Loading...
AWC-DCA3-FireRatedFloorWall-1007Fire-Rated Wood-Frame Wall and Floor/Ceiling Assemblies Building Code Requirements For occupancies such as stores, apartments, of-fices, and other commercial and industrial uses, build- ing codes commonly require floor/ceiling and wall assemblies to be fire-resistance rated in accordance with standard fire tests. Depending on the application, wall assemblies may need to be rated either from one side or both sides. For specific exterior wall applications, the model building codes allow wood-frame, wood-sided walls to be tested for exposure to fire from the inside only. Rating for both interior and exterior fire expo- sure is only required when the wall has a fire separa- tion distance of less than 5 feet. Code recognition of one and two-hour wood-frame wall systems is also predicated on successful fire and hose stream testing in accordance with ASTM E119, Standard Test Methods for Fire Tests of Building Construction Materials. Fire Tested Assemblies Fire-rated wood-frame assemblies can be found in a number of sources including the IBC, Underwriters Laboratories (UL) Fire Resistance Directory, Intertek Testing Services' Directory of Listed Products, and the Gypsum Association's Fire Resistance Design Manual. The American Wood Council (AWC) and its members have tested a number of wood-frame fire-rated assem- blies. Descriptions of successfully tested lumber wall assemblies are provided in Table 1 for one-hour rated wall assemblies and Table 2 for two-hour rated wall assemblies. Lumber shall be identified by the grade mark of a lumber grading or inspection agency that has been approved by an accreditation body that complies with the American Softwood Lumber Standard (PS 20). Descriptions of successfully tested I-joist floor as- semblies are provided in Table 3 for one-hour rated floor/ceiling assemblies and Table 4 for two-hour rated floor/ceiling assemblies. I-joists are required to comply with the latest version of ASTM D5055, Standard Specification for Establishing and Monitoring Struc- tural Capacities of Prefabricated Wood I-Joists. Addi- tional tests are being conducted and the Tables will be updated periodically. Conclusions Wood-frame assemblies are used in architectural designs because of their adaptability to style prefer- ences, ease and economies of construction, and en- ergy-saving performance. Copyright © 2010 American Wood Council 2 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES Table 1 One-Hour Fire-Rated Loadbearing Wood-Frame Wall Assemblies Assemblies Rated From Both Sides Studs Insulation Sheathing on Both Sides Fasteners Details 2x4 @ 16" o.c. 3½" mineral wool batts 5/8" Type X Gypsum Wallboard (H) 2¼" #6 Type S drywall screws @ 12" o.c. WS4-1.1 2x6 @ 16" o.c. (none) 5/8" Type X Gypsum Wallboard (H) 2¼" #6 Type S drywall screws @ 7" o.c. WS6-1.1 2x6 @ 16" o.c. 5½" mineral wool batts 5/8" Type X Gypsum Wallboard (H) 2¼" #6 Type S drywall screws @ 12" o.c. WS6-1.2 2x6 @ 16" o.c. R-19 fiberglass insulation 5/8" Type X Gypsum Wallboard (V) 2¼" #6 Type S drywall screws @ 12" o.c. WS6-1.4 Assemblies Rated From One Side (Fire on Interior Only) Studs Insulation Sheathing Fasteners I 5/8" Type X Gypsum Wallboard (H) 2¼" #6 Type S drywall screws @ 12" o.c. 2x4 @ 16" o.c. 3½" mineral wool batts E 3/8" wood structural panels (V) 6d common nails @ 6" edges/12" field WS4-1.2 I 5/8" Type X Gypsum Wallboard (V) 6d cement coated box nails @ 7" o.c. ½" fiberboard (V) 1½" roofing nails @ 3" edges/6" field 2x4 @ 16" o.c. 4 mil polyethylene 3½" mineral wool batts E 3/8" hardboard shiplapped panel siding 8d galv. nails @ 4" edges/8" field WS4-1.3 I 5/8" Type X Gypsum Wallboard (H) 2¼" #6 Type S drywall screws @ 12" o.c. 2x6 @ 16" o.c. 5½" mineral wool batts E 7/16" wood structural panels (V) 6d common nails @ 6" edges/12" field WS6-1.3 I 5/8" Type X Gypsum Wallboard (V) 2¼" #6 Type S drywall screws @ 12" o.c. 2x6 @ 16" o.c. R-19 fiberglass insulation E 3/8" wood structural panels (V) 6d common nails @ 6" edges/12" field WS6-1.5 H- applied horizontally with vertical joints over studs I- Interior sheathing V- applied vertically with vertical joints over studs E- Exterior sheathing Table 2 Two-Hour Fire-Rated Loadbearing Wood-Frame Wall Assemblies Assemblies Rated From Both Sides Studs Insulation Sheathing on Both Sides Fasteners Details B 5/8" Type X Gypsum Wallboard (H) 2¼" #6 Type S drywall screws @ 24" o.c. 2x6 @ 24" o.c. 5½" mineral wool batts F 5/8" Type X Gypsum Wallboard (H) 2¼" #6 Type S drywall screws @ 8" o.c. WS6-2.1 H- applied horizontally with vertical joints over studs B- Base layer sheathing F- Face layer sheathing . American Wood Council FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES 3 Table 3 One-Hour Fire-Rated Wood Floor/Ceiling Assemblies Wood I-Joist Assemblies Joists Insulation Furring Ceiling Sheathing Fasteners Details I-joists @ 24" o.c. Min. flange depth: 1-1/2" Min. flange area: 5.25 sq. in. Min. web thickness: 3/8" Min. I-joist depth: 9-1/4" 1-1/2" mineral wool batts (2.5 pcf-nominal) Resting on hat-shaped channels Hat-shaped channels F 5/8" Type C Gypsum Wallboard (GWB) 1-1/8" Type S drywall screws spaced 12" o.c. in GWB field spaced 8" o.c. at GWB end joi ts n (see fastening details) WIJ-1.1 I-joists @ 24" o.c. Min. flange depth: 