055-12 53 Emerson Way duct test #230 West Pomeroy Lane
Amherst, MA 01002
Phone: 413-835-5162
Email: matt.turcotte@gmail.com
Date Of Test: 2/22/2013
Client Countryside Home Builders
Site Address: 53 Emerson Way
Northampton, MA 01062
Test Performed By: Matt Turcotte
Job #: 055-12
Type of Test Performed: Post-Construction, leakage to outside (8%)
Duct System 1
Conditioned Floor Area: 1075 sq ft
Duct Flow at 25 Pa: 62 CFM
Duct Leakage: 5.77 CFM per 100 sq ft of conditioned floor area
TEST RESULT : PASS
Duct System 2 (if applicable)
Conditioned Floor Area: 1252 sq ft
Duct Flow at 25 Pa: 71 CFM
Duct Leakage: 5.67 CFM per 100 sq ft of conditioned floor area
TEST RESULT: PASS
Notes on Area Tested and/or Testing Conditions:
2009 IECC Minimum Requirements, per Section 403.2.2
Post-Construction Test, leakage to the outdoors < 8 CFM per 100 sq ft of conditioned floor area
Post-Construction Test, total leakage < 12 CFM per 100 sq ft of conditioned floor area
Mid-Construction Test, total leakage without air handler < 4 CFM per 100 sq ft of conditioned floor area
Site Information
Duct Pressurization Test Results
Mid-Construction Test, total leakage with air handler < 6 CFM per 100 sq ft of conditioned floor area