32A-227 (10) FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the time of the inspection or test. It shall be permitted to modify this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Attach additional sheets,data,or calculations as necessary to provide a complete record. Date of this inspection or test: 10-26-2018 Time of inspection or test: 8:45 1. PROPERTY INFORMATION Name of property: COLLEGE CHURCH SCHOOL,LOGAN.KIRPATRICK Address: 48 POMEROY TERRACE NORTHAMPTON.MA 01060 Description of property: CHURCH Occupancy type: COMM Name of property representative: RICHARD Address: Phone: 559-0235 Fax: 586-0063 E-mail: Authority having jurisdiction over this property: NFD Phone: Fax: E-mail: 2. INSTALLATION,SERVICE,AND TESTING CONTRACTOR INFORMATION Service and/or testing organization for this equipment: Security&Fire Integrations LLC Address: 73 Gunn Road Southampton MA 01073 Phone: 413-203-2008 Fax: 413-203-2015 E-mail: office@securityfireintegrations.com Service technician or tester: Dave Qualifications of technician or tester: ALARM TECH A contract for test and inspection in accordance with NFPA standards is in effect as of: =018 The contract expires: 2019 Contract number: Frequency of tests and inspections: YRLY Monitoring organization for this equipment: NFD Address: Phone: Fax: E-mail: Entity to which alarms are retransmitted: NFD#0331 Phone: 3. TYPE OF SYSTEM OR SERVICE ®Fire alarm system(nonvoice) ❑Fire alarm with in-building fire emergency voice alarm communication system(EVACS) ❑Mass notification system(MNS) ❑Combination system,with the following components: ❑Fire alarm ❑EVACS ❑MNS ❑Two-way,in-building,emergency communication system ❑Other(specify): Copyright 0 2009 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution. 3. TYPE OF SYSTEM OR SERVICE (continued) NFPA 72 edition: Additional description of system(s): 3.1 Control Unit Manufacturer: SILENT KNIGHT Model number: 5820 XL 3.2 Mass Notification System ®This system does not incorporate an MNS. 3.2.1 System Type: ❑In-building MNS--combination In-building MNS--stand-alone ❑Wide-areaMNS ❑Distributed recipient MNS ❑Other(specify): 3.2.2 System Features: ❑Combination fire alarm/MNS ❑MNS ACU only ❑Wide-area MNS to regional national alerting interface ❑Local operating console(LOC) ❑Direct recipient NNS(DRMNS) ❑Wide-area MNS to DRMNS interface ❑Wide-area MNS to high-power speaker array(IIPSA)interface ❑In-building MNS to wide-area MNS interface ❑Other(specify): 3.3 System Documentation ®An owner's manual,a copy of the manufacturer's instructions,a written sequence of operation,and a copy of the record record drawings are stored on site. Location: in contra 3.4 System Software ®This system does not have alterable site-specific software. Software revision number: Software last updated on: ®A copy of the site-specific software is stored on site. Location: 3FI Office 4. SYSTEM POWER 4.1 Control Unit 4.1.1 Primary Power Input voltage of control panel: 120 Control panel amps: 15 4.1.2 Engine-Driven Generator ®This system does not have a generator. Location of generator: Location of fuel storage: Type of fuel: 4.13 Uninterruptible Power System ®This system does not have a UPS. Equipment powered by a UPS system: Location of UPS system: Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode(hours): In alarm mode(minutes): Copyright 02009 National Fire Protection Association.This form maybe copied for individual use other than for resale.It may not be copied for commercial sale or distribution. 4. SYSTEM POWER(continued) 4.1.4 Batteries Location: PANEL Type: SEALED Nominal voltage: 24 Amp/hour rating: 7 Calculated capacity of batteries to drive the system: In standby mode(hours): In alarm mode(minutes): ❑ Batteries are marked with date of manufacture. 4.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System ®This system does not have an EVACS or MNS. 4.2.1 Primary Power Input voltage of EVACS or MNS panel: EVACS or MNS panel amps: 4.2.2 Engine-Driven Generator ❑This system does not have a generator. Location of generator: Location of fuel storage: Type of fuel: 4.23 Uninterruptible Power System ❑This system does not have a UPS. Equipment powered by a UPS system: Location of UPS system: Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode(hours): In alarm mode(minutes): 4.2.4 Batteries Location: Type: Nominal voltage: Amp/hour rating: Calculated capacity of batteries to drive the system: In standby mode(hours): In alarm mode(minutes): ❑Batteries are marked with date of manufacture. 