1-1/2" Min. flange area: 5.25 sq. in. Min. web thickness: 7/16" Min. I-joist depth: 9-1/4" 1-1/2" mineral wool batts (2.5 pcf-nominal) Resting on resilient channels Resilient channels F 5/8" Type C Gypsum Wallboard (GWB) 1" Type S drywall screws spaced 12" o.c. in GWB field spaced 8" o.c. at GWB end joi ts n(see fastening details) WIJ-1.2 I-joists @ 24" o.c. Min. flange depth: 1-5/16" Min. flange area: 2.25 sq. in. Min. web thickness: 3/8" Min. I-joist depth: 9-1/4" 2" mineral wool batts (3.5 pcf-nominal) Resting on 1x4 setting strips Resilient channels F 5/8" Type C Gypsum Wallboard (GWB) 1-1/8" Type S drywall screws spaced 7" o.c. in GWB field spaced 7" o.c. at GWB end joi ts n (see fastening details) WIJ-1.3 I-joists @ 24" o.c. Min. flange depth: 1-1/2" Min. flange area: 3.45 sq. in. Min. web thickness: 3/8" Min. I-joist depth: 9-1/4" 1" mineral wool batts (6 pcf-nominal) Resting on hat-shaped channels under I-joist bottom flange Hat-shaped channels supported by CSC clips F 1/2" Type C Gypsum Wallboard (GWB) 1" Type S drywall screws spaced 12" o.c. in GWB field spaced 6" o.c. at GWB end joi ts n(see fastening details) WIJ-1.4 B 1/2" Type C Gypsum Wallboard (GWB) 1" Type S drywall screws spaced 12" o.c. in GWB field spaced 12" o.c. at GWB end joints I-joists @ 24" o.c. Min. flange depth: 1-1/2" Min. flange area: 2.25 sq. in. Min. web thickness: 3/8" Min. I-joist depth: 9-1/4" (none) (none) F 1/2" Type C Gypsum Wallboard (GWB) 1-5/8" Type S drywall screws spaced 12" o.c. in GWB field spaced 8" o.c. at GWB end joints 1-1/2" Type G drywall screws spaced 8" o.c. at GWB end joi ts n(see fastening details) WIJ-1.5 B 1/2" Type X Gypsum Wallboard (GWB) 1-1/4" Type S drywall screws spaced 12" o.c. in GWB field spaced 12" o.c. at GWB end joints I-joists @ 24" o.c. Min. flange depth: 1-5/16" Min. flange area: 1.95 sq. in. Min. web thickness: 3/8" Min. I-joist depth: 9-1/2" (none) Resilient channels F 1/2" Type X Gypsum Wallboard (GWB) 1-5/8" Type S drywall screws spaced 12" o.c. in GWB field spaced 12" o.c. at GWB end joints 1-1/2" Type G drywall screws spaced 8" o.c. at GWB end joi ts n(see fastening details) WIJ-1.6 B 1/2" Type X Gypsum Wallboard (GWB) 1-1/4" Type S drywall screws spaced 12" o.c. in GWB field spaced 12" o.c. at GWB end joints I-joists @ 24" o.c. Min. flange depth: 1-1/2" Min. flange area: 2.25 sq. in. Min. web thickness: 3/8" Min. I-joist depth: 9-1/2" Fiberglass batts Resting on resilient channels Resilient channels F 1/2" Type X Gypsum Wallboard (GWB) 1-5/8" Type S drywall screws spaced 12" o.c. in GWB field spaced 12" o.c. at GWB end joints 1-1/2" Type G drywall screws spaced 8" o.c. at GWB end joi ts n(see fastening details) WIJ-1.7 B- Base layer sheathing F- Face layer sheathing American Wood Council 4 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES American Wood Council Table 4 Two-Hour Fire-Rated Wood Floor/Ceiling Assemblies Wood I-Joist Assemblies Joists Insulation Furring Ceiling Sheathing Fasteners Details (none) B 5/8" Type C Gypsum Wallboard (GWB) 1-5/8" Type S drywall screws spaced 12" o.c. in GWB field spaced 12" o.c. at GWB end joints M 5/8" Type C Gypsum Wallboard (GWB) 1" Type S drywall screws spaced 12" o.c. in GWB field spaced 12" o.c. at GWB end joints I-joists @ 24" o.c. Min. flange depth: 1-1/2" Min. flange area: 2.25 sq. in. Min. web thickness: 3/8" Min. I-joist depth: 9-1/4" 3-1/2" fiberglass insulation Supported by stay wires spaced 12" o.c. Hat-shaped channels F 5/8" Type C Gypsum Wallboard (GWB) 1-5/8" Type S drywall screws spaced 8" o.c. in GWB field spaced 8" o.c. at GWB end join ts (see fastening details) WIJ-2.1 B- Base layer sheathing (direct attached) M- Middle layer sheathing F- Face layer sheathing While every effort has been made to insure the accu- racy of the information presented, the American Wood Council and its members do not assume responsibility for a particular design prepared from this publication. For additional information or assistance contact: American Wood Council 803 Sycolin Rd, Suite 201 Leesburg, VA 20175 http://www.awc.org/ 202-463-2766 Copyright © 2010 American Wood Council January 2009 & March 2010 Revisions FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES 5 WS4-1.1 One Hour Fire-Resistive Wood-Frame Wall Assembly 2x4 Wood Stud Wall – 100% Design Load – ASTM E 119/NFPA 251 2 1 3 4 2 1. Framing - Nominal 2x4 wood studs, spaced 16 in. o.c., double top plates, single bottom plate 2. Sheathing - 5/8 in. Type X gypsum wallboard, 4 ft. wide, applied horizontally. Horizontal joints are unblocked. Horizontal application of wallboard represents the direction of least fire resistance as opposed to vertical applica- tion. 3. Insulation - 3-1/2 in. thick mineral wool insulation (2.5 pcf, nominal) 4. Fasteners - 2-1/4 in. #6 Type S drywall screws, spaced 12 in. o.c. 5. Joints and Fastener Heads - Wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound Tests conducted at the Fire Test Laboratory of National Gypsum Research Center Test No: WP-1248 (Fire Endurance) March 29, 2000 WP-1246 (Hose Stream) March 09, 2000 Third Party Witness: Intertek Testing Services Report J20-06170.1 This assembly was tested at 100% design load, calculated in accordance with the 2005 National Design Specification® for Wood Construction. The authority having jurisdiction should be consulted to assure acceptance of this report. Copyright © 2010 American Wood Council January 2009 6 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES WS4-1.2 One-Hour Fire-Resistive Wood-Frame Wall Assembly 2x4 Wood Stud Wall – 100% Design Load – ASTM E 119/NFPA 251 2 4 1 6 3 5 1 Framing - Nominal 2x4 wood studs, spaced 16 in. o.c., double top plates, single bottom plate 2. Interior Sheathing - 5/8 in. Type X gypsum wallboard, 4 ft. wide, applied horizontally. Horizontal joints are un- blocked. Horizontal application of wallboard represents the direction of least fire resistance as opposed to vertical application. 