drain. Provide temporary support of sleeves during
placement of concrete and other work around sleeves, and provide
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 13 of 17
temporary closure to prevent concrete and other materials from enter-
ing sleeves.
d. Sleeve Seals: Install in accordance with the following:
Fill and pack annular space between sleeve and pipe with
oakum, caulk with lead, on both sides.
2. Provide pipe escutcheons as specified herein with inside diameter closely
fitting pipe outside diameter or outside of pipe insulation where pipe is
insulated. Select outside diameter of escutcheon to completely cover pipe
sleeve and extension, if any. Furnish pipe escutcheons with nickel or chrome
finish for occupied areas; prime paint finish for unoccupied areas.
a. Pipe Escutcheons for all areas: Provide chrome plated sheet steel
escutcheons, solid or split hinged.
b. Subject to compliance with requirements, provide pipe escutcheons
of one of the following:
Chicago Specialty Mfg. Co.
Producers Specialty & Mfg. Co.
Sanitary-Dash Mfg. Co.
c. Install pipe escutcheons on each pipe penetration through floors,
walls, partitions, and ceilings where penetration is exposed to view;
and on exterior of building. Secure escutcheon to pipe so escutcheon
covers penetration hole, and is flush with adjoining surface.
K. Supports, Anchors, and Seals
1. Provide factory-fabricated piping hangers and supports complying with MSS
SP-58, of one of the following MSS types listed, selected by Installer to suit
piping systems, in accordance with MSS SP-69 and manufacturer's published
product information. Use only one type by one manufacturer for each piping
service. Select size of hangers and supports to exactly fit pipe size.
a. Adjustable Steel Clevis Hangers: MSS Type 1, for piping larger than
4".
b. Adjustable Steel Band Hangers: MSS Type 7, for piping 4" and less.
c. Two-Bolt Riser Clamps: MSS Type 8.
2. Provide factory-fabricated hanger-rod attachments complying with MSS SP-
58, of one of the following MSS types listed, selected by Installer to suit
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 14 of 17
horizontal piping hangers and building attachments, in accordance with MSS
SP-69 and manufacturers published product information. Use only one type
by one manufacturer for each piping service. Select size of hanger-rod
attachments to suit hanger rods.
a. Steel Turnbuckles: MSS Type 13.
b. Swivel Turnbuckles: MSS Type 15.
c. Malleable Iron Sockets: MSS Type 16.
d. Steel Weldless Eye Nuts: MSS Type 17.
3. Provide factory-fabricated building attachments complying with MSS SP-58,
of one of the following types listed, selected by Installer to suit building sub-
strate conditions, in accordance with MSS SP-69 and manufacturer's
published product information. Select size of building attachments to suit
hanger rods.
a. Top Beam C-Clamps: MSS Type 19.
b. Side Beam or Channel Clamps: MSS Type 20.
c. C-Clamps: MSS Type 23.
d. Side Beam Clamps: MSS Type 27.
e. Malleable Beam Clamps: MSS Type 30.
4. Subject to compliance with requirements, provide hangers and supports of
one of the following:
B-Line Systems Inc.
Carpenter and Patterson, Inc.
Corner & Lada Co., Inc.
Elcen Metal Products Co.
Fee & Mason Mfg. Co.
ITT Grinnell Corp.
5. Install building attachments at required locations on structural steel or wood
structural members for proper piping support. Space attachments within
maximum piping span length indicated on MSS SP-69. Install additional
building attachments where support is required for additional concentrated
loads, including valves, flanges, guides, strainers, expansion joints, and at
changes in direction of piping.
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 15 of 17
6. Install hangers, supports, clamps and attachments to support piping properly
from building structure; comply with MSS SP-69. Arrange for grouping of
parallel runs of horizontal piping to be supported together on trapeze type
hangers where possible. Install supports with maximum spacing complying
with MSS SP-69. Where piping of various sizes is to be supported together
by trapeze hangers, space hangers for smallest pipe size or install interme-
diate supports for smaller diameter pipe. Do not use wire or perforated metal
to support piping, and do not support piping from other piping.
