31D-096 Forbes Drawings_ReBid Set_Oct_2017CITY OF NORTHAMPTON240 MAIN STREETNORTHAMPTON, MA 01060DAVID NARKEWICZ, MAYOR OF NORTHAMPTONDAVID POMERANTZ, DIRECTOR OF CENTRAL SERVICESJOE COOK, CHIEF PROCUREMENT OFFICERCHRIS MASON, ENERGY COORDINATORFORBES LIBRARY20 WEST STREETNORTHAMPTON, MA 01060RUSSELL CARRIER, PRESIDENT, BOARD OF TRUSTEES LISA DOWNING, DIRECTORMOLLY MOSS, ASSISTANT DIRECTORJASON PETCEN, FACILITIES MANAGERARCHITECTJONES WHITSETT ARCHITECTS, INC.308 MAIN STREETGREENFIELD, MA 01301413-773-5551PLUMBING, MECHANICAL, ELECTRICALGARCIA GALUSKA DESOUSA CONSULTING ENGINEERS, INC.370 FAUNCE CORNER ROADN. DARTMOUTH, MA 02747-1217508-998-5700Consultants:Proj. Number:Date:Scale:Drawn By:Revisions:A12345678BCDEF 1" = 1'-0"TITLE SHEETT10010/04/171615HDA10/10/17REBIDHVAC UPGRADES AT THEFORBES LIBRARYFORBES LIBRARYNORTHAMPTON, MAFORBES LIBRARY:RESTORATION OF WINDOWS & HVAC UPGRADESLIST OF DRAWINGST001 - TITLESHEETARCHITECTURALA112 - SECOND FLOOR REFLECTED CEILING PLANPLUMBINGP101 - MECHANICAL MEZZANINE PART PLAN - PLUMBINGMECHANICALM101 - HVAC ATTIC PLAN, MECH ROOM PART PLAN & SECTIONM102 - HVAC ROOF PART PLAN, SCHEDULES & DETAILSM103 - HAMPSHIRE ROOM PART PLAN, CONTROL DWGS &SEQUENCESM104 - COOLIDGE ROOM PART PLANELECTRICALE100 - SYMBOLS, SCHEDULES, POWER RISER & NOTESE101 - ELECTRICAL NEW WORK FLOOR PLANS A00123456A0.5ABCDEFGHJE.66.5782.4PATCH AND REPAIR CEILING AT ALL DIFFUSERS AFFECTED BYPROJECT SCOPE. SEE DRAWINGS M103 & M104 FOR SCOPE.LOCAL HISTORY & GENEALOGY213RARE BOOKS214STAIR 1S01GENERAL COLLECTION202WOMEN204MEN203BOOK REPAIR210STAFF WORKROOM212STORAGE211ARTS & MUSIC CIRCULATION205LOBBY206ART GALLERY207PERIODICALS201CALVIN COOLIDGE MEMORIAL ROOM208ARCHIVIST'S OFFICE209EXISTING PENDANTLIGHT FIXTURE TOREMAINEXISTING PENDANT LIGHTFIXTURE TO REMAIN4' - 0"4' - 0"EXISTING HATCHTO MECHANICALMEZZANINESLOPED CEILING,VERIFY SLOPE IN FIELDSLOPED CEILING,VERIFY SLOPE IN FIELDEXISTING PENDANT LIGHTFIXTURE TO REMAINEXISTING PENDANT LIGHTFIXTURE TO REMAINEXISTING PENDANT LIGHTFIXTURE TO REMAINEXISTING PENDANT LIGHTFIXTURE TO REMAINEXISTING SOFFITSEXISTING TRACKLIGHTINGEXISTING TRACKLIGHTINGEXISTING TRACKLIGHTING2A11288LEVEL SLEEPER SURFACE88NEW ROOF EQUIPMENTEXIST. EPDM ROOF (VIF)EXIST. SUBSTRATE (VIF)EXIST. PLYWOOD (VIF)EXIST. ROOF STRUCTURE (VIF)TYPICAL PRESSURE TREATED 8x8WOOD SLEEPER SET FULLY INASPHALT MASTICCONTINUOUS EPDMREINFORCED MEMBRANEFLASHING ADHERED W/ MASTIC6" MIN. MEMBRANE FLASHINGSET FULLY IN ASPHALT MASTICRIPPED P.T. BLOCKING W/1/8" TAPER FOR CRICKETRIPPED P.T. BLOCKING SHIMMED TOKEEP SLEEPER SURFACE LEVELSLEEPERS TO BE 34" O.C., 60" LONG AND ALIGNED WITH THE SLOPE OF THE ROOF.COORDINATE FINAL PLACEMENT W/ MECHANICAL SUBCONTRACTOR2' - 10"DOWN TO ROOF SHEATHING AS REQ.CUT, REMOVE & DISPOSE OFEXIST. MEMBRANE ROOFINGDOWN TO ROOF SHEATING AS REQ.CUT, REMOVE & DISPOSE OFEXIST. MEMBRANE ROOFINGMECH MEZZANINE28' - 6"+/- 1" PLASTER18" X 24" CLAY CEILING TILESSUSPENSION CABLES3" X 2 1/2" CEILING TEES,1'-6 1/2" O.C.METAL LATHEXISTING CEILING TO BE CUT,PATCH PLASTER TO MATCHREMOVE EXISTING CLAY BACKING TILESWHERE REQUIRED FOR NEW DIFFUSERS.TILES TO BE REUSED WHERE POSSIBLE. ATREMAINING LOCATIONS, REPLACE WITHGYPSUM BACKER BOARD, CUT TO FIT.NEW LINEAR DIFFUSERNConsultants:Proj. Number:Date:Scale:Drawn By:Revisions:A12345678BCDEFAs indicatedSECOND FLOOR REFLECTEDCEILING PLANA11210/04/171615HA10/10/17REBIDHVAC UPGRADES AT THEFORBES LIBRARYFORBES LIBRARYNORTHAMPTON, MA 1/8" = 1'-0"12ND FLOOR RCP 1 1/2" = 1'-0"3SLEEPER DETAIL AT NEW ROOF EQUIPMENTGENERAL NOTE:1. NO WINDOW WORK IS INCLUDED IN THIS BID. 1 1/2" = 1'-0"2EXISTING PLASTER CEILING DETAIL AT NEW DIFFUSER BCDE2AHU4AHURELOCATED HUMIDIFIER BY HVACRELOCATED HUMIDIFIERNP NP NPP.C.TO EXTEND 1/2" COLD WATERMAKE-UP TO RELOCATED HUMIDIFIERP.C.TO EXTEND 1/2" COLD WATERMAKE-UP TO RELOCATED HUMIDIFIERCONNECT TO EX. 1/2"COLD WATER MAKE-UPCONNECT TO EX. 1/2"COLD WATER MAKE-UP1615FORBES LIBRARY NORTHAMPTON, MAProject:Date:Scale:Drawn By:Consultants:Revisions:HVAC UPGRADES AT FORBES LIBRARYREBIDSET CGAS NOTEDP101MECHANICAL MEZZANING PART PLAN - PLUMBING 1. THE PLUMBING DRAWINGS ARE DIAGRAMMATIC AND ARE TO BE USED FOR THE PURPOSEOF ESTABLISHING GENERAL LOCATIONS OF PIPING RUNS, SIZES OF PIPING, ANDQUANTITIES OF FIXTURES AND EQUIPMENT TO BE FURNISHED HEREIN. REFER TOARCHITECTURAL DRAWINGS FOR DIMENSIONS FOR EXACT LOCATIONS OF ALL PLUMBINGFIXTURES, AND EQUIPMENT, INCLUDING FLOOR DRAINS, AND MOUNTING HEIGHTS. IN THEEVENT OF CONFLICT OR IF DIMENSIONS ARE NOT SHOWN, OBTAIN FIELD DIRECTIVEFROM THE ARCHITECT AS TO THE LOCATIONS OF ALL VISIBLE EQUIPMENT. PAYPARTICULAR CARE TO COORDINATE WITH THE ARCHITECT'S FIELD REPRESENTATIVE2. EXISTING CONDITIONS INDICATING PIPING AND EQUIPMENT LOCATIONS ARE TAKEN FROMENGINEERING FIELD NOTES AND ARE TO BE CONSIDERED APPROXIMATE ONLY. FIELD VERIFY POINTS OF CONNECTION OF NEW TO EXISTING BEFORE INSTALLING ANY PIPE OR EQUIPMENT.BRING ANY DISCREPANCY TO THE ATTENTION OF THE ARCHITECT.3. INSTALL ALL NEW VALVES SO AS TO BE EASILY ACCESSIBLE AND OPERABLE.4. MAINTAIN PLUMBING SYSTEMS IN OTHER BUILDING AREAS AT ALL TIMES DURING THECONSTRUCTION. REFER TO PHASING PLANS AND SPECIFICATIONS ON THE ARCHITECT'SDRAWINGS & SPECIFICATIONS.HVACGCFPCPCF&IFIRE PROTECTION CONTRACTORHEAT, VENT & AIR COND. CONTRACTORGENERAL CONTRACTORFURNISH AND INSTALLPLUMBING CONTRACTORS&WTYP.EXPTVOVEXISTINGCONNECT TO EXISTINGTYPICALFLOW IN DIRECTION OF ARROWVALVE ON VERTICALSTOP & WASTE VALVEP-TRAPDP,DNRDBVCVFDUPTEE LOOKING DOWNFLOOR DRAIN, ROOF DRAIN, AREA DRAINCHECK VALVEBALL VALVECAP ON END OF PIPEUNIONSTRAINERADPIPE DROP OR DOWNPIPE RISE OR UPABBREVLEGENDHWRHWCWEXSYMBOL NEWHOT WATERHOT WATER RETURNCOLD WATEREXISTING WORK (LIGHT)DESCRIPTIONNEW WORK (DARK)NOTE: NOT ALL SYMBOLS LISTED ARE APPLICABLE TO THIS PROJECTCTEETREXISTING TO REMAINHANGER ROD SUPPORTEDFROM STRUCTURELOCKING NUT(TYP.)FIBERGLASSINSULATIONPIPEGALVANIZED INSULATIONSHIELD - 12" LONGTHIS DETAIL INDICATES HANGING OF INSULATED PIPING WHICHMAY BE EITHER WATER OR STORM DRAIN. CLEVIS HANGERDETAIL APPLIES TO ALL PLUMBING PIPING ON THIS PROJECT.HEAVY-DUTYCLEVIS HANGERSUPPORT NUT(TYP.)TYPICAL PIPE HANGER DETAILN.T.S.PLUMBING SPECIFICATIONA. PERFORM ALL WORK IN ACCORDANCE WITH THE REQUIREMENTS OF THE MASSACHUSETTS PLUMBING CODEAS MOST RECENTLY AMENDED AND ALL OTHER LOCAL, STATE, AND FEDERAL AUTHORITIES HAVINGJURISDICTION. WHERE THESE DOCUMENTS EXCEED CODE AND STANDARDS, THESE DOCUMENTS SUPERSEDE.B. FILE ALL PLANS AND NOTICES WITH APPROPRIATE AUTHORITIES. OBTAIN AND PAY FOR ALL PERMITS AND FEESFOR ALL PLUMBING WORK.C. SCOPE OF WORK INCLUDES THE FURNISHING AND INSTALLING OF COMPLETE WORKING AND APPROVEDSYSTEMS AS SHOWN ON THE DRAWINGS AND AS FOLLOWS:1. DOMESTIC WATER SUPPLY PIPING TO RELOCATED HUMIDIFERS, ALL BEING PROPERLY SUPPORTED,INSULATED, TESTED, VALVED, WITH DRAINS AT LOW POINTS.D. ALL CORE DRILLING AND CUTTING FOR WORK OF THIS TRADE SHALL BE PROVIDED BY THIS SUB-CONTRACTOR.PATCHING TO BE PERFORMED BY GENERAL CONTRACTOR. PRIOR TO CUTTING, HOWEVER, CO-ORDINATELOCATIONS, SIZES, AND METHODS TO BE EMPLOYED IN THE CUTTING AND DRILLING OPERATIONS WITH THEGENERAL CONTRACTOR AND OBTAIN APPROVAL. DO NOT CUT OR DRILL ANY STRUCTURAL ELEMENT UNLESSSPECIFICALLY APPROVED BY THE ARCHITECT.E. PROVIDE SHOP DRAWINGS FOR THE FOLLOWING:1. PIPING, FITTINGS, HANGERS, INSULATION, AND VALVES.F. PIPE AND FITTINGS:1. DOMESTIC HOT AND COLD WATER: TYPE 'L' HARD TEMPERED COPPER TUBING WITH PRESS FITTINGS ANDJOINTS.G. VALVES SHALL BE:1. SHUTOFF VALVES, LEAD FREE BALL VALVES.H. ALL HORIZONTAL AND VERTICAL PIPING SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE (NOT FROMHANGERS OF OTHER TRADES), SPACED IN ACCORDANCE WITH THE CODE. HANGERS SHALL BE CLEVIS TYPEWITH MACHINE THREAD HANGER RODS, COPPER PLATED WHERE IN CONTACT WITH COPPER PIPE, (NO WIRE ORSTRAP HANGERS WILL BE PERMITTED) 14 GAGE GALVANIZED METAL PIPE SHIELDS, 12" LONG, SHALL BE PLACEDBETWEEN HANGERS AND INSULATION.I. AFTER PERFORMING ALL TESTS, INSULATE NEW WATER PIPING, FITTINGS, VALVES, INCLUDING EXPOSED ANDCONCEALED MAINS, RISERS, BRANCHES AND STUBS TO FIXTURE SUPPLIES WITH 1" THICK HEAVY DENSITYPRE-FORMED FIBERGLASS SNAP-ON INSULATION WITH SELF SEALING ALL SERVICE JACKET EQUAL TOCERTAINTEED 850. INCLUDE VAPOR BARRIER ON COLD WATER.1. FITTINGS AND VALVES SHALL USE PRE-FORMED OR SEGMENTED INSULATION COVERED WITHPREMOULDED P.V.C. COVERS OVERLAPPING ADJOINING INSULATION AND SEALED WITH 1-1/2" WIDE VINYLTAPE. ALL MATERIALS USED SHALL BE FIRE RETARDANT, UL/FM APPROVED.2. NO STAPLES WILL BE PERMITTED ON ANY PORTION OF THIS INSTALLATION.J. ALL PIPING PASSING THROUGH WALLS, AND PARTITIONS SHALL BE SLEEVED WITH SCHEDULE 40 GALVANIZEDSTEEL PIPE LARGE ENOUGH TO PROVIDE MIN. 1/4" SPACE BETWEEN PIPE OR INSULATION AND SLEEVE. COREDRILL HOLES LARGE ENOUGH TO ACCOMMODATE SLEEVE. SET SLEEVES IN CONCRETE WITH LEAD AND OAKUMCAULKING. SEAL SPACE BETWEEN SLEEVE AND PIPING WITH U.L. APPROVED RESILIENT CAULKING COMPOUND.SLEEVES THROUGH WALLS OR PARTITIONS SHALL BE SET FLUSH WITH WALL SURFACE; AND THROUGHFLOORS, SHALL EXTEND 2" ABOVE FINISHED FLOOR. COVER ALL EXPOSED PENETRATIONS WITH CHROMEPLATED BRASS ESCUTCHEONS WITH SET SCREWS.K. TEST ALL PIPING PRIOR TO CONCEALING OR INSULATING AND REPAIR ANY LEAKS USING NEW MATERIALS ORRE-JOINING. NO MAKESHIFT REPAIRS, SUCH AS WICKING OR COMPOUNDS, WILL BE PERMITTED.L. KEEP THE PREMISES REASONABLY CLEAN AT ALL TIMES AND AT COMPLETION OF WORK CLEAN ALL FIXTURESAND EQUIPMENT. BE FULLY RESPONSIBLE FOR PROTECTION OF ALL PLUMBING MATERIALS AND EQUIPMENTUNTIL COMPLETION AND FINAL ACCEPTANCE.M. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATION AND ELEVATION OF ALL EQUIPMENT OF THIS TRADE. IFTHERE ARE DISCREPANCIES IN MOUNTING HEIGHTS, BETWEEN THE ARCHITECT'S DRAWINGS AND DIMENSIONSHEREIN, REQUEST CLARIFICATION FROM THE ARCHITECT PRIOR TO ROUGHING.N. COORDINATE SHUTDOWNS OF EXISTING SYSTEMS WITH THE OWNER AND SUBMIT A WRITTEN REQUEST AT LEASTTEN WORKING DAYS IN ADVANCE. MINIMIZE SYSTEM SHUT DOWNS AS MUCH AS POSSIBLE. SUBMIT A LIST OF ALLAFFECTED AREAS, THE PROPOSED WORK TO BE PERFORMED, AND THE EXPECTED LENGTH OF THE SHUT-DOWNINCLUDING TIME FOR RETESTING. PROVIDE TEMPORARY SERVICES TO MAINTAIN ACTIVE SYSTEM DURINGEXTENDED SHUT-DOWNS AS REQUIRED FOR DEMOLITION & CONSTRUCTION PHASING.10/10/17 A00123456A0.5ABCDEFGHJE.66.5782.44-1VAV4-2VAV2-2VAV2-3VAV2-1VAV‘26x14 DN TO AHU-4RELOCATED HUMIDIFIERDISCHARGE TUBE26x12 DN TO AHU-2RELOCATED HUMIDIFIERDISCHARGE TUBE. ADD ACCESSDOORS ON BOTH SIDES OF TUBE& WATER SEAL DUCT UNDERTUBE & 4 FT DOWNSTREAM OFTUBE‘6"x19" LINEAR SLOT DIFFUSER -TYP OF 1014"x19" LINEAR SLOT DIFFUSERREFRIGERANT PIPING SIZED PERMANUFACTURER'S RECOMMENDATIONSDOUBLE INSULATE HUMIDIFIERDISTRIBUTION PIPING IN ATTICDOUBLE INSULATE HUMIDIFIERDISTRIBUTION PIPING IN ATTIC(275)(275)(415)(415)(410)(410)TTO VAV 4-1TTO VAV 4-2HH‘10"x8"10"x8"14"x10"14"x12"18"x14"10"x8"24"x14"RELOCATED HUMIDIFIERDISCHARGE TUBE. ADD ACCESSDOORS ON BOTH SIDES OF TUBE &WATER SEAL DUCT UNDER TUBE &4 FT DOWNSTREAM OF TUBEEXISTING SA TEMP SENSOR & DUCTSMOKE DETECTOR18"x6" 26"x12"26"x12"12"X12"‘‘‘‘‘‘‘‘‘‘‘‘‘‘‘12"X12"TYP OF 5BCDE2AHU4AHU15"x15"40"x14"14"x26"12"x12"AM-1.044"x16"44"x16"13"x11"REFRIGERANT PIPING UP TO ATTICREFRIGERANT PIPING UP TO ATTICHUMIDIFIER DISTRIBUTION PIPING UP TO ATTICRELOCATED EXISTING HUMIDIFIER -PROVIDE NEW STEAM GENERATINGCANNISTERHUMIDIFIER DISTRIBUTION PIPING UP TO