3. Exterior Sheathing - 3/8 in. wood structural panels (oriented strand board), applied vertically, horizontal joints blocked 4. Gypsum Fasteners - 2-1/4 in. #6 Type S drywall screws, spaced 12 in. o.c. 5. Panel Fasteners - 6d common nails (bright) - 12 in. o.c. in the field, 6 in. o.c. panel edges 6. Insulation - 3-1/2 in. thick mineral wool insulation (2.5 pcf, nominal) 7. Joints and Fastener Heads - Wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound Tests conducted at the Fire Test Laboratory of National Gypsum Research Center Test No: WP-1261 (Fire Endurance & Hose Stream) November 1, 2000 Third Party Witness: Intertek Testing Services Report J20-006170.2 This assembly was tested at 100% design load, calculated in accordance with the 2005 National Design Specification® for Wood Construction. The authority having jurisdiction should be consulted to assure acceptance of this report. Copyright © 2010 American Wood Council January 2009 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES 7 WS4-1.3 One-Hour Fire-Resistive Wood-Frame Wall Assembly 2x4 Wood Stud Wall – 78% Design Load – ASTM E 119/NFPA 251 2 5 6 3 4 1 7 8 9 1. Framing - Nominal 2x4 wood studs, spaced 16 in. o.c., double top plates, single bottom plate 2. Interior Sheathing - 5/8 in. Type X gypsum wallboard, 4 ft. wide, applied vertically, unblocked 3. Exterior Sheathing - 1/2 in. fiberboard sheathing. Alternate construction - minimum 1/2 in. lumber siding or 1/2 in. wood based sheathing. 4. Exterior Siding - 3/8 in. hardboard shiplap edge panel siding. Alternate construction - lumber, wood based, vinyl, or aluminum siding. 5. Vapor Barrier - 4-mil polyethylene sheeting 6. Insulation - 3-1/2 in. thick mineral wool insulation (2.5 pcf, nominal) 7. Gypsum Fasteners - 6d cement coated box nails spaced 7 in. o.c. 8. Fiberboard Fasteners - 1-1/2 in. galvanized roofing nails - 6 in. o.c. in the field, 3 in. o.c. panel edges 9. Hardboard Fasteners - 8d galvanized nails - 8 in. o.c. in the field, 4 in. o.c. panel edges 10. Joints and Fastener Heads - Wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound Tests conducted at the Gold Bond Building Products Fire Testing Laboratory Test No:WP-584 (Fire Endurance & Hose Stream) March 19, 1981 Third Party Witness: Warnock Hersey International, Inc. Report WHI-690-003 This assembly was tested at 78% design load using an le/d of 33, calculated in accordance with the 2005 National Design Specification® for Wood Construction. The authority having jurisdiction should be consulted to assure acceptance of this report. Copyright © 2010 American Wood Council January 2009 8 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES WS6-1.1 One-Hour Fire-Resistive Wood-Frame Wall Assembly 2x6 Wood Stud Wall – 100% Design Load – ASTM E 119/NFPA 251 2 1 3 2 1. Framing - Nominal 2x6 wood studs, spaced 16 in. o.c., double top plates, single bottom plate 2. Sheathing - 5/8 in. Type X gypsum wallboard, 4 ft. wide, applied horizontally. Horizontal joints are unblocked. Horizontal application of wallboard represents the direction of least fire resistance as opposed to vertical applica-tion. 3. Fasteners - 2-1/4 in. #6 Type S drywall screws, spaced 7 in. o.c. 4. Joints and Fastener Heads - Wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound Tests conducted at the Fire Test Laboratory of National Gypsum Research Center Test No: WP-1232 (Fire Endurance) September 16, 1999 WP-1234 (Hose Stream) September 27, 1999 Third Party Witness: Intertek Testing Services Report J99-22441.2 This assembly was tested at 100% design load, calculated in accordance with the 2005 National Design Specification® for Wood Construction. The authority having jurisdiction should be consulted to assure acceptance of this report. Copyright © 2010 American Wood Council January 2009 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES 9 WS6-1.2 One-Hour Fire-Resistive Wood-Frame Wall Assembly 2x6 Wood Stud Wall – 100% Design Load – ASTM E 119/NFPA 251 2 1 3 4 2 1. Framing - Nominal 2x6 wood studs, spaced 16 in. o.c., double top plates, single bottom plate 2. Sheathing - 5/8 in. Type X gypsum wallboard, 4 ft. wide, applied horizontally. Horizontal joints are unblocked. Horizontal application of wallboard represents the direction of least fire resistance as opposed to vertical applica- tion. 3. Insulation - 5-1/2 in. thick mineral wool insulation (2.5 pcf, nominal) 4. Fasteners - 2-1/4 in. #6 Type S drywall screws, spaced 12 in. o.c. 5. Joints and Fastener Heads - Wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound Tests conducted at the Fire Test Laboratory of National Gypsum Research Center Test No: WP-1231 (Fire