7. Support sprinkler piping independently of other piping.
8. Install hangers and supports to allow controlled movement of piping systems
and to permit freedom of movement between pipe anchors and to facilitate
action of expansion joints, expansion loops, expansion bends and similar
units.
9. Pipe Slopes: Install hangers and supports to provide pipe slopes and so that
maximum pipe deflections allowed to ANSI B31 Pressure Piping Codes are
not exceeded.
10. Hanger Adjustments: Adjust hangers so as to distribute loads equally on
attachments.
L. Valves
1. Provide factory-fabricated valves recommended by manufacturer for use in
service indicated. Provide valves of types and pressure ratings indicated;
provide proper selection as determined by Installer to comply with instal-
lation requirements. Provide end connections, which properly mate with
pipe, tube, and equipment connections. Where more than one type is indicat-
ed, selection is Installer's option.
a. Unless otherwise indicated, provide valves of same size as upstream
pipe size.
b. Provide handwheels, fastened to valve stem, for valves other than
quarter-turn.
2. Gate Valves
a. Threaded End, 2" and Smaller: FM, UL-listed, 175 psi, bronze body,
solid wedge, outside screw and yoke, rising stem.
Crane: 459
Fairbanks: 0222
Hammond: IB681
Jenkins: 275U
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 16 of 17
Stockham: B-133
Walworth: 904
b. Flanged End, 2-1/2" and Larger: FM, UL listed, 175 psi, iron body
bronze mounted, solid wedge, outside screw and yoke, rising stem.
Crane: 467
Fairbanks: 0412
Hammond: IR1154
Jenkins: 825-A
Stockham: G-634
Walworth: 8713-F
3. Check Valves
a. 2-1/2" and Larger: FM, 175 psi, iron body bronze mounted,
renewable composition disc and bronze seat ring, bolted cover,
flanged ends.
Fairbanks: 0711
Jenkins: 729
Stockham: G-940
Walworth: 8883-LT
4. Install valves where required for proper operation of piping and equipment,
including valves in branch lines where necessary to isolate sections of piping.
Locate valves so as to be accessible and so that separate support can be
provided when necessary.
5. Install valves with stems pointed up, in vertical position where possible, but
in no case with stems pointed downward from horizontal plane unless
unavoidable.
M. Fire Protection Specialties
1. Provide fire protection specialties, UL listed, in accordance with the
following listing. Provide sizes and types, which mate and match piping and
equipment connections.
a. Upright sprinkler heads shall be Viking Corp., Model "M" standard
upright sprinkler head, rough brass. Temperature rating 165oF or as
required by the insurance underwriter.
b. Spare sprinklers shall be provided in one 12-head cabinet equal to
Viking, Model A-1 cabinet. Each cabinet shall have an assortment of
PERFORMANCE SPECIFICATION James House
Northampton, MA
Fire Protection 15300 - 17 of 17
heads as used on the job and also an approved type sprinkler head
wrench; mount cabinet in alarm check valve area.
c. Head guards shall be equal to Reliable Model 1 for upright sprinklers
in areas specified on drawings.
d. Drain and test connections shall be equal to AGF Model 1000 with
sight glass, and test orifice.
e. Horizontal sidewall sprinkler heads shall be Star Model "E" with
wh0
f. Dry horizontal sidewall shall be equal to Viking Model H-1, 1"
NPT, 165oF.
g. Dry pendent sprinkler shall be equal to Viking Model A-1 recessed
type with white cover, extended dry pendent, 1" NPT, 165oF.
h. Subject to compliance with requirements, provide fire protection
specialties of the following Grinnell Fire Protection Systems, Co.,
Inc., Viking Corporation, or equal.
END OF SECTION