ATTIC24"x14" UPVFD-4VFD-2RELOCATED HUMIDIFIER - PROVIDE NEWSTEAM GENERATING CANNISTERPROVIDE NEW VFDS (BY JOHNSON CONTROLS)TEMPORARILY REMOVE 3" & 1-1/2" HHWS/RPIPING RISER FOR ACCESS, THEN REINSTALL &REINSULATETEMPORARILY REMOVE HHWS/R & CONDENSATEPIPING AT SIDE OF AIR HANDLER, THENREINSTALL & REINSULATETEMPORARILY REMOVE OFFSET INDUCTWORK, THEN REINSTALL13"x11"EXISTING 16"x12" SUPPLYDUCT TO REMAINEXISTING AHU-1 TO REMAINEXISTING AHU-3 TO REMAINTEMPORARILY REMOVE CLAMP ON CONDUIT,THEN REINSTALL2" CONDUIT TO ATTIC1" DRAIN1" HUMIDIFIER DRAINPATCH DUCT AT REMOVEDHUMIDIFIER WANDPATCH DUCT AT REMOVEDHUMIDIFIER WAND4AHU12"x12"11"x13"26"x14"16"x44"2AHU40"x14"15"x15"11"x13"16"x44"1-1/4"1-1/4"SHIFT EXISTING ANGLE STAND TO ALIGN WITH NEW AIRHANDLER LOCATION. PROVIDE NEW WAFFLE PADS.EXISTING CHANGEOVER PIPING &CONTROL VALVE TO REMAINEXISTING CHANGEOVER PIPING &CONTROL VALVE TO REMAINCONNECT TO NEW CHANGEOVER COILS WITH UNIONS.PROVIDE NEW BALL VALVE ISOLATION VALVES & PROVIDEDRAIN VALVE WITH HOSE CONNECTION AT LOW POINT.PROVIDE NEW DRAIN PAN TRAP & REWORK/EXTENDCONDENSATE DRAIN PIPING.1615FORBES LIBRARY NORTHAMPTON, MAProject:Date:Scale:Drawn By:Consultants:Revisions:HVAC UPGRADES AT FORBES LIBRARYREBIDSET CLAS NOTEDM101HVAC ATTIC PLAN, MECHANICAL ROOM PART PLAN & SECTION 1M-1.03410/10/17 2CU4CUREFRIGERANT PIPINGDN THRU ROOF INDOGHOUSEROOF IS OUT OF WARRANTY. MODIFY & REPAIRROOF WITH MATERIALS COMPATIBLE WITHEXISTING ROOF AND OF SIMILAR CONSTRUCTIONNO.S-1STYLESDS-100REGISTERSELECTION BASED ON "PRICE"REMARKSVAV BOXESNO.UNITHTGMAXNO.MANUF.MINCFMKWELECTRIC RH COILMBHREMARKSIN WGNcMax DischAPDDIRECT DIGITAL CONTROLSDOOR GRILLEDDCDGCONDENSATE PUMPC.P.AIR CONDITIONER TAG NUMBERAC-XDEEPDPNUMBERNOMAXIMUMMAXRETURN/EXHAUST AIR DUCT SECTIONHEATING,VENTILATING AND AIR COND.MOTORIZED DAMPERBRANCH CONNECTION OUT OF SIDEBRANCH CONNECTION OUT OF BOTTOMBRANCH CONNECTION OUT OF TOPGALVANIZED STEELGALVH.V.A.C.CONDKWFLAE.C.P.C.G.C.A.T.C.PHCON.T.S.U.D.A.F.F.T'STATMANUFHPP.D.T.D.H.E.S.P.T.S.P.VKILOWATTSFULL LOAD AMPSELECTRICAL CONTRACTORPLUMBING CONTRACTORGENERAL CONTRACTORAUTOMATIC TEMP. CONTROLCONDENSATEUNDERCUT DOORABOVE FINISHED FLOORPRESSURE DROPTOTAL DYNAMIC HEADEXTERNAL STATIC PRESSURETOTAL STATIC PRESSUREPHASECLEANOUTNOT TO SCALETHERMOSTATMANUFACTURERHORSEPOWERVOLTSRETURN/EXHAUST AIREFD.B.ALUML.W.B.L.D.B.E.W.B.E.D.B.W.B.L.A.T.E.A.T.VELCFMO.A.MDE-XTYP.EUHMDFDEXHAUST FANALUMINUMLEAVING WET BULBLEAVING DRY BULBENTERING WET BULBENTERING DRY BULBLEAVING AIR TEMPERATUREENTERING AIR TEMPERATURECUBIC FEET PER MINUTEDRY BULB WET BULB VELOCITYOUTSIDE AIREXHAUST REGISTER TAG NUMBERCONNECT TO EXISTINGMOTORIZED DAMPERELECTRIC UNIT HEATERTYPICALFIRE DAMPERTSUPPLY AIR DUCT SECTIONFLOW IN DIRECTION OF ARROWPIPE CLEANOUTSUPPLY AIRTHERMOSTATABBREVDESCRIPTIONSYMBOL /RSRLDIAREFRIGERANT SUCTIONREFRIGERANT LIQUIDDIAMETERLEGENDEXHAUSTEXH.DUCTLESS COOLING UNIT CONDENSER (OUTDOOR)CONDENSING UNITDCUcCUR.A.RETURN AIR###EQUIPMENT TYPEEQUIPMENT NUMBERDUCTLESS COOLING UNIT EVAPORATOR (INDOOR)DCUeDUCTLESS COOLING UNITDCUEBBELECTRIC BASEBOARD12x12S-AGRD DESIGNATION (REFER TO SCHEDULE)500GRD SIZEGRD CFMVOLUMEPDMOCPSYSLBSEERSEERMCASENSLVGENTFTVOLHTGIN WGRPMGPMHZPRESSURE DROPSYSTEMPOUNDSENERGY EFFICIENCY RATIOMINIMUM CIRCUIT AMPACITYSENSIBLEENTERINGMAXIMUM OVERCURRENT PROTECTIONSEASONAL ENERGY EFFICIENCY RATIOLEAVINGLINEAR FOOTHEATINGINCHES OF WATER GAUGEHERTZREVOLUTIONS PER MINUTEGALLONS PER MINUTESPSTATIC PRESSURENORTHHAMPTON, MASSACHUSETTS9075726772AIR CONDITIONING DESIGN DATAOUTDESIGN AREAD.B.D.B.SUMMERW.B.INW.B.WINTERD.B.OUTIND.B.SELECTION BASED ON "JOHNSON CONTROLS" TO MATCH COOLING COIL CAPACITY.CU-2AHU-295AIR COOLED CONDENSING UNITSSERVICEUNITNO.NO.MANUF.UNITMCAMBHTOTAL CLGENT.D.B.REMARKSRHP14J604S2256.837.315.0VOLT/PH.‘ALTERNATE ACCEPTABLE MANUFACTURERS INLUDE TRANE, CARRIER OR EQUAL, PROVIDED THEY COMPLY WITHSCHEDULE & SPECIFICATIONS REQUIREMENTS.SEERW/ COIL-5CU-46(/(&7,216%$6('21-2+1621&21752/6&+$1*(29(5&+,//(':$7(5&2,/5$7(',1+($7,1*$7ƒ($7ƒ/$70%+*30ƒ(:7ƒ/:7NO.UNITTOTALC.F.M.NO.MANUF.C.F.M.O.A.CHILLED WATER COOLING COILAIR HANDLING UNITSP.D.AIRSEN.MBHTOT.GPMCHWWAT.P.D.EWTLWTH.P.S.P.EXTVPH.MOTORREMARKSAHI-20AHU-4AHU-2AHI-204505002200240055.765.079.057.93.1468.356.1--13.74554.91.0"22083ENT. COND.D.B.W.B.P.D.AIRSEN.LVG COND.D.B.W.B.MBHTOT.57.365.079.059.557.351.7--DX COOLING COIL55.765.079.057.93.1468.356.1--13.74554.91.0"2208357.365.079.059.557.351.7--PROVIDE HIGH EFFICIENCY FILTER RACK WITH 2" MERV 8 PREFILTER AND 4" MERV 13 FINAL FILTER.ALTERNATE ACCEPTABLE MANUFACTURERS INCLUDE TRANE, CARRIER OR EQUAL, PROVIDED THEY COMPLY WITH SCHEDULE & SPECIFICATION REQUIREMENTS.SMACNA STANDARDSDUCT GAGE PER(NOT TO SCALE)DIFFUSER/GRILLE CONNECTION TO BRANCHBRANCH DUCTBRANCH DUCT TO ONE DIFFUSER OR GRILLE ONLY1. CONNECTION ONLY TO BEONE DIFFUSER OR GRILLE2. ONLY USED DOWNSTREAMSEALANT ALL AROUND JOINTVOLUME CONTROL DAMPERƒ&21,&$/&211OF VAV BOXUSED FOR BRANCH TONOTES: STAINLESS STEEL HOSE CLAMPSPLITTER DAMPERONLY ON SUPPLYTYPICAL TEE DUCT CONNECTION(NOT TO SCALE)SMACNA STANDARDSNOTE: PROVIDEDUCT GAGE PERTURNING VARIESDOUBLE THICKNESSVOLUME CONTROLDAMPER LOCATED ASCLOSE TO MAIN ASPOSSIBLEVOLUME CONTROLDAMPER LOCATED ASCLOSE TO MAIN ASPOSSIBLEREMOTE STARTERNOTE:FOR ROOF FLASHING, REFER TOARCHITECTURAL DRAWINGSFOR DETAILED INSTRUCTIONSLIQU IDSUCTIONSERVICE VALVE (TYP )SUCTION ACCUMULATORSIZE TO SU IT APPL ICAT IONVALVE-SPORLAN TYPE SVE ,THERMOSTATIC EXPANS IONAIRFLOWEXTERNAL EQUAL IZER (TYP )REMOTE BULB ISOLAT ION VALVEEVAPORATOR COILTRAP (TYP )SITE G LASS (TYP . )SOLENOID VA LVELIQU ID L INEREFRIGERANT PIPING: SUCTION LINES WITH ISOLATIONVALVE, SUCTION ACCUMULATOR AND CHARGINGCONNECTION. LIQUID LINE WITH SITE GLASS HAVING