Endurance) September 14, 1999 WP-1230 (Hose Stream) August 30, 1999 Third Party Witness: Intertek Testing Services Report J99-22441.1 This assembly was tested at 100% design load, calculated in accordance with the 2005 National Design Specification® for Wood Construction. The authority having jurisdiction should be consulted to assure acceptance of this report. Copyright © 2010 American Wood Council January 2009 10 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES WS6-1.3 One-Hour Fire-Resistive Wood-Frame Wall Assembly 2x6 Wood Stud Wall – 100% Design Load – ASTM E 119/NFPA 251 2 3 4 1 6 5 1. Framing - Nominal 2x6 wood studs, spaced 16 in. o.c., double top plates, single bottom plate 2. Interior Sheathing - 5/8 in. Type X gypsum wallboard, 4 ft. wide, applied horizontally. Horizontal joints are un-blocked. Horizontal application of wallboard represents the direction of least fire resistance as opposed to vertical application. 3. Exterior Sheathing - 7/16 in. wood structural panels (oriented strand board), applied vertically, horizontal joints blocked 4. Gypsum Fasteners - 2-1/4 in. #6 Type S drywall screws, spaced 12 in. o.c. 5. Panel Fasteners - 6d common nails (bright) - 12 in. o.c. in the field, 6 in. o.c. panel edges 6. Insulation - 5-1/2 in. thick mineral wool insulation (2.5 pcf, nominal) 7. Joints and Fastener Heads - Wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound Tests conducted at the Fire Test Laboratory of National Gypsum Research Center Test No: WP-1244 (Fire Endurance & Hose Stream) February 25, 2000 Third Party Witness: Intertek Testing Services Report J99-27259.2 This assembly was tested at 100% design load, calculated in accordance with the 2005 National Design Specification® for Wood Construction. The authority having jurisdiction should be consulted to assure acceptance of this report. Copyright © 2010 American Wood Council January 2009 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES 11 WS6-1.4 One-Hour Fire-Resistive Wood-Frame Wall Assembly 2x6 Wood Stud Wall – 100% Design Load – ASTM E 119/NFPA 251 2 1 3 4 2 1. Framing - Nominal 2x6 wood studs, spaced 16 in. o.c., double top plates, single bottom plate 2. Sheathing - 5/8 in. Type X gypsum wallboard, 4 ft. wide, applied vertically. All panel edges backed by framing or blocking. 3. Insulation - R-19 fiberglass insulation 4. Fasteners - 2-1/4 in. #6 Type S drywall screws, spaced 12 in. o.c. 5. Joints and Fastener Heads - Wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound Tests conducted at NGC Testing Services Test No: WP-1346 (Fire Endurance) August 22, 2003 WP-1351 (Hose Stream) September 17, 2003 Third Party Witness: NGC Testing Services This assembly was tested at 100% design load, calculated in accordance with the 2005 National Design Specification® for Wood Construction. The authority having jurisdiction should be consulted to assure acceptance of this report. Copyright © 2010 American Wood Council January 2009 12 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES WS6-1.5 One-Hour Fire-Resistive Wood-Frame Wall Assembly 2x6 Wood Stud Wall – 100% Design Load – ASTM E 119/NFPA 251 2 4 1 6 53 1. Framing - Nominal 2x6 wood studs, spaced 16 in. o.c., double top plates, single bottom plate 2. Interior Sheathing - 5/8 in. Type X gypsum wallboard, 4 ft. wide, applied vertically. All panel edges backed by framing or blocking. 3. Exterior Sheathing - 3/8 in. wood structural panels (oriented strand board), applied vertically, horizontal joints blocked 4. Gypsum Fasteners - 2-1/4 in. #6 Type S drywall screws, spaced 7 in. o.c. 5. Panel Fasteners - 6d common nails (bright) - 12 in. o.c. in the field, 6 in. o.c. panel edges 6. Insulation - R-19 fiberglass insulation 7. Joints and Fastener Heads - Wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound Tests conducted at the NGC Testing Services Test No: WP-1408 (Fire Endurance & Hose Stream) August 13, 2004 Third Party Witness: NGC Testing Services This assembly was tested at 100% design load, calculated in accordance with the 2005 National Design Specification® for Wood Construction. The authority having jurisdiction should be consulted to assure acceptance of this report. Copyright © 2010 American Wood Council January 2009 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES 13 WS6-2.1 Two-Hour Fire-Resistive Wood-Frame Wall Assembly 2x6 Wood Stud Wall – 100% Design Load – ASTM E 119/NFPA 251 2 1 3 4 2 5 1. Framing - Nominal 2x6 wood studs, spaced 24 in. o.c., double top plates, single bottom plate. 2. Sheathing: Base Layer - 5/8 in. Type X gypsum wallboard, 4 ft. wide, applied horizontally, joints staggered on opposite sides of the wall. Face Layer - 5/8 in. Type X gypsum wallboard, 4 ft. wide, applied horizontally, joints staggered with base layer. Horizontal joints are unblocked. Horizontal application of wallboard represents the direction of least fire resis- tance as opposed to vertical application. 