4.3 Notification Appliance Power Extender Panels This system does not have power extender panels. 4.3.1 Primary Power Input voltage of power extender panel(s): Power extender panel amps: 4.3.2 Engine-Driven Generator ❑This system does not have a generator. Location of generator: Location of fuel storage: Type of fuel: 4.33 Uninterruptible Power System ❑This system does not have a UPS. Equipment powered by a UPS system: Location of UPS system: Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode(hours): In alarm mode(minutes): Copyright®2009 National Fire Protection Association.This form maybe copied for individual use other than for resale.It may not be copied for commercial sale or distribution. 4. SYSTEM POWER(continued) 4.3.4 Batteries Location: Type: Nominal voltage: Amp/hour rating: Calculated capacity of batteries to drive the system: In standby mode(hours): In alarm mode(minutes): ❑Batteries are marked with date of manufacture. 5. ANNUNCIATORS ®This system does not have annunciators. 5.1 Location and Description of Annunciators Annunciator 1: Annunciator 2: Annunciator 3: 6. NOTIFICATIONS MADE PRIOR TO TESTING Monitoring organization Contact: NTON FD Time: 8:00 Building management Contact: Time: Building occupants Contact: Time: Authority having jurisdiction Contact: Time: Other,if required Contact: Time: 7. TESTING RESULTS 7.1 Control Unit and Related Equipment Visual Functional Description Inspection Test Comments Control unit i Lamps/LEDs/LCDs Fuses ❑ ❑ Trouble signals Disconnect switches Ground-fault monitoring ❑ ❑ Supervision ❑ ❑ Local annunciator Remote annunciators ❑ ❑ Power extender panels ❑ ❑ Isolation modules ❑ ❑ Other(specify) ❑ ❑ Copyright 0 2009 National Fire Protection Assodation.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution. 7. TESTING RESULTS (continued) 7.2 Control Unit Power Supplies Visual Functional Description Inspection Test Comments 120-volt power Generator or UPS ❑ ❑ Battery condition Load voltage ❑ ❑ Discharge test ❑ Cl Charger test ED Other(specify) ❑ ❑ 71 7.3 In-Building Fire Emergency Voice Alarm Communications Equipment Visual Functional Description Inspection Test Comments Control unit ❑ ❑ Lamps/LEDs/LCDs ❑ ❑ Fuses ❑ 1 ❑ Primary power supply ❑ 1 ❑ Secondary ower supply ❑ ❑ Trouble signals ❑ ❑ Disconnect switches ❑ ❑ Ground-fault monitoring ❑ ❑ Panel supervision Cl ❑ System performance ❑ ❑ Sound pressure levels ❑ ❑ Occupied ❑Yes ❑No Ambient dBA I Alarm dBA (attach report with locations,values, and weather conditions System intelligibility ❑ ❑ ❑CSI ❑STI (attach report with locations,values, and weather conditions Other(specify) ❑ ❑ Copyright 02009 National Fire protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution. 7. TESTING RESULTS(continued) 7.4 Notification Appliance Power Extender Panels Visual Functional Description Inspection Test Comments Lamps/LEDs/LCDs ❑ ❑ Fuses ❑ ❑ Primary power supply ❑ ❑ Secondaty power supply ❑ ❑ Trouble signals ❑ ❑ Ground-fault monitoring ❑ I ❑ Panel supervision ❑ ❑ Other(specify) ❑ ❑ 7.5 Mass Notification Equipment Visual Functional Description Inspection Test Comments Functional test ❑ ❑ Resetl ower down test ❑ ❑ Fuses ❑ ❑ Primary power supply ❑ ❑ UPS power test ❑ ❑ Trouble signals ❑ ❑ Disconnect switches ❑ ❑ Ground-fault monitoring ❑ ❑ CCU security mechanism ❑ ❑ Prerecorded message content ❑ ❑ Prerecorded message activation ❑ ❑ Software backup performed ❑ ❑ Test backup software ❑ ❑ Fire alarm to MNS interface ❑ ❑ MNS to fire alarm interface ❑ ❑ In-building MNS to wide-area ❑ ❑ MNS Copyright 0 2009 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution. 7. TESTING RESULTS (continued) 7.5 Mass Notification Equipment(continued) Visual Functional Description Inspection Test Comments MNS to direct recipient MNS ❑ ❑ Sound pressure levels ❑ ❑ Occupied ❑Yes ❑No Ambient dBA Alarm dBA (attach report with locations,values, and weather conditions System intelligibility ❑ ❑ ❑CSI ❑STI (attach report with locations,values, and weather conditions) Other(specify) ❑ ❑ 7.6 Two-Way Communications Equipment Visual Functional Description Inspection Test Comments Phone handsets ❑ ❑ Phone jacks ❑ ❑ Off-hook indicator ❑ ❑ Call-in signal ❑ ❑ System performance ❑ ❑ System audibility ❑ ❑ System intelligibility ❑ ❑ Radio communications ❑ ❑ enhancements stem Area of refuge communication ❑ ❑ system Elevator emergency ❑ ❑ communications system Other(specify) ❑ ❑ Copyright®2009 National Fire protection Association.This form maybe copied for individual use other than for resale.It may not be copied for commercial sale or distribution. 