L&S Public Safety Adenddum 01-26-11
435 Cottage Street, Suite 1, Springfield, MA 01104-4005 Phone: (413) 732-4336 / Fax: (413) 731-0786
PUBLIC SAFETY / FACILITY PLANNING
SMITH COLLEGE
Northampton, Massachusetts
ADDENDUM No 1
January 28, 2011
CHANGES TO THE DRAWINGS
Fire Protection
Drawing FP 101: DELETE: Note 2 at the existing sprinkler heads in the existing
reception area and entry hall (total of 6 heads). The
existing heads shall remain to protect the space above
the new ceiling.
Drawing FP 201: CHANGE: Drawing Note 1 to read as follows: “Connect new 1”
sprinkler to existing piping and install new concealed
pendent head as shown. Install new upright heads to
protect new ceiling space. Replace branch piping as
required.”
Drawing FP 102: DELETE: Reference to work in Rooms 208 and 209. This work
will be performed under a separate contract.
Drawing FP 202: DELETE: Work in new conference and training room. This work
will be performed under a separate contract.
Drawing FP 301: ADD: On the typical pendent heads detail ADD an upright
sprinkler head on the new branch pipe serving the new
pendent head for all new first floor pendent heads only.
Plumbing
Drawing P 101: CHANGE: Note 4 to read as follows: “Remove existing sink to
allow installation of new countertop. Re-install sink in
new countertop as required.
Page 2
HVAC
Drawing H 101: CHANGE: The make and Model of the dehumidifier to, “ Ebec
Kompact 56, with built in condensate pump, automatic defrost cycle, and moisture removal
rate of 56 pints/day.
Electrical
Drawing E 202
Admin 108: ADD: Two (2) duplex receptacles below counter for
computers. Wire both receptacles and new monitor
receptacle with 2#12, 1#12 ground in ¾” conduit to
new 20A-IPC/B in existing emergency panel ”EM2” in
basement corridor.
ADD: Two tel/data outlets below counter for computers
DELETE: Note: Extend branch circuit wiring to existing
receptacle branch circuit in Admin Room.
REMOVE: Doorbell mounted on wall and RELOCATE to new
wall in Lobby Area 100R1.
ADD: Provide two (2) security monitors and monitor desk
stands to be located on counter. Monitor shall be
AIPHONE Model JF-2MED with PS-182OUL power
supply.
Waiting Area 100R2:
ADD: Security door station on wall adjacent to door entering
Public Safety. Door station shall be AIPHONE JF-
DVF.
DELETE: Camera and keyed note 13.
REVISE: Keyed Note 9 to read: Run 2#12, 1#12 ground in ¾”
conduit to new 20 amp, single pole circuit breaker in
existing emergency panel “EM2” in basement corridor
for equipment in the communication closet.
Page 3
ADD: Keyed Note 18: Run 2#12, 1#12 ground in ¾” conduit
to new 20A-IPC/B in existing emergency panel “EM2”
in basement corridor.