3. Insulation - 5-1/2 in. thick mineral wool insulation (2.5 pcf, nominal) 4. Gypsum Fasteners: Base Layer - 2-1/4 in. #6 Type S drywall screws, spaced 24 in. o.c. 5. Gypsum Fasteners: Face Layer - 2-1/4 in. #6 Type S drywall screws, spaced 8 in. o.c. 6. Joints and Fastener Heads - Wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound Tests conducted at the Fire Test Laboratory of National Gypsum Research Center Test No: WP-1262 (Fire Endurance) November 3, 2000 WP-1268 (Hose Stream) December 8, 2000 Third Party Witness: Intertek Testing Services Report J20-006170.3 This assembly was tested at 100% design load, calculated in accordance with the 2005 National Design Specification® for Wood Construction. The authority having jurisdiction should be consulted to assure acceptance of this report. Copyright © 2010 American Wood Council March 2010 14 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES WIJ-1.1 One-Hour Fire-Resistive Ceiling Assembly Floora/Ceiling - 100% Design Load - 1 Hour Rating - ASTM E 119 / NFPA 251 5 2 4 6 3 1. Floor Topping (optional, not shown): Gypsum concrete, lightweight or normal concrete topping. 2. Floor Sheathing: Minimum 23/32 inch thick tongue-and-groove wood sheathing (Exposure 1). Installed per code requirements with minimum 8d common nails and glued to joist top flanges with AFG-01 construction adhesive. 3. Insulation: Minimum 1-1/2 inch thick mineral wool insulation batts – 2.5 pcf (nominal), supported by furring channels. 4. Structural Members: Wood I-joists spaced a maximum of 24 inches on center. Minimum I-joist flange depth: 1-1/2 inches Minimum I-joist flange area: 5.25 inches2 Minimum I-joist web thickness: 3/8 inch Minimum I-joist depth: 9-1/4 inches See ASTM D 5055-07 for qualification requirements. 5. Furring Channels: Minimum 0.026 inch thick galvanized steel hat-shaped furring channels, attached perpendicu- lar to I-joists using 1-5/8 inch long drywall screws. Furring channels spaced 16 inches on center and doubled at each wallboard end joint extending to the next joist. 6. Gypsum Wallboard: Minimum 5/8 inch thick Type C gypsum wallboard installed with long dimension perpen- dicular to furring channels and fastened to each channel with minimum 1-1/8 inch long Type S drywall screws. Fasteners spaced 12 inches on center in the field of the wallboard, 8 inches on center at wallboard end joints, and 3/4 inches from panel edges and ends. End joints of wallboard staggered. 7. Finish System (not shown): Face layer joints covered with tape and coated with joint compound. Screw heads covered with joint compound. Fire Test conducted at Gold Bond Building Products Research Center February 9, 1990 Third Party Witness: Warnock Hersey International, Inc. Report No: WHI-651-0311.1 STC and IIC Sound Ratings for Listed Assembly Without Gypsum Concrete With Gypsum Concrete Cushioned Vinyl Carpet & Pad Cushioned Vinyl Carpet & Pad STC IIC STC IIC STC IIC STC IIC - - - - - - 49 b 59 b a This assembly may also be used in a fire-rated roof/ceiling application, but only when constructed exactly as described. b STC and IIC values estimated by David L. Adams Associates, Inc Copyright © 2010 American Wood Council January 2009 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES 15 WIJ-1.2 One-Hour Fire-Resistive Ceiling Assembly Floora/Ceiling - 100% Design Load - 1 Hour Rating - ASTM E 119 / NFPA 251 5 2 4 6 3 1. Floor Topping (optional, not shown): Gypsum concrete, lightweight or normal concrete topping. 2. Floor Sheathing: Minimum 23/32 inch thick tongue-and-groove wood sheathing (Exposure 1). Installed per code requirements with minimum 8d common nails and glued to joist top flanges with AFG-01 construction adhesive. 3. Insulation: Minimum 1-1/2 inch thick mineral wool insulation batts – 2.5 pcf (nominal), supported by resilient channels. 4. Structural Members: Wood I-joists spaced a maximum of 24 inches on center. Minimum I-joist flange depth: 1-1/2 inches Minimum I-joist flange area: 5.25 inches2 Minimum I-joist web thickness: 7/16 inch Minimum I-joist depth: 9-1/4 inches See ASTM D 5055-07 for qualification requirements. 5. Resilient Channels: Minimum 0.019 inch thick galvanized steel resilient channels, attached perpendicular to I- joists using 1-5/8 inch long drywall screws. Resilient channels spaced 16 inches on center and doubled at each wallboard end joint extending to the next joist. 6. Gypsum Wallboard: Minimum 5/8 inch thick Type C gypsum wallboard installed with long dimension perpen- dicular to resilient channels and fastened to each channel with minimum 1 inch long Type S drywall screws. Fas-teners spaced 12 inches on center in the field of the wallboard, 8 inches on center at wallboard end joints, and 3/4 inches from panel edges and ends. End joints of wallboard staggered. 7. Finish System (not shown): Face layer joints covered with tape and coated with joint compound. Screw heads covered with joint compound. Fire Test conducted at Gold Bond Building Products Research Center June 19, 1984 Third Party Witness: Warnock Hersey International, Inc. Report No: WHI-694-0159 STC and IIC Sound Ratings for Listed Assembly Without Gypsum Concrete With Gypsum Concrete Cushioned Vinyl Carpet & Pad Cushioned Vinyl Carpet & Pad STC IIC STC IIC STC IIC STC IIC 51 b 46 b 51 b 64 b 60 b 50 b 60 b 65 b a This assembly may also be used in a fire-rated roof/ceiling application, but only when constructed exactly as described. b STC and IIC values estimated by David L. Adams Associates, Inc Copyright © 2010 American Wood Council January 2009 16 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES WIJ-1.3 One-Hour Fire-Resistive Ceiling Assembly Floora/Ceiling - 100% Design Load - 1 Hour Rating - ASTM E 119 / NFPA 251 2 4 7 6 53 1. Floor Topping (optional, not shown): Gypsum concrete, lightweight or normal concrete topping. 