DOUBLEPORTS WITH CAPS, FILTER DRYER, ISOLATION VALVES ANDCHARGING CONNECTION. INSULATE PER SPECIFICATIONS.COVER ALL REFRIGERANT PIPING WITH ULTRA VIOLETPROTECTED PVC COVERING (COLOR= GRAY)REFRIGERANT PIPING DIAGRAMFILTER DRYER :REMOVABLE CORETYPE (TYP )MOUNT UNIT ON ELEVATED(NOT TO SCALE)SPLIT SYSTEMINDOOR UNITEQUIPMENT SUPPORTSPIPING INDICATED IS FOR SINGLE CIRCUIT;CONTRACTOR SHALL PIPE UNITS WITHMULTIPLE CIRCUITS AND HOT GAS BYPASSCIRCUIT AS REQUIRED. ALL COMPONENTSSHALL BE INSTALLED IN SIMILAR MANNERIN ACCORDANCE WITH MANUFACTURE'SRECOMMENDATIONS AND GUIDELINEREQUIREMENTS.CEILINGLINEAR SLOT DIFFUSERSEALANT ALL AROUND JOINTDIFFUSER/GRILLE CONNECTION TO BRANCH(NOT TO SCALE)ƒ%5$1&+'8&7&211(&7,21STAINLESS STEEL HOSE CLAMPBRANCH DUCTDUCT GAGE PERSMACNA STANDARDSNOTES:1. CONNECTION ONLY TO BEUSED FOR BRANCH TO ONEDIFFUSER OR GRILLEVOLUME CONTROL DAMPER LOCATEDAS CLOSE TO MAIN AS POSSIBLEBRANCH DUCT TO ONEDIFFUSER OR GRILLE ONLY14"H METAL PLENUMPER SMACNA STANDARDSFLEXIBLE DUCT 4' MAX LENGTH FOR LINEAR SLOT DIFFUSERSAHU-495YZH06012C55.436.913.0‘EATLATDIAINLETUNITMOCP6036.9ENT. COND.D.B.W.B.LVG COND.D.B.W.B.DCUc(NOT TO SCALE)CU OUTDOOR EQUIPMENT SUPPORT SYSTEMSPLIT SYSTEMTYPICALCOOLING UNITMOUNT DUCTLESSSUPPORT STANDS INCONDENSERS ONACCORDANCE WITHMANUFACTURER'S RECOMMENDATIONSREFRIGERANT PIPE SUPPORTSPROVIDED IN ACCORDANCE SIZEDAND SPACED WITH MANUFACTURER'SRECOMMENDATIONS(TYP)EXACT LENGTH AND WIDTH SHALL BE COORDINATED WITH DCUc EQUIPMENTBY THE HVAC CONTRACTOR PRIOR TO ORDERING SUPPORT STANDS(TYP)ROOF18"FASTENERSSHALL BE SEALEDWEATHER TIGHT.(TYP)ADJ. HANGER W/ROLLER(FOR PIPES 4" & OVER)INSULATIONTYPICAL PIPE HANGER DETAILREFER TO SPECIFICATIONS FOR HANGERCLEVIS HANGER(FOR PIPES UP TO 3")ROD SIZE & SPACING.SUPPORT WEIGHTADEQUATE TO RIGID INSULATIONHIGH DENSITYOF PIPE.NOTE:SHIELD 12"LONG.HEAVY-DUTYHANGERCLEVISGALVINIZEDPIPE COVERINGPROTECTIONFIBERGLASSINSULATIONSUPPORT NUT(TYP.)LOCKING NUT(TYP.)PIPESADDLEINSULATION.FILL W/LOOSEREFER TO SPEC SECTION 230548 FOR SEISMIC& VIBRATION ISOLATION REQUIREMENTS.(NOT TO SCALE)TYPICAL VAV BOX DETAILDUCT SIZES NOTED ARENET INTERIORNOTE:TO DRAWINGS FOR SIZING INFO.)RECTANGULAR DUCT (REFERSIZE (REFER TO SCHEDULE)DUCT DIAMETER TO MATCH INLETELECTRIC REHEAT COILSQUARE TO ROUND FITTINGFLEXTIBLE DUCT 4' MAX8sx48NUMBER OF SLOTS x LENGTHMOUNT ON SLEEPERS SETLEVEL ON SLOPED ROOFWOOD NAILER10"MIN PRESSURE TREATEDSAFINGALL AROUND, TIGHT TOCONTRACTORMEMBRANEROOFCURB BY HVACINSULATED ROOF PENETRATIONHOUSING WITH ACCESSIBLE CAP.RUN THRU ROOF PENETRATIONREFRIGERANT LINE SETS SHALLHOUSING TO INDOOREVAPORATORS SIMILAR TO ROOFPENETRATION HOUSING VAULTMODELS. CONFIRM SIZEWITH NUMBER OF LINE SETSAT EACH CAPTO DCU EVAPORATORS10"MIN ALL EXTERIOR REFRIGERANTPIPING SHALL HAVE ALUMINUMOVER ARMAFLEX PIPEWEATHERPROOF JACKETINGINSULATION (TYP)INSULATED REFRIG.PIPING (TYP)NOT TO SCALECURBREFRFIGERANT PIPE ROOF PENETRATION HOUSINGFASTENCURB TOROOF PERROOF &CURBMANUFACTURER'SRECOMMENDATIONSIF ALTERNATE MANUFACTURERS ARE SELECTED, COORDINATE WITH ACCESS HATCH. HATCH MAY REQUIRE ADDITION MODIFICATION, MORE PIPING MAY NEED TO BE TEMPORARILY REMOVED IN MECHANICAL ROOM OR COMPONENTS OF UNIT MAY NEED TO BE SHIPPED KNOCKED DOWN. 1615FORBES LIBRARY NORTHAMPTON, MAProject:Date:Scale:Drawn By:Consultants:Revisions:HVAC UPGRADES AT FORBES LIBRARYREBIDSET CLAS NOTEDM102HVAC ROOF PART PLAN, SCHEDULES & DETAILS10/10/17 S-12158sx19S-11355sx19TTTHTO VAV 2-1TO VAV 2-2TO VAV 2-3HHS-11355sx19S-11355sx19S-11355sx19S-11355sx19S-11355sx19S-11355sx19S-11205sx19S-11305sx19S-11205sx19S-12158sx19S-12158sx19S-12158sx19S-12108sx19EXISTING RETURN REGISTER - TYPEXISTING DIFFUSER TO BE REMOVED &CEILING PATCHED - TYP FOR 6LIBRARY STAFF WILL REMOVE ALL ARTIFACTS FROM HORIZONTALSURFACES. THE PRIME CONTRACTOR SHALL WRAP THE VERTICALSURFACES SUCH AS BOOKSHELVES IN PLASTIC TO PROTECT ARTIFACTS.THE CONTRACTOR SHALL ONLY DO THIS ONCE, AS HE SHALL HAVEEXCLUSIVE USE OF THE ROOM UNTIL CEILING WORK IS COMPLETE.ROOM TEMPERATURE SENSOR W/ SET32,176/,'(5 ƒ) $1'0$18$/OCCUPANCY OVER-RIDE PUSH BUTTONSPACE/OCC/TECTNCVAV-DPRDAMPERS BY UNITMANUFACTURERACTUATORS &CONTROLS BY ATCCONTRACTORFROMAHUHTG -COILVARIABLE AIR VOLUME BOX (VAV)AIAODIDOALARMDAMPER POS./COMMAND (EACH)XXSUPPLY AIR TEMP.XROOM TEMPERATURE/HUMIDITYXELECTRIC REHEAT COIL WITH % ENERGIZED FEEDBACKVARIABLE AIR VOLUME BOX WITH ELECTRIC REHEATSUPPLY AIR VOLUME (CFM)XXA. THE SPACE THERMOSTAT SHALL MODULATE THE NORMALLY OPEN VARIABLE AIR VOLUME BOX DAMPER BETWEENTHE MAXIMUM AND MINIMUM POSITIONS AS INDICATED IN THE DRAWINGS. AT THE MINIMUM POSITION IF THE SPACETEMPERATURE CONTINUES TO FALL, THE ELECTRIC REHEAT COIL SHALL MODULATE TO MAINTAIN SPACE SETPOINT. AS THE SPACE TEMPERATURE IS SATISFIED, THE REVERSE SHALL OCCUR.B. DURING UNOCCUPIED THE PERIMETER RADIATION SHALL BE THE FIRST STAGE OF HEATING. AS THE SECOND REHEAT COIL SHALL MODULATE TO MAINTAIN UNOCCUPIED SPACE THERMOSTAT SETPOINT.C. WHEN THE BOILER IS NOT OPERATING, THE AIR VOLUME DAMPER SHALL MODULATE TO THE COOLING MINIMUMD. ROOM/ZONE TEMPERATURE SENSORS SHALL HAVE PUSH BUTTON OCCUPIED OVER-RIDE BUTTON CAPABILITY TOMANUALLY CHANGE TO UNIT OCCUPIED MODE FOR A PERIOD OF 3 HOURS (ADJ.)E. THE ROOM HUMIDITY SENSOR SHALL MODULATE THE CENTRAL HUMIDIFIER TO MAINTAIN ROOM HUMIDITY LEVELS.XXSTAGE OF HEATING, THE VAV BOX DAMPER SHALL OPEN TO THE FULL HEATING AIRFLOW AND THE ELECTRICAIR HANDLER WITH A/CAIAOBIBOSHOW ON GRAPHICOUTSIDE AIR TEMPREMARKSOUTSIDE AIR HUMIDITYMIXED AIR TEMPERATUREFILTER DIFFERENTIAL PRESSUREDISCHARGE AIR TEMPALARMSUPPLY AIRFLOWCHANGEOVER COIL FREEZESTATAVBVLOOPSCHEDTRENDXXXXXXXXXXXXXXXXPOINT NAMEHARDWARE POINTSSOFTWARE POINTSDX COIL DISCHARGE TEMPERATUREXOUTSIDE AIR DAMPERXFROM