41-063 HFP 28 Ridgeview Lot 2GENERAL NOTES: 1.SYSTEM INSTALLATION TO CONFORM TO NFPA-13D, 2013 EDITION. 2.OWNER IS REQUIRED TO PROVIDE HEAT THROUGHOUT THE ENTIRE BUILDING TO MAINTAIN $0,1,0807(03(5$785(2)ƒ)$+5(1+(,7)25$//$5($63527(&7(':,7+$:(7 PIPE SPRINKLER SYSTEM. THE SYSTEM IS TO BE MAINTAINED BY THE OWNER AS REQUIRED BY NFPA-25. 3.BRANCHLINE PIPING: 3.1.EXPOSED WET SYSTEM BRANCHLINE PIPING 1 12" AND SMALLER SHALL BE BLACK SCHEDULE 40 PIPE WITH THREADED CAST IRON FITTINGS OR BLACK SCHEDULE 10 PIPE WITH WELDED OUTLETS & GROOVED FITTINGS. 3.2.WET SYSTEM BRANCHLINE PIPING 1 1/4"& SMALLER, ARMOVERS, AND DROPS/SPRIGS TO NEW SPRINKLERS TO BE CPVC PIPING WITH CPVC FITTINGS AND APPROVED SOLVENT CEMENT. 4.PIPING TO BE SUPPORTED AS REQUIRED BY NFPA-13D. HANGERS ARE TO BE FIELD LOCATED TO BEST SUPPORT THE PIPE. 5.STRUCTURAL LOAD BEARING ANALYSIS OF THE FIRE SPRINKLER SYSTEM AND IT'S RELATED COMPONENTS HAVE NOT BEEN INCLUDED AS PART OF THIS CONTRACT. 6.WORK IS LIMITED TO SPRINKLER SCOPE INDICATED ON THIS DRAWING. 7.SMALL ROOM RULE IN USE WHERE APPLICABLE. 8.OWNER TO MAINTAIN 18" OF CLEARANCE FROM SPRINKLER DEFLECTOR TO TOP OF PENDENT LIGHT FIXTURES & STORAGE. 9. DENOTES HYDRAULIC REFERENCE POINTS. 10.PER MASSACHUSETTS GENERAL LAW CHAPTER 112 SECTION 81R STAMPED FIRE SPRINKLER SHOP DRAWINGS ARE NOT REQUIRED SYSTEM NOTES: 1.BUILDING CONSTRUCTION: COMBUSTIBLE WOOD FRAME RESIDENTIAL HOME 2.OCCUPANCY: ONE OR TWO FAMILY DWELLING 3.DENSITY/AREA: .05 DENSITY/ 2 RESIDENTIAL SPRINKLER HEADS PER MANUFACTURER REQUIREMENTS. 4.SPRINKLER OMISSIONS PER NFPA 13D SECTION 8.3.2: 4.1.BATHROOMS 55 SQ. FT. OR LESS. 4.2.CLOSETS NOT EXCEEDING 24 SQ. FT, SHORTEST DIMENSION DOES NOT EXCEED 3 FT. WALLS & CEILINGS ARE SURFACED WITH NONCOMBUSTIBLE MATERIALS DEFINED IN NFPA 220. 4.3.GARAGES, CARPORTS, & OPEN ATTACHED PORCHES 4.4.ATTICS WITH OR WITHOUT STORAGE, PENTHOUSE EQUIPMENT ROOMS, CRAWL SPACES, AND OTHER CONCEALED SPACES THAT ARE NOT USED OR INTENDED FOR LIVING PURPOSES. SPRINKLER NOTES: 1. F1 RES 49 & RFC49 RESIDENTIAL SPRINKLER SPACING TO BE 16 FEET BETWEEN SPRINKLERS MAX. 8'-0" OFF WALLS MAX. AND 8'-0" MINIMUM BETWEEN SPRINKLERS. 550 GAL. SPRINKLER SUPPLY WATER TANK PUMP 3'-4"8'-5" 1 BASEMENT FLOOR PLAN SCALE: 3/16" = 1'-0" BEDROOM # 2 BEDROOM # 3 KITCHEN PANTRY BREAKFAST MASTER BEDROOM CLOSET CL BATHROOM COAT ROOM LAUNDRY DINING FOYER BATHROOM LIVING ROOM GARAGE CL CL 20.04 GPM at -36.77 PSI TWO HEAD CALCULATION 2 Sprinklers Operating Density .05 GPM Over Two Sprinklers Total Demand at Fire Pump Discharge ALL PIPE TO BE INSTALLED ABOVE BOTTOM CORD OF ROOF JOIST w/ INSULATION & CHICKEN WIRE BY OTHERS TO PROTECT PIPING FROM FREEZING (SEE DETAIL) 1 FIRST FLOOR PLAN SCALE: 3/16" = 1'-0" DETAIL OF INSULATION NOT TO SCALE INSULATION BY OTHERS WIRE MESH BY OTHERS 2 x FRAMING BY OTHERS SPRINKLER PIPING SYM CNT MFG SIN STYLE RESPONSE K ORIF NPT HEAD TEMP COVER TEMP ESCUTCH GUARD FINISH NOTES SPRINKLER LEGEND FOR BOTH FLOORS 17 RELIABLE R3516 PENDENT FR 4.9 7/16 1/2 ƒCHROME MODEL F1 RES 49 19 RELIABLE RA0616 PENDENT FR 4.9 7/16 1/2 ƒCONCEALED WHITE MODEL RFC49 HANGER #1 SEE NOTE # 10