2. Floor Sheathing: Minimum 23/32 inch thick tongue-and-groove wood sheathing (Exposure 1). Installed per code requirements. 3. Insulation: Minimum 2 inch thick mineral wool insulation batts – 3.5 pcf (nominal), supported by setting strip edges, friction-fitted between the sides of the I-joist flanges. 4. Structural Members: Wood I-joists spaced a maximum of 24 inches on center. Minimum I-joist flange depth: 1-5/16 inches Minimum I-joist flange area: 2.25 inches2 Minimum I-joist web thickness: 3/8 inch Minimum I-joist depth: 9-1/4 inches See ASTM D 5055-07 for qualification requirements. 5. Setting Strips: Minimum 1x4 (nominal) wood setting strips attached with 1-1/2 inch long drywall screws at 24 inches on center along the bottom flange of I-joist creating a ledge to support insulation. 6. Resilient Channels: Minimum 0.019 inch thick galvanized steel resilient channels, attached perpendicular to I- joists using 1-7/8 inch long drywall screws. Resilient channels spaced 16 inches on center and doubled at each wallboard end joint extending to the next joist. 7. Gypsum Wallboard: Minimum 5/8 inch thick Type C gypsum wallboard installed with long dimension perpen- dicular to resilient channels and fastened to each channel with minimum 1-1/8 inch long Type S drywall screws. Fasteners spaced 7 inches on center and 3/4 inches from panel edges and ends. End joints of wallboard staggered. 7. Finish System (not shown): Face layer joints covered with tape and coated with joint compound. Screw heads covered with joint compound. Fire Test conducted at National Gypsum Testing Services, Inc. September 28, 2001 Third Party Witness: Underwriter’s Laboratories, Inc. Report No: NC3369 STC and IIC Sound Ratings for Listed Assembly Without Gypsum Concrete With Gypsum Concrete Cushioned Vinyl Carpet & Pad Cushioned Vinyl Carpet & Pad STC IIC STC IIC STC IIC STC IIC 51 b 46 b 52 66 60 b 48 b 60 b 60 b a This assembly may also be used in a fire-rated roof/ceiling application, but only when constructed exactly as described. b STC and IIC values estimated by David L. Adams Associates, In Copyright © 2010 American Wood Council January 2009 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES 17 WIJ-1.4 One-Hour Fire-Resistive Ceiling Assembly Floora/Ceiling - 100% Design Load - 1 Hour Rating - ASTM E 119 / NFPA 251 . Floor Topping (optional, not shown): Gypsum concrete, lightweight or normal concrete topping. ode require- 3. l wool insulation batts – 6 pcf (nominal), with width equal to the on-center spacing 4. I-joist flange area: 3.45 inches2 D 5055-07 for qualificatio 5. Furring Channels: Minimum 0.0 els, attached perpendicular to I-joists C . 6. inimum 1/2 inch thick Type C gypsum wallboard. Wallboard installed with long dimension perpen- 7. er joints covered with tape and coated with joint compound. Screw heads covered with ed at Underwriter’s Laboratories, Inc. May 11, 1983 R10371-1 2 4 6 5 3 1 2. Floor Sheathing: Minimum 23/32 inch thick tongue-and-groove wood sheathing (Exposure 1). Installed per cments with minimum 8d common nails. Insulation: Minimum 1 inch thick mineraof the I-joists. Batts installed on top of furring channels and under bottom flange of I-joists with the sides butted against sup-port clips. Abutted ends of batts centered over furring channels with batts tightly butted at all joints. Structural Members: Wood I-joists spaced a maximum of 24 inches on center. Minimum I-joist flange depth: 1-1/2 inches Minimum Minimum I-joist web thickness: 3/8 inch Minimum I-joist depth: 9-1/4 inches See ASTM n requirements. 19 inch thick galvanized steel hat-shaped furring channspaced 24 inches on center. At channel splices, adjacent pieces overlapped a minimum of 6 inches and tied with a double strand of No. 18 gage galvanized steel wire at each end of the overlap. Channels secured to I-joists with Simpson Type CSsupport clips at each intersection with the I-joists. Clips nailed to the side of I-joist bottom flange with one 1-1/2 inch long No11 gage nail. A row of furring channel located on each side of wallboard end joints and spaced 2.25 inches from the end joint (4.5 inches on center). Gypsum Wallboard: Mdicular to furring channels and fastened to each channel with minimum 1 inch long Type S drywall screws. Fasteners spaced 12 inches on center in the field of the wallboard, 6 inches on center at wallboard end joints, and 3/4 inches from panel edges and ends. End joints of wallboard staggered. For staggered wallboard end joints, furring channels extend a minimum of 6 inches beyond each end of the joint. Finish System (not shown): Face layjoint compound. Fire Test conduct Third Party Witness: Underwriter’s Laboratories, Inc. Report No: UL STC and IIC Sound Ra isted Assembly tings for L Without Gypsum sum Concrete Concrete With Gyp Cushion et & Pad Cushioned pet & Pad ed Vinyl Carp Vinyl Car S S S S TC IIC TC IIC TC IIC TC IIC - - 46 68 51 47 50 73 a This assembly may also be used in a fire-rated roof/ceiling application, but only when constructed exactly as described. Copyright © 2010 American Wood Council January 2009 18 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES WIJ-1.5 One-Hour Fire-Resistive Ceiling Assembly Floor /Ceiling - 100% Design Load - 1 Hour Rating - a ASTM E 119 / NFPA 251 23 4B 4A 1. Floor Topping (optional, not shown): Gypsum concrete, lightweight or normal concrete topping. lled per code ge area: 2.25 inches2 55-07 for qu 4. Gypsum Wallboard: Two laye ched with the long dimen-sion perpendicular to the I-joists as follows: wallboard centered on bottom flange of the I-joist and stag- - 5. F 2. Floor Sheathing: Minimum 23/32 inch thick tongue-and-groove wood sheathing (Exposure 1). Instarequirements with minimum 8d common nails. 