BMS (EXISTING)FROM BMS (EXISTING)XXMODULATING W/ FEEDBACK (NEW)SUPPLY STATIC PRESSUREXSUPPLY FAN STATUSXXXRAOANCAOOADPRFILTER-SDX COOLINGCOILCONDENSINGUNITAC UNIT CONTROL SCHEMATICXXXXTO UNIT CONTROLLERTO UNIT CONTROLLERHEAT PUMP CHANGEOVER TEMPERATUREXXCHANGEOVERCOILHW-VLVNOMA-TDX-SA-TSF-VFDLHSF-AFMSSA-TSADPSAFANSA-HCSCRFRZ-STATSA-SDBY DIV 260000WIRED TO FIRE ALARMPANEL BY DIV 260000WIRED TOSTOP FANSA-DPDIFFERENTIAL PRESSURE SENSOR LOCATED2/3RDS OF THE WAY IN DUCT SYSTEMSUPPLY FAN SPEEDXXXXDUCT SMOKE DETECTORXXXXXXXXXXXDONORADPRRA-TRETURN AIR DAMPERXW/ FEEDBACK (EXISTING)XXRETURN AIR TEMPXXXXADDITIONAL CONTROL ELEMENTSHTSPACE HUMIDITY SENSORSPACE TEMP SENSORREFER TO PLANSRA-HRA-TEXISTINGEXISTING CONTROL ELEMENTS ADDITIONAL CONTROL(EXISTING)(EXISTING)(EXISTING)CHANGEOVER COIL CONTROL VALVEXXHEAT PUMP CHANGEOVER TEMPERATUREXXDUCT STATIC PRESSUREXXXXSUPPLY FAN VFD FAULTXX(EXISTING)XXXXXX* ALL SETPOINTS SHALL BE ADJUSTABLE THRU THE BMS SYSTEM. CONTROLS CONTRACTOR SHALL INSTALL ALL CONTROLS ASSOCIATED WITH HUMIDIFIERS.DUCT HIGH LIMIT HUMIDITYXXHUMIDIFIER START/STOPXXXXXELEMENTSCONTROL ELEMENTSHUMIDIFIER AIR PROVING SWITCHHUMIDIFIER SETPOINTHUMIDIFIER OUTPUT (% OF CAPACITY)RA CO2XXXXXXXXXXXAC UNIT CONTROL SEQUENCE (AHU-2 & AHU-4):1.START/STOP CONTROL: THE OCCUPIED MODE IS SCHEDULED THROUGH THE BMS METASYS SYSTEM. INTHE OCCUPIED MODE, THE SUPPLY FAN RUNS CONTINUOUSLY AND THE OUTDOOR AIR DAMPER OPENSTO THE MINIMUM POSITION. IN THE UNOCCUPIED MODE, THE OUTSIDE AIR DAMPER REMAINS CLOSEDAND THE FAN CYCLES TO MAINTAIN REDUCED HEATING OR ELEVATED COOLING TEMPERATURESETPOINT. ROOM TEMPERATURE SETPOINT SHALL BE ƒ) $'- +/- ƒ) HUMIDITY SETPOINT SHALL BE45% RH +/- 5% RH.2.SUPPLY FAN SPEED CONTROL: THE SUPPLY FAN SHALL ADJUST IT'S SPEED BASED ON THE DUCTMOUNTED PRESSURE SENSOR WHICH WILL FLUCUATE BASED ON VAV DAMPER POSITIONS, KEEPINGABOVE MINIMUM DX COOLING & HEATING MINIMUM AIRFLOW. THE TAB CONTRACTOR SHALL DETERMINETHE EXACT SYSTEM PRESSURE & UTILIZE THIS VALUE AS THE SYSTEM SETPOINT.3.TEMPERATURE CONTROL:A.HEATING & COOLING MODE: THE CHANGEOVER COIL 3-WAY VALVE MODULATES TO MAINTAIN SPACETEMPERATURE SETPOINT. WHEN THE CHILLER IS NOT AVAILABLE AND THERE IS A CALL FORCOOLING, THE SPLIT SYSTEM SHALL OPERATE. THE 2 STAGES OF THE HEAT PUMP SHALL CYCLE &THE HOT GAS BYPASS VALVE SHALL FURTHER MODULATE TO MAINTAIN SPACE TEMPERATURESETPOINT.4. DEHUMIDIFICATION CONTROL: ON A CALL FOR DEHUMIDIFICATION, WHEN THE CHILLER IS AVAILABLE,THE CHANGEOVER COIL 3-WAY VALVE SHALL MODULATE TO MAINTAIN A DISCHARGE AIR TEMPERATURE OF50 DEG (ADJ). THE ELECTRIC REHEAT COILS AT THE VAV BOXES SHALL MODULATE TO MAINTAIN ROOMTEMPERATURE SETPOINT. WHEN THE CHILLER IS NOT AVAILABLE, THE SPLIT SYSTEM SHALL OPERATE.THE 2 STAGES OF THE HEAT PUMP SHALL CYCLE AND THE HOT GAS BYPASS VALVE SHALL FURTHER MODULATE TO MAINTAIN A DISCHARGE AIR TEMPERATURE OF 46 DEG (ADJ). IF HOT WATER HEATING ISAVAILABLE, THE CHANGEOVER COIL SHALL FUNCTION AS THE FIRST STAGE OF REHEAT WITH THE 3-WAYVALVE MODULATING TO MAINTAIN A CALCULATED DISCHARGE AIR TEMPERATURE THAT OPTIMIZES HOTWATER REHEAT & MINIMIZES ELECTRIC REHEAT. THE ELECTRIC REHEAT COILS AT THE VAV BOXES SHALL FUNCTION AS A FINAL STAGE OF REHEAT, MODULATING TO MAINTAIN SPACE TEMPERATURE SETPOINT.5. HUMIDITY CONTROL: IN THE HEATING MODE, THE HUMIDIFIER MODULATES TO MAINTAIN A CONSTANTSPACE HUMIDITY SETPOINT OF 45% RH (ADJ) +/- 5% RH. THE SPACE HUMIDITY SENSORS SHALL BE AVERAGED IN CONTROLLING THE HUMIDIFIER. THE HUMIDIFIER SHALL RUN ONLY WHEN THE AIR PROVINGSWITCH IS SATISFIED. A DUCT MOUNTED HIGH LIMIT HUMIDISTAT SHALL SHUT DOWN THE HUMIDIFIER WHENDUCT HUMIDITY EXCEEDS 90% RH (ADJ). WHEN THE SUPPLY FAN IS OFF, THE HUMIDIFIER SHALL BE DEENERGIZED.6. SAFETIES: IF THE CHANGEOVER COIL DISCHARGE AIR TEMPERATURE FALLS BELOW 38 DEG F (ADJ), THESUPPLY FAN SHALL SHUT DOWN, THE VALVE SHALL OPEN 100% TO THE COIL & THE OUTSIDE AIR DAMPERSHALL CLOSE. AN ALARM SHALL BE INITIATED AT THE BMS OPERATOR WORKSTATION. IF SMOKE ISDETECTED IN THE SUPPLY DUCT, THE SUPPLY FAN SHALL SHUT DOWN AND AN ALARM SHALL BE INITIATEDAT THE BMS OPERATOR WORKSTATION. ON A LOSS OF CONTROL SIGNAL TO THE CHANGEOVER COIL VALVE, THE VALVE SHALL FULLY OPEN TO THE COIL.7. DEMAND CONTROL VENTILATION: A CO2 SENSOR LOCATED IN THE UNIT RA DUCTWORK SHALL MODULATE THE OUTSIDE AIR DAMPER TO MAINTAIN A RETURN AIR CO2 LEVEL OF 800 PPM (ADJ). IF THE CO2LEVEL IS BELOW THRESHOLD, THE OUTSIDE AIR DAMPER SHALL OPEN TO ITS ABSOLUTE MINIMUM POSITION(80 CFM FOR AHU-2 AND 100 CFM FOR AHU-4).22DUCTWORK DIMENSIONS INDICATED ARE CLEAR INSIDE DIMENSIONS.23ALL AIR HANDLING UNITS >2000 CFM SHALL HAVE A DUCT MOUNTEDSMOKE DETECTOR INSTALLED IN THE AIRSTREAM.24ALL SMOKE DAMPERS SHALL BE COMBINATION SMOKE/FIRE DAMPERS SHALLSHALL BE MOTOR OPERATED WITH 24VOLT/120 VOLT ACTUATOR BY HVACCONTRACTOR. FIRE ALARM INTERLOCK BY ELECTRICAL CONTRACTOR.BE FURNISHED, INSTALLED AND POWER WIRED BY HVAC CONTRACTOR. DAMPERS192010161817151412131198763542GENERAL NOTES 1ALL PIPING AND DUCTWORK UNLESS DIMENSIONED IS SHOWNDIAGRAMATICALLY ONLY, EXACT LOCATION SHALL BEDETERMINED IN FIELD AFTER COORDINATING WITH OTHERWORK.FOR TYPICAL PIPING DIAGRAMS AND CONNECTIONS ATEQUIPMENT, SEE DETAIL DRAWINGS.EXACT LOCATION OF ALL CEILING DIFFUSERS, REGISTERS, ANDGRILLES SHALL BE COORDINATED WITH LIGHTING FIXTURES.REFER TO REFLECTED CEILING PLAN.FOR DETAILS OF ROOF CURBS, FLASHING, PIPING, AND VENTSTHRU ROOF REFER TO ARCHITECTURAL DRAWINGS.FOR LOCATION OF OPENINGS IN ROOF AND FLOORS REFERTO STRUCTURAL AND ARCHITECTURAL DRAWINGS.AUTOMATIC VENTS, VALVES, ETC. THAT MUST BESERVICED SHALL BE LOCATED IN ACCESSIBLE POSITIONS.H.V.A.C. CONTRACTOR SHALL PROVIDE REMOVABLE PANELS ATLOCATIONS