7. TESTING RESULTS(continued) 7.11 Auxiliary Functions Visual Functional Description Inspection Test Comments Door-releasing devices ❑ ❑ Fan shutdown ❑ ❑ Smoke management/smoke control ❑ ❑ Smoke damper operation ❑ ❑ Smoke shutter release ❑ ❑ Door unlocking ❑ ❑ Elevator recall ❑ ❑ Elevator shunt trip ❑ ❑ MNS override of FA signals ❑ ❑ Other(specify) ❑ ❑ 7.12 Alarm Initiating Device ® Device test results sheet attached listing all devices tested and the results of the testing 7.13 Supervisory Alarm Initiating Device ❑ Device test results sheet attached listing all devices tested and the results of the testing 7.14 Alarm Notification Appliances ❑ Appliance test results sheet attached listing all appliances tested and the results of the testing 7.15 Supervisory Station Monitoring Description Yes No Time Comments Alarm signal ® ❑ Alarm restoration ® ❑ Trouble signal ❑ ❑ Trouble restoration ❑ ❑ Supervisory signal ❑ ❑ Supervisory restoration ❑ ❑ P %2. v=ia. -14.6.2 4 (c. 9 ci'i'.. Copyright®2009 National Fire Protection Association.This form maybe copied for individual use other than for resale.It may not be copied for commercial sale or distribution. 7. TESTING RESULTS (continued) 7.11 Auxiliary Functions Visual Functional Description Inspection Test Comments Door-releasing devices ❑ ❑ Fan shutdown ❑ ❑ Smoke management/smoke control ❑ ❑ Smoke damper operation ❑ ❑ Smoke shutter release ❑ ❑ Door unlocking ❑ ❑ Elevator recall ❑ ❑ Elevator shunt trip ❑ ❑ MNS override of FA signals ❑ ❑ Other(specify) ❑ ❑ 7.12 Alarm Initiating Device ® Device test results sheet attached listing all devices tested and the results of the testing 7.13 Supervisory Alarm Initiating Device ❑ Device test results sheet attached listing all devices tested and the results of the testing 7.14 Alarm Notification Appliances ❑ Appliance test results sheet attached listing all appliances tested and the results of the testing 7.15 Supervisory Station Monitoring Description Yes No Time Comments Alarm signal ® ❑ Alarm restoration ® ❑ Trouble signal ❑ ❑ Trouble restoration ❑ ❑ Supervisory signal ❑ ❑ Supervisory restoration ❑ ❑ �e _ �;a Copyright 0 2009 National Fire Protection Association.This form maybe copied for individual use other than for resale.It may not be copied for commercial sale or distribution. 8. NOTIFICATIONS THAT TESTING IS COMPLETE Monitoring organization Contact: NTON FD Time: 11:30 Building management Contact: Ken Strong Time: 11:30 Building occupants Contact: Time: Authority having jurisdiction Contact: Time: Other,if required Contact: Time: 9. SYSTEM RESTORED TO NORMAL OPERATION Date: 10-26-2018 Time: 11:30 10. CERTIFICATION 10.1 Inspector Certification: This system,as specified herein,has been inspected and tested according to all NFPA standards cited herein. Signed: Dave P SIG ON FILE Printed name: Dave P Date: 10-26-2018 Organization: SFI LLC Title: ALARM TECH Phone: 413-203-2008 10.2 Acceptance by Owner or Owner's Representative: The undersigned has a service contract for this system in effect as of the date shown below. Signed: Printed name: Date: Organization: Title: Phone: Copyright 0 2009 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution. J DEVICE TEST RESULTS (Attach additional sheets if required) Device Type Address Location Test Results SCHOOL-REPLACED In control 2-12 Volt DC BATTERY HEATS ELEC BACK&ENTR CK HORN ELEC HALL CK HEAT AT FIRE PANEL CK BELL&DIALER ( AT PANEL f CK HORN HALL BY DOOR 10 CK PULL HALL BY DOOR 10 CK HEATS 19A FRONT&BACK I CK PULL&HORN BY RM 23&24 CK HEAT BOILER RM CK FRONT/BACK Smoke Acclimates Thru out building CK clean LOGAN-SK 5208 PANEL PULL HALL, 1ST LEFT, 1ST CK RIGHT BATTERYS CHARGING 27.31 KIRKPATRICK ZONE 1 IST FL&BASE CK ZONE 2 2ND FL SMOKES CK ZONE 3 PULL STATIONS CK ZONE 4 GARAGE HEATS I CK BATTERYS CHARGING 27.24 Copydght 0 2009 National Fire Protection Association.This form may be copied for individual use other than for resale.it may not be copied for commercial sale or distribution.