3. Structural Members: Wood I-joists spaced a maximum of 24 inches on center. Minimum I-joist flange depth: 1-1/2 inches Minimum I-joist flanMinimum I-joist web thickness: 3/8 inch Minimum I-joist depth: 9-1/4 inches 50See ASTM D alification requirements. rs of minimum 1/2 inch Type C gypsum wallboard atta 4a. Wallboard Base Layer: Base layer of wallboard attached to bottom flange of I-joists using 1 inch Type S drywall screws at 12 inches on center. End joints of gered. 4b. Wallboard Face Layer: Face layer of wallboard attached to bottom flange of I-joists through base layer us- ing 1-5/8 inch Type S drywall screws spaced 12 inches on center on intermediate joists and 8 inches on center at end joints. Edge joints of wallboard face layer offset 24 inches from those of base layer. End joints centered on bottom flange of I-joists and offset a minimum of 48 inches from those of base layer. Additionally, wallboard face layer attached to base layer with 1-1/2 inch Type G drywall screws spaced 8 inches on center with a 4" stag ger, placed 6 inches from face layer end joints. inish System (not shown): Face layer joints covered with tape and coated with joint compound. Screw heads covered with joint compound. Fire Test conducted at NGC Testing Services, Inc Report No. FC-687 January 25, 2007 STC and IIC Sound Ratin isted Assembly gs for L Without Gypsum Concrete With Gypsu Concrete m Cushioned Vinyl Carpet & Pad Carpet & Pad Cushioned Vinyl STC IIC STC IIC IIC STC IIC STC - - b- - - -49 b 55 a This ass ay also be used e-rated roof/c ation, b when constru tly as describe b STC and I alues estimated by id L. Adams Ass tes, Inc. em y mbl IC v in fir a Dav eil pplicing a ocia ut lyon cte xacd e d. Copyright © 2010 American Wood Council January 2009 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES 19 WIJ-1.6 One-Hour Fire-Resistive Ceiling Assembly Floora/Ceiling - 100% Design Load - 1 Hour Rating - ASTM E 119 / NFPA 251 4 5B 2 3 5A 1. Floor Topping (optional, not shown): Gypsum concrete, lightweight or normal concrete topping. 2. Floor Sheathing: Minimum 23/32 inch thick tongue-and-groove wood sheathing (Exposure 1). Installed per code requirements with minimum 8d common nails. 3. Structural Members: Wood I-joists spaced a maximum of 24 inches on center. Minimum I-joist flange depth: 1-5/16 inches Minimum I-joist flange area: 1.95 inches2 Minimum I-joist web thickness: 3/8 inch Minimum I-joist depth: 9-1/2 inches See ASTM D 5055-07 for qualification requirements. 4. Resilient Channelsb: Minimum 0.019 inch thick galvanized steel resilient channel attached perpendicular to the bottom flange of the I-joists with one 1-1/4 inch drywall screw. Channels spaced a maximum of 16 inches on cen- ter [24 inches on center when I-joists are spaced a maximum of 16 inches on center]. 5. Gypsum Wallboard: Two layers of minimum 1/2 inch Type X gypsum wallboard attached with the long dimen- sion perpendicular to the resilient channels as follows: 5a. Wallboard Base Layer: Base layer of wallboard attached to resilient channels using 1-1/4 inch Type S dry-wall screws at 12 inches on center. 5b. Wallboard Face Layer: Face layer of wallboard attached to resilient channels through base layer using 1-5/8 inch Type S drywall screws spaced 12 inches on center. Edge joints of wallboard face layer offset 24 inches from those of base layer. Additionally, wallboard face layer attached to base layer with 1-1/2 inch Type G drywall screws spaced 8 inches on center, placed 1-1/2 inches from face layer end joints. 6. Finish System (not shown): Face layer joints covered with tape and coated with joint compound. Screw heads covered with joint compound. Fire Test conducted at National Research Council of Canada Report No. A-4440.1 June 24, 1997 STC and IIC Sound Ratings for Listed Assembly Without Gypsum Concrete With Gypsum Concrete Cushioned Vinyl Carpet & Pad Cushioned Vinyl Carpet & Pad STC IIC STC IIC STC IIC STC IIC - - 54 68 - - 58 c 55 c a This assembly may also be used in a fire-rated roof/ceiling application, but only when constructed exactly as described. b Direct attachment of gypsum wallboard in lieu of attachment to resilient channels is typically deemed acceptable. When gypsum wallboard is directly attached to the I- joists, the wallboard should be installed with long dimension perpendicular to the I-joists and sound ratings for WIJ-1.5 should be used. c STC and IIC values estimated by David L. Adams Associates, Inc Copyright © 2010 American Wood Council January 2009 20 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES WIJ-1.7 One-Hour Fire-Resistive Ceiling Assembly Floora/Ceiling - 100% Design Load - 1 Hour Rating - ASTM E 119 / NFPA 251 6B 2 4 6A 5 3 1. Floor Topping (optional, not shown): 2. Floor Sheathing: Minimum 23/32 inch thick tongue-and-groove wood sheathing (Exposure 1). Insta Gypsum concrete, lightweight or normal concrete topping. I-joists supported by the resilient channels. Min 5. imum of 16 inches on cen- 6. Type X gypsum wallboard attached with the long dimen- s yer of wallboard attached to resilient channels using 1-1/4 inch Type S dry- om -1/2 inch Type G drywall 7. ce layer joints covered with tape and coated with joint compound. Screw heads co Fire Test conducted at Na 4219.13.2 March 23, 1998 lled per code requirements with minimum 8d common nails. Insulation: Fiberglass insulation placed between3. 