WHERE ACCESS TO VALVES, DAMPERS, FIRE DAMPERS,ETC. ARE REQUIRED.ALL DUCTWORK SHALL HAVE JOINTS AND SEAMS FILLEDWITH SEALANT FOR AIR TIGHT INSTALLATIONS.PROVIDE SWING JOINTS AT ALL PIPING TAKEOFFS FROMMAINS (MINIMUM OF 3 ELBOWS), AND PROVIDE ISOLATION VALVESALL AIR VENTS & PRESSURE GAUGES SHALL BE INSTALLEDWITH COCKS SUCH THAT THE DEVICE CAN BE REMOVEDWITHOUT DRAINING PIPING SYSTEM.PROVIDE DUCT ACCESS DOORS FOR ALL FIRE AND CONTROLDAMPERS LOCATED IN DUCTWORK RUNS.H.V.A.C. CONTRACTOR SHALL COORDINATE ALL WORK WITHPLUMBING AND ELECTRICAL CONTRACTORS.H.V.A.C. CONTRACTOR SHALL INFORM G.C. AS TO THE LOCATIONAND SIZE OF ALL ACCESS PANELS.ALL SUPPORT STEEL REQUIRED FOR HVAC SYSTEMS AND EQUIPMENTUNLESS SHOWN ON STRUCTURAL DRAWINGS SHALL BE PROVIDED BYH.V.A.C. CONTRACTOR.ALL DUCT ELBOWS SHALL BE LONG RADIUS (R=1.5), OR SQUARETYPE WITH DOUBLE THICKNESS TURNING VANES.DUCT SMOKE DETECTORS INDICATED ARE TO BE PROVIDED &WIRED BY ELECTRICAL CONTRACTOR AND INSTALLED BY H.V.A.C.CONTRACTOR.FOR ALL CONNECTIONS TO BUILDING STEEL REFER TO STRUCTURALDRAWINGS.TOTAL DYNAMIC HEAD AND STATIC PRESSURE INDICATED IN THESCHEDULES IS BASED ON ENGINEERING ANALYSIS AND MAY NOTNECESSARILY MATCH ACTUAL INSTALLED CONDITIONS. THIS CONTRACTORSHALL PROVIDE REQUIRED SHEEVES, BELTS AND DRIVES TO MEETVOLUME FLOW CHARACTERISTICS SPECIFIED.PROVIDE 4" FLEXIBLE CONNECTION AT EACH DUCT CONNECTIONTO FAN OR AIR HANDLING UNIT.THE MANUFACTURER LISTED IN THE SCHEDULES REFLECTS THE BASIS OF DESIGN ASINDICATED ON THE CONTRACT DRAWINGS AND IS NOT INTENDED TO SUGGEST THEREQUIRED PROVIDER. REFER TO THE SPECIFICATIONS FOR A COMPLETE DESCRIPTIONOF EACH PRODUCT REQUIRED AND REFERENCE "OR EQUAL" REQUIREMENTS.PROVIDE ISOLATION VALVES FOR ALL PIPING BRANCH LINES WHICH SERVETWO OR MORE TERMINAL HEATING AND/OR COOLING UNITS AS IT RELATES 21ON SUPPLY AND RETURN PIPING TAKEOFFS.TO INDIVIDUAL SPACES.ATC HOT WATER HEATING CONTROL VALVES SHALL FAIL OPEN ON LOSSOF POWER W/ SPRING RETURN.25THE PRIME CONTRACTOR (HVAC CONTRACTOR) SHALL BE RESPONSIBLE FOR PROVIDING ANY OPENING 12" OR GREATER.261615FORBES LIBRARY NORTHAMPTON, MAProject:Date:Scale:Drawn By:Consultants:Revisions:HVAC UPGRADES AT FORBES LIBRARYREBIDSET CLAS NOTEDM103HAMPSHIRE ROOM PART PLAN, CONTROL DRAWINGS & CONTROL SEQUENCES10/10/17 DEFGHJE.68TTO VAV 4-1TO VAV 4-2HTH234566.572.426x12 DN TO AHU-236"x8"18"x10"18"x6"26"x12"26"x12"EXISTING SA TEMP SENSOR & DUCTSMOKE DETECTORREMOVE DUCTWORK & DIFFUSERREMOVE DUCTWORK& DIFFUSERREMOVE DUCTWORK & DIFFUSERREMOVE DUCTWORKREMOVE DUCTWORKCDE4AHU15"x15"40"x14"14"x26"12"x12"44"x16"24"x14" UPEXISTING 16"x12" SUPPLYDUCT TO REMAINEXISTING AHU-1 TO REMAINEXISTING AHU-3 TO REMAIN2" CONDUIT TO ATTIC2AHUREMOVE BLOWER COIL UNIT &ASSOCIATED DUCTWORK, PIPING,CONTROLS & APPURTENANCESREMOVE BLOWER COIL UNIT &ASSOCIATED DUCTWORK, PIPING,CONTROLS & APPURTENANCESEFGHJE.6826x14 DN TO AHU-4(275)(275)(415)(410)(410)10"x8"10"x8"14"x10"14"x12"18"x14"24"x14"REMOVE DUCTWORKREMOVE DUCTWORKCAP DUCTWORK1615FORBES LIBRARY NORTHAMPTON, MAProject:Date:Scale:Drawn By:Consultants:Revisions:HVAC UPGRADES AT FORBES LIBRARYREBIDSET CLAS NOTEDM104COOLIDGE ROOM HVAC PART PLAN & HVAC REMOVALS PART PLANS10/10/17 1615FORBES LIBRARYNORTHAMPTON, MAProject: Date: Scale: Drawn By: Consultants: Revisions: GARCIA GALUSKA DESOUSA HVAC UPGRADES ATFORBES LIBRARYREBID SET MLP AS NOTED E100SYMBOLS, MECHANICAL SCHEDULE,PANEL SCHEDULE, POWER RISERAND NOTED1. MECHANICAL SCHEDULE NOTES: 2. 3. PROVIDE FLEXIBLE CONNECTION TO EQUIPMENT REFER TO SPECIFICATIONS. CONTROLLERS AND DISCONNECT DEVICES SHALL BE NRTL RATED FOR USE WITH A DESIGN E MOTOR WITH A HORSE POWER RATING NOT LESS THAN 1.4 TIMES THE MOTOR HORSE POWER. (REFER TO ELECTRICAL CODE ARTICLE 430). WHERE INDICATED PROVIDE WEATHERPROOF DUPLEX RECEPTACLES AT MECHANICAL EQUIPMENT. PROVIDE 3/4"C. WITH 2#10+#10G AWG TO NEAREST PANEL AND CONNECT TO 20A/1P CIRCUIT BREAKER UNLESS OTHERWISE INDICATED. 4. 5. TYPICALLY LOCATE STARTERS NEAR EQUIPMENT. ALL EXTERIOR MOUNTED DISCONNECT SWITCHES, JUNCTION/PULL BOXES, RACEWAYS, FLEXIBLE CONNECTION TO EQUIPMENT, ETC. SHALL BE NEMA "3R." 6.WHERE INDICATED PROVIDE 120 VOLT CIRCUIT FOR LIGHT FIXTURE TYPE "J" AT EXTERIOR CHILLER AS NOTED. TYPICALLY CONNECT TO SAME 120 VOLT RECEPTACLE CIRCUIT UNLESS OTHERWISE INDICATED. 7.PROVIDE 3/4" CONDUIT WITH PULL LINE BETWEEN INDOOR UNIT & OUTDOOR UNIT FOR EACH SPLIT SYSTEM. (TYPICAL FOR ALL "DCU" UNITS). PROVIDE FUSED DISCONNECT SWITCHES AS REQUIRED @ UNIT. 8.PROVIDE HARD CONNECTION FOR CONDENSATE PUMP (CP-1) FOR AHU UNITS AS REQUIRED. PROVIDE THERMAL SWITCH AT UNIT. REFER TO MECHANICAL DRAWINGS FOR INDOOR UNIT LOCATIONS. SEE DETAIL E100 1 SCHEDULE OF MECHANICAL EQUIPMENT DESCRIPTION VOLT PH FEEDER REMARKS EQUIPMENT AND CONNCECTIONS STS J SWP VFD LOCATION CO D UNIT NO. LOAD CHARACTERISTICS PANEL CIRCUIT CIRCUIT BREAKER ---AHU-1 --AIR HANDLING UNIT MECH. RM.EXISTING 208 3 ---------EXISTING TO REMAIN J 2015 3020152015 40 S 225 200 42MP1MAIN ELEC RM.(2)-60A/2P 30 30 -10 -----3 1 1 PANEL NO.LOCATION MTG MAIN BUS AMPS MAIN CB BRANCH CKT BREAKER (AMPS) 1 POLE 2 POLE 3 POLE TOTAL POLES OTHERS PANEL SCHEDULE 120/208V, 3Ø, 4W, 22 KAIC LEGEND NOTES: SYMBOL LIST ON THIS PROJECT. ALL EQUIPMENT IS TO BE PROVIDED UNDER THIS SECTION UNLESS SPECIFICALLY INDICATED OTHERWISE. DRAWINGS. NOT ALL SYMBOLS OR ABBREVIATIONS ARE NECESSARILY USED SHALL BE USED AS A DICTIONARY TO DEFINE ITEMS INDICATED ON THIS SHEET IS A GENERAL LIST OF SYMBOLS AND ABBREVIATIONS AND POWER FLEXIBLE CONNECTION TO EQUIPMENT DW J J J WIRE AND RACEWAYS WIRING AND RACEWAY - NO. OF DIAGONAL LINES INDICATES 2#12 AWG+#12AWG GROUND UNLESS NOTED OTHERWISE. NO. #12 AWG CONDUCTORS. ABSENCE OF DIAGONAL LINES INDICATES GROUND WIRE IS NOT SHOWN IN COUNT BUT SHALL BE PROVIDED. A. JUNCTION BOX - SIZE AS REQUIRED. 