4. Structural Members: Wood I-joists spaced a maximum of 24 inches on center. Minimum I-joist flange depth: 1-1/2 inche imum I-joist flange area: 2.25 inchess 2 Minimum I-joist web thickn inches ess: 3/8 inch Minimum I-joist depth: 9-1/2 See ASTM D 5055-07 for qualification requirements. Resilient Channels: Minimum 0.019 inch thick galvanized steel resilient channel attached perpendicular to the bottom flange of the I-joists with one 1-1/4 inch drywall screw. Channels spaced a max ter [24 inches on center when I-joists are spaced a maximum of 16 inches on center]. Gypsum Wallboard: Two layers of minimum 1/2 inch ion perpendicular to the resilient channels as follows: 6a. Wallboard Base Layer: Base lawall screws at 12 inches on center. 6b. Wallboard Face Layer: Face layer of wallboard attached to resilient channels through base layer using 1-5/8 inch Type S drywall screws spaced 12 inches on center. Edge joints of wallboard face layer offset 24 inches frthose of base layer. Additionally, wallboard face layer attached to base layer with 1 screws spaced 8 inches on center, placed 1-1/2 inches from face layer end joints. Finish System (not shown): Favered with joint compound. tional Research Council of Canada Report No. A- STC and IIC Sound Ratings for Listed Assembly Without Gypsum Conc psum Concrrete With Gy ete Cushioned Vinyl Carpet & Pad Cushioned Vinyl Carpet & Pad STC IIC S STC IIC TC IIC STC IIC 59 50 55 68 65 51 63 65 b b b b a This assembly may also be used in a fire-rated roof/ceiling application, but only when constructed exactly as described. STC and IIC values estimated by David L. Adams Associates, Inc b Copyright © 2010 American Wood Council January 2009 FIRE-RATED WOOD-FRAME WALL AND FLOOR/CEILING ASSEMBLIES 21 WIJ-2.1 Two-Hour Fire-Resistive Ceiling Assembly Floora/Ceiling - 100% Design Load - 2 Hour Rating - ASTM E 119 / NFPA 251 2 4 6A 6B 6C3 5 1. Floor Topping (optional, not shown): Gypsum concrete, lightweight or normal concrete topping. 2. Floor Sheathing: Minimum 23/32 inch thick tongue-and-groove wood sheathing (Exposure 1) nstalled per code .25 inches2 55-07 fo 5. Furr galvaniz tached perpen- dicul ng channels spaced 16 inches on center (furring chan- 6. ists using 1-5/8 inch Type S ith joint compound. Screw d Bond Building Products Research Center December 16, 1992 . I requirements. 3. Insulation: Minimum 3-1/2 inch thick unfaced fiberglass insulation fitted between I-joists supported by stay wires spaced 12 inches on center. 4. Structural Members: Wood I-joists spaced a maximum of 24 inches on center. ge area: 2Minimum I-joist flange depth: 1-1/2 inches Minimum I-joist flan Minimum I-joist web thickness: 3/8 inch Minimum I-joist depth: 9-1/4 inches 50See ASTM D r qualification requirements. ing Channels: Minimum 0.0179 inch thick ed steel hat-shaped furring channels, at ar to I-joists using 1-5/8 inch long drywall screws. Furri nels used to support the second and third layers of gypsum wallboard). Gypsum Wallboard: Three layers of minimum 5/8 inch Type C gypsum wallboard as follows: 6a. Wallboard Base Layer: Base layer of wallboard attached to bottom flange of I-jo drywall screws at 12 inches on center with the long dimension of wallboard perpendicular to I-joist. End joints ofwallboard centered on bottom flange of the I-joist and staggered from end joints in adjacent sheets. 6b. Wallboard Middle Layer: Middle layer of wallboard attached to furring channels using 1 inch Type S dry- wall screws spaced 12 inches on center with the long dimension of wallboard perpendicular to furring channels. End joints staggered from end joints in adjacent sheets. 6c. Wallboard Face Layer: Face layer of wallboard attached to furring channels through middle layer using 1-5/8 inch Type S drywall screws spaced 8 inches on center. Edge joints of face layer of wallboard offset 24 inches from those of middle layer. End joints of face layer of wallboard staggered with respect to the middle layer. 7. Finish System (not shown): Face layer joints covered with tape and coated w heads covered with joint compound. Fire Test conducted at Gol Third Party Witness: PFS Corporation Report No: #92-56 STC and IIC Sound Ratings for Listed Assembly Without Gypsum Concrete With Gypsum Concrete Cushioned Vinyl Carpet & Pad Cushioned Vinyl Carpet & Pad S TC IIC STC IIC S TC IIC STC IIC - - 49 b 54 b 52 b 46 b 52 b 60 b a n, but only when constructed exactly as described. This assembly may also be used in a fire-rated roof/ceiling applicatio b STC and IIC values estimated by David L. Adams Associates, Inc Copyright © 2010 American Wood Council January 2009