120/208 VOLT, 3 PHASE, 4 WIRE POWER PANEL GENERAL CONTRACTOR GROUND FAULT INTERRUPTER HEATING, VENTILATING, AND HORSEPOWER JUNCTION BOX ISOLATED GROUND AIR CONDITIONING SUBCONTRACTOR THOUSAND CIRCULAR MILS G,GND KCMIL HVAC IT JB HP IG GC GFI GROUND CONDUIT (GENERIC TERM FOR CABLE TELEVISION CIRCUIT BREAKER AUTOMATIC TRANSFER SWITCH ABOVE FINISHED FLOOR ABOVE FINISHED GRADE RACEWAY. PROVIDE AS SPECIFIED) CENTERLINE ELECTRIC METALLIC TUBING ELECTRIC WATER COOLER ELECTRICAL SUBCONTRACTOR FIRE ALARM FURNISHED AND INSTALLED AMERICAN WIRE GAUGE INTERRUPTING CAPACITY AMP, FRAME CATV EMT FA FPC F&I DWG EWC EC CU CL DP CKT CB CLG DRAWING DEEP CEILING CIRCUIT COPPER ARCH ATS AWG C ATC AT AFG AIC AFF A AL AF AMP TRIP ARCHITECT AMPERE ALUMINUM ABBREVIATIONS TELEPHONE/DATATEL/DATA UNLESS NOTED OTHERWISE MOUNT 72 INCHES TO CENTERLINE ABOVE FINISHED FLOOR OR GRADE TYPICAL WIRE GUARD EXPLOSION PROOF WEATHERPROOF TRANSFORMER @72" XFMR WP XP TYP UNO WG KITCHEN EQUIPMENT SUPPLIER MAIN DISTRIBUTION PANEL THOUSAND CIRCULAR MILS MOTOR CONTROL CENTER MAIN CIRCUIT BREAKER MANUAL TRANSFER SWITCH POLY-VINYL CHLORIDE CONDUIT PLUMBING SUBCONTRACTOR RIGID GALVANIZED STEEL CONDUIT NOT IN CONTRACTNIC NUMBER NOT TO SCALE PULL BOX PHASE POWER REFRIGERATOR SWITCHBOARD SOLID NEUTRAL POLE(S) PH,Ø RGS SWBD SN PVC REF PWR P PC PB NO,# NTS KILO-WATT KILO-VOLT AMPERE LIGHTING MOUNTING HEIGHT MOUNTING MOUNTED MAIN LUGS ONLY MCM MTD MTG MTS MDP MLO MH LTG MCC MCB KES KW KVA INTERMEDIATE METALLIC CONDUITIMC HORSEPOWER RATED THERMAL SWITCH WITH PILOT LIGHT OTHERWISE. HOMERUN TO PANEL - NO. OF ARROWS INDICATES NO. OF 20 AMP/1 POLE CIRCUITS TO PANEL - UNLESS NOTED INFORMATION TECHNOLOGY SUBCONTRACTOR AUTO-TEMP CONTROL SUBCONTRACTOR FIRE PROTECTION SYSTEM SUBCONTRACTORJUNCTION BOX - WITH FLEXIBLE CONNECTION TO EQUIPMENT-"DW" DENOTES DISHWASHER, "H" HOOD, "WO" WALL OVEN, "D" DISPOSER, "HD" HAND DRYER. IF EXACT MOUNTING OR RACEWAY ROUTINGS ARE NOT INDICATED (LOCATION OR HEIGHT) REQUEST CLARIFICATION PRIOR TO ROUGHING, OR INSTALLATION. WIRE AND CONDUIT SIZES INDICATED ON HOMERUNS SHALL BE CONTINUOUS THROUGHOUT CIRCUIT. 17. 16. 15. 14. 13. 12. 11. 10. 9. ALL MOUNTING HEIGHTS ARE TO CENTERLINE UNLESS OTHERWISE INDICATED. SUPPORT ALL WORK FROM THE BUILDING STRUCTURE. GENERAL NOTES: DRAWINGS, SPECIFICATIONS, CODES, LOCAL AUTHORITIES AND REGULATIONS. INCLUDE ON THE CONTRACT DOCUMENTS INCLUDING THE DRAWINGS AND THE THE SCOPE OF WORK SHALL INCLUDE PROVIDING ALL WORK INDICATED, BOTH DOCUMENTS . WHERE DOCUMENTS CONFLICT WITHIN THEMSELVES OR WITH CODES AND REGULATIONS, PROVIDE THE HIGHER QUANTITY AND OF WORK. IN GENERAL, WORK REQUIREMENTS ARE NOT INDICATED IN ANY CONTRACT DOCUMENT SHALL BE CONSIDERED PART OF THE SCOPE SPECIFICATIONS, WHICH ARE COMPLIMENTARY. WORK INDICATED IN AND COORDINATION WITH ALL TRADES. SCOPE OF WORK IS INDICATED TEST ALL EQUIPMENT AND SYSTEMS INSTALLED TO CERTIFY COMPLIANCE WITH LABOR AND COSTS FOR TESTING, REVIEWS, APPROVALS AND CERTIFICATIONS. QUALITY AND FOLLOW THE STRICTER REQUIREMENTS. 6. 7. 8. 5. 4. 3. 2. 1. FUSED DISCONNECT SWITCH HEAVY DUTY TYPE-"3R" INDICATES NEMA 3R3R EQUIPMENT CONTROL PANEL.CP E ELECTRIC DOOR-OPERATOR. FURN. & INST. BY GC, WIRED BY EC. COORDINATE WITH THE GENERAL CONTRACTOR, OTHER TRADES AND OF MANUFACTURERS EQUIPMENT AND MAKE ALL FINAL CONNECTIONS AS REQUIRED, I.E., POWER, CONTROL, INTERLOCK, ETC. ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH OSHA, NFPA STANDARDS, THE ELECTRICAL CODE AND THE LOCAL GOVERNING AUTHORITIES. THE DRAWINGS AND SPECIFICATIONS DO NOT ATTEMPT TO INDICATE ALL WORK REQUIRED BY CODES AND AUTHORITIES. DRAWINGS ARE DIAGRAMMATIC ONLY. EXACT LOCATION, MOUNTING HEIGHTS OF EQUIPMENT AND ROUTING OF RACEWAYS SHALL BE COORDINATED WITH THE EQUIPMENT REQUIREMENTS AND FIELD CONDITIONS. FURNISH AND INSTALL ALL INCIDENTAL ACCESSORIES NECESSARY TO MAKE THE ELECTRICAL WORK COMPLETE AND READY FOR OPERATION. ELECTRICAL WORK SHALL BE RECESSED INTO WALLS OR INSTALLED ABOVE HUNG CEILINGS UNLESS OTHERWISE INDICATED. DO NOT INSTALL OUTLETS BACK TO BACK. PROVIDE 24 INCH SPACING IN FIRE RATED WALLS. PROVIDE ELECTRICAL OUTLET PLATE GASKET SEALS AT RECEPTACLES, SWITCHES AND OTHER ELECTRICAL BOXES ON EXTERIOR WALLS AND INTERIOR WALLS BETWEEN CONDITIONED AND NON-CONDITIONED SPACES. FURNISH AND INSTALL CODE REQUIRED DISCONNECTS WHICH ARE NOT FURNISHED BY THE HVAC OR PLUMBING CONTRACTORS. INSTALL A GREEN GROUNDING CONDUCTOR WITHIN EACH RACEWAY SIZED IN ACCORDANCE WITH THE ELECTRIC CODE. PROVIDE NRTL LISTED SMOKE AND FIRE SEALS AT ALL PENETRATIONS THROUGH FLOORS OR FULL HEIGHT (SLAB TO SLAB) WALLS. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE COPPER MINIMUM #12 AWG. SIZE UNLESS OTHERWISE INDICATED. (REFER TO MECHANICAL EQUIPMENT SCHEDULE) MECHANICAL EQUIPMENT EXHAUST FAN - F & I BY HVAC, WIRED BY E.C. UNIT HEATER - F & I BY HVAC, WIRED BY E.C. CABINET HEATER - F & I BY HVAC, WIRED BY E.C. EF UH CH BB ELECTRIC BASEBOARD-FURNISHED BY HVAC, INSTALLED AND WIRED BY EC. EXISTING EQUIPMENT TO REMAIN.XM RELOCATED. NEW LOCATION OF RELOCATED EXISTING EQUIPMENT. EQUIPMENT INSTALLED IN SAME LOCATION. EXISTING EQUIPMENT TO BE REMOVED AND NEW EXISTING EQUIPMENT TO BE REMOVED ANDXR XL XN OUTLET/BACK TO PANEL. EXISTING EQUIPMENT DOTTED DENOTES EXISTING EQUIPMENT. EXISTING EQUIPMENT TO BE REMOVED AND CIRCUIT PULLED BACK TO NEXT ACTIVE X MOTOR - NUMERAL INDICATES HORSEPOWER2 TS X X XAHU-2 --AIR HANDLING UNIT MECH. RM.2 HP 208 3 ---------UTLIZE EXISTING CIRCUIT ---AHU-3 --AIR HANDLING UNIT MECH. RM.EXISTING 208 3 --------- UTLIZE EXISTING CIRCUIT -----------EXISTING TO REMAIN X X XAHU-4 --AIR HANDLING UNIT MECH. RM.2 HP 208 3 --------- X X XCU-2 X XCOOLING UNIT EXTERIOR 37.3 MCA 208 1 MP1-1,3 60A/2P 3#4 & 1#10G, 1"C ------NEMA 3R X X XCU-4 --COOLING UNIT EXTERIOR 36.9 MCA 208 1 MP1-2,4 60A/2P 3#4 & 1#10G, 1"C ------NEMA 3R 9 9 9.DISCONNECT EXISTING MOTOR AND RE-CONNECT NEW MOTOR AFTER INSTILLATION OF NEW MOTOR BY HVAC CONTRACTOR. EXTEND EXISTING WIRING AND PROVIDE NEW FUSING AS REQUIRED. COORDINATE WITH HVAC CONTRACTOR. ---H-2 --HUMIDIFIER MECH. RM.EXISTING 208 3 ---------EXISTING TO BE RELOCATED. ---H-4 --HUMIDIFIER MECH. RM.EXISTING 208 3 ---------EXISTING TO BE RELOCATED. X X XVAV-2-1 X XVARIABLE AIR VOLUME BOX ABOVE CLG 4 KW 208 3 MP1-5,7,9 20A/3P 4#12 & 1#12G, 3/4"C ------- X X XVAV-2-2 X XVARIABLE AIR VOLUME BOX ABOVE CLG 4 KW 208 3 MP1-6,8,10 20A/3P 4#12 & 1#12G, 3/4"C ------- X X XVAV-2-3 X XVARIABLE AIR VOLUME BOX ABOVE CLG 7 KW 208 3 MP1-11,13,15 30A/3P 4#10 & 1#10G, 3/4"C ------- X X XX X------- X X XX X------- BASEMENT MECHANICAL MEZZANINE 4#3/0 & 1#4G,2"C. NEW PANEL MP1 EXISTING SIEMENS 800A/3P SWITCHBOARD 'DP' XM N.T.S. ONE LINE DIAGRAM - POWER1 E100 PROVIDE NEW 200A/3P CIRCUIT BREAKER INSTALLED IN 3 POLE SPACE. CIRCUIT BREAKER TO MATCH EXISTING AIC RATINGS AND MANUFACTURER. 800A/3P EXISTING PANEL PP1 XM VAV-4-1 VARIABLE AIR VOLUME BOX ABOVE CLG 3.5 KW 208 3 MP1-12,14,16 20A/3P 4#12 & 1#12G, 3/4"C VAV-4-2 VARIABLE AIR VOLUME BOX ABOVE CLG 10 KW 208 3 MP1-17,19,21 40A/3P 4#8 & 1#10G, 3/4"C 10.VFD BY HVAC CONTRACTOR, INSTALLED AND WIRED BY ELECTRICAL CONTRACTOR. COORDINATE WITH HVAC CONTRACTOR. 10 10 11 11 11.EXISTING HUMIDIFIER TO BE RELOCATED. EXTEND CONDUIT AND WIRING AS REQUIRED. COOLING COIL BY HVAC. FAN COIL DRAIN PAN LOW VOLTAGE PIG TAIL WIRE BY HVAC. DETECTION UNIT FLOAT SWITCH @ DISCHARGE 1/2" KNOCKOUT BY E.C. COORDINATE WITH HVAC SUNCONTRACTOR JB 4" SQ. x 2 1/2" DP. J. BOX FOR CONNECTION OF PIG TAIL. CONDENSATE PUMP FURNISHED BY HVAC. MOUNTED IN 1" NIPPLE FOR PIG TAIL CORD. 120VAC, 1Ø POWER SUPPLY. BY HVAC. DRAIN PIPING FROM CONDENSATE PUMP BY HVAC. DRAIN PIPING FROM CONDENSATE PUMP BY HVAC. TS 8" x 8" x 4" NEMA 1 ENCLOSURECONDENSATE PUMP FUNRNISHED BY HVAC, TYPICAL FOR 3. INSTALLED & WIRED BY E.C. OF DRAIN PAN BY HVAC. BY E.C. CONDENSATE PUMP WIRING DETAIL WITH APPROVED SHOP DRAWINGS PRIOR TO ROUGHING. WIRING MAY VARY BY MANUFACTURER. FIELD CONFIRM1 NOTE: SCALE: N.T.S.E100 2 WP D EXCELINE, HUBBELL, RIG-A-LITE FIXTURE MANUFACTURER (EQUALS) LIGHT SOURCE DESCRIPTIONMTG.MANUFACTURER MODEL / SERIESTYPE LIGHTING FIXTURE SCHEDULE VOLTAGE LUMENS WATTS TYPE LURALINEJ WALL UTILITY SERVICE FIXTURE WITH PRISMATIC FROSTED GLASS GLOBE AND CAST GUARD88411LVW43-FR-L10 LTE 50K-TAL 5000K LED120 10/10/17 REBID A0 0 1 2 3 4 5 6 A0.5 A B C D E F G H J E.6 6.5 7 8 2.4 2 CU 4 CU ON ROOFON ROOF 2-1 VAV 2-2 VAV 2-3 VAV 4-1 VAV 4-2 VAV APPROXIMATE LOCATION OF EXISTING SWITCHBOARD 'DP' IN BASEMENT 2" ELECTRICAL CONDUIT. CORE UP INTO MECHANICAL CHASE TO MECHANICAL MEZZANINE. EXPOSED CEILING AREA ACT CEILING AREA PLEXIGLASS REMOVABLE PANEL AREA APPROXIMATE LOCATION OF CONDUIT RUN IN BASEMENT. COORDINATE EXACT ROUTE WITH EXISTING CONDITIONS. 3 4 B C D E XM 4 AHU 3 AHUXN XM 1 AHU 2 AHU XN EXISTING PANEL 'PP1' XM 2 H 1 H XR XR NEW PANEL MP1' VFD-4 VFD-2 1 H XL 2 H XL 1615FORBES LIBRARYNORTHAMPTON, MAProject: Date: Scale: Drawn By: Consultants: Revisions: GARCIA GALUSKA DESOUSA HVAC UPGRADES ATFORBES LIBRARYREBID SET MLP AS NOTED E101ELECTRICAL New Work Floor Plans7. BRANCH CIRCUIT NOTES: 5. 6. 4. 3. 2. 1.COORDINATE EXACT LOCATION OF ALL DEVICES AND EQUIPMENT W/ARCHITECT PRIOR TO INSTALLATION. REFER TO MECHANICAL PLANS FOR ANY CHANGES AND FOR EXACT LOCATION OF ALL HVAC EQUIPMENT. WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES OR SPECIAL CONDITIONS. WIRING AND CONDUIT SHALL BE REQUIRED BETWEEN ALL OUTLETS INDICATED WITH CIRCUIT NUMBERS AND PANEL DESIGNATIONS. REFER TO SPEC FOR MC CABLE USE. ALTHOUGH ALL BRANCH CIRCUIT WIRE AND CONDUIT IS NOT SHOWN, IT IS THE INTENT OF THESE DOCUMENTS THAT A COMPLETE BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE 98% CONDUCTIVITY, COPPER MINIMUM #12 AWG SIZE, THWN/THHN INSULATION, 600 VOLTS RATED UNLESS OTHERWISE NOTED. ALL RECEPTACLE BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS. GENERAL DEMOLITION NOTES: 1. 2. 3. 4. 5. 6. REFER TO DEMOLITION SECTION OF SPECIFICATION FOR ADDITIONAL REQUIREMENTS. WHERE DOWNSTREAM DEVICES ARE AFFECTED BY THE DEMOLITION WORK THIS CONTRACTOR SHALL PROVIDE NEW SERVICES AS REQUIRED TO MAINTAIN SUCH DOWNSTREAM DEVICES. ALL DEVICES AND/OR EQUIPMENT REMOVED BY THIS CONTRACTOR SHALL BE INSPECTED BY THE OWNER FOR DETERMINATION OF DISPOSAL OR STORAGE AS DIRECTED BY THE OWNER. FOR PURPOSES OF PRICING THIS CONTRACTOR SHALL ASSUME THAT NO DEVICE OR EQUIPMENT WILL BE RE-USED UNLESS SPECIFICALLY NOTED AS SUCH. TURN OVER ALL LIGHT FIXTURES TO OWNER IN GOOD CONDITION. IT IS NOT THE INTENT OF THESE DRAWINGS TO SHOW ALL EQUIPMENT TO BE DISCONNECTED AND/OR REMOVED. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO VISIT THE SITE PRIOR TO SUBMITTING HIS/HER BID TO DETERMINE THE EXACT QUANTITY AND TYPES OF EQUIPMENT TO BE REMOVED. PARTICULAR CARE SHALL BE TAKEN TO AVOID CREATING HAZARDS ON THE PROJECT OR CAUSING DISRUPTION OF SERVICES REMAINING. ALL EXISTING EQUIPMENT INDICATED TO BE REMOVED SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER. ALL EXISTING EQUIPMENT INDICATED TO BE TURNED OVER TO THE OWNER SHALL BE PRESENTED TO THE OWNER IN GOOD CONDITION AT A LOCATION DESIGNATED BY THE OWNER. ALL OTHER EQUIPMENT SHALL BE REMOVED FROM THE SITE. SCALE: 1/8"=1'-0" ELECTRICAL FLOOR PLAN - POWER1 E101 SCALE: 1/8"=1'-0" ELECTRICAL MEZZANINE PLAN - POWER1 E101 10/10/17 REBID