23A-291 (10) 190 NONOT[ICK ST-NTON VET CLINIC BP-2017-0173
GIS#; COMMONWEALTH OF MASSACHUSETTS
Mao-Block: 23A-291 CITY OF NORTHAMPTON
Lot:-60_0
Permit: Building BUILDING PERMIT
Care ryB
:renovation UILDING 1 RMI T
Permit y BP-2017-0173
Project# JS-2017-000284
Est.Cost:$219000.00
Fee: $1533.00 PERMISSION IS HEREBY GRANTED TO:
Const. Class: Contractor: License:
lyse Group MARK SARAFIN 053434
Lot Size(sq.ft.i Owner: NORTHAMPTON VETERINARY CLINIC REAL ESTATE TRUST LLC
Zoning:G1(100)/ Applicant: MARK SARAFIN
AT: 190 NONOTUCK ST - N'TON VET CLINIC
Applicant Address: Phone: Insurance:
42 Pomeroy Meadow Road (413) 527-7812 Workers
Compensation
SOUTHAMPTONMA01073 ISSUED ON:8/29/2016 0:00:00
TO PERFORM THE FOLLOWING WORK: REMODEL & RECONFIGURE SPACE
POST THIS CARD SO IT IS VISIBLE FROM THE STREET
Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector
Underground: Service: Meter:
Footings:
Rough: Rough: House# Foundation:
Driveway Final:
Final: Final:
Rough Frame:
Gas: Fire Department Fireplace/Chimney:
Rough: Oil: Insulation:
Final: Smoke: Final:
THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF
ANY OF ITS RULES AND REGULATIONS.
Certificate of Occupancy signature: FeeTYpe:
Date Paid: Amount:
Building 8129.,20160:00:00 51533.00
212 Main Street, Phone(413)587-1240 Fax: (413)587-1272
Louis Hasbrouck-Building Commissioner
File(1 BP-2017-0173
APPLICANT/CONTACT PERSON MARK SARAFIN
ADDRESS/PHONE 42 Pomeroy Meadow Road SOUTHAMPTON01073 (413)5'27-7812
PROPERTY LOCATION 190 NONOTUCK ST-N'TON VET CLINIC
MAP 23A PARCEL 291 000 ZONE GI(100V
THIS SECTION FOR OFFICIAL USE ONLY:
PERMIT APPLICATION CHECKLIST
ENCLOSED REQUIRED DATE
ZONING FORM FILLED OUT �/y ��/�
Fee Paid /O�f&g Sr3J, 33
Buildinp Permit Filled out
Fge Paid
TvpeofConstructionJIEMODEL&.RECONFIGURE SPACE
New Constructipn
Non Structural interior renovations
Addition to Existing
_ Accessory Structure
Building Plans Included:
Owner/Statement or License 053- 434 C _F.--, Q
3 sets of Plans/Plot Plan 1c G leamiC Y Aid
THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON
INFO ATION PRESENTED:
Approved Additional permits required(see below)
PLANNING BOARD PERMIT REQUIRED UNDER:§
Intermediate Project: Site Plan AND/OR Special Permit With Site Plan
Major Project: Site Plan AND/OR Special Permit With Site Plan
ZONING BOARD PERMIT REQUIRED UNDER: §_
Finding Special Permit Variance*
Received&Recorded at Registry of Deeds Proof Enclosed
Other Permits Required:
Curb Cut from DPW Water Availability Sewer Availability
Septic Approval Board of Health Well Water Potability Board of Health
Permit from Conservation Commission Permit from CB Architecture Committee
Permit from Elm Street Commission Permit DPW Storm Water Management
! molition De sy
,tom' /(
Signature of Bui .im'T"tial Date
Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning
requirements and obtain all required permits from Board of Health,Conservation Commission,Department
of public works and other applicable permit granting authorities.
Variances are granted only to those applicants who meet the strict standards of MGL.40A. Contact Office of
Planning&Development for more intormation.
Versfon1 7 Commercial Boldin_Permit May 15,2000
Department use only
RF City of Northampton Status of Permit
C�• .co Mg Department Curb Cut:Driveway Permit
AUG
. 2 Main Street Sewer/Septic Availabiltty
" s 9 'lQj Room 100 Water/Well Availability
o ampton, MA 01060 Two Sets of Structural Plans
Ar oF.at
Ar 'unrraG. • one '13 .87-1240 Fax 413-587-1272 Plot/Site Plans
a*un tone
Other Specify
APPLICATION TO CONSTRR1,REPAIR,RENOVATE,CHANGE THE USE OR OCCUPANCY OF,OR DEMOLISH ANY BUILDING
OTHER THAN A ONE OR TWO FAMILY DWELLING
SECTION 1 -SITE INFORMATION 1
1.1 Pro a��ddress,'1y'{1+ 1 This section to be completed by office
f `I ock 5�-K1 r2 .. Map Lot Unit
'reyiIIP1( Q 1 'G' 0\CAD-V Zone Overlay District
-- - -- -- - Elm St District CB District
SECTION 2-PROPERTY OWNERSHIP/AUTHORIZED AGENT
3.1 ner of Record: j`[
o2 law p/Eon Ve C�ks IC PEA cJin L---1 Q� fl
d+ Name(Print) (ICM1t/ 5W thhy Current Mailing Address
>r 1.
Signature .i.701 Telephone
2.2 Authorized Agent:
INVA4L 12,/y6,,,4(24Fi 98 -am.7<,.f bnye,S., 2crcP
,
Name{Pdnt} � �-(V4 tweet04 Atltlress `
Signature r Telephone 44 R- ca 4_ -3_911
- "3-911 a
SECTION 3-ESTIMATED CONSTRUCTION COSTS
Item Estimated Cost(Dollars)to be Official Use Only
completed by permit applicant
I. Buildinghet, (a) Building Permit Fee
no 0
2. Electrical '2 - . ! (b}Estimated Total Cost of
6O b0�.'1. Construction from(6)
3, Plumbing ,„»)O T DaG .moi Building Permit Fee
5. Total rotectt {HVA£) Q
4 Mechanical + '/�7 //f}/---(��
Protection * t � _ _ .
!� • 2+3+4+5) a 00 , GQ Check Numbel'� jV—
s../ ,/JI` his Section For Official Use Only
Building Permit Number Date
Issued
Signature:
I
Building Commissioner/Inspector of Buildings Date
Versionl.7 Conuncrcial Building Permit May 15, 2000
SECTION 4-CONSTRUCTION SERVICES FOR PROJECTS LESS THAN 35,000
CUBIC FEET OF ENCLOSED SPACE
Interior Alterations g Existing Wall Signs 0 Demolition^ Repairs 0 Additions 0 Accessory Building
Exterior Alteration 0 Existing Ground Sign 0 New Signs 0 Roofing❑ Change of Use Other (1
Brief Description Enter' a brief description here. 2eµtp�_', e, m4 ` 5 'CC Qe-('o.,}19,,.Q,p
Of Proposed Work:
Leto '-I�rA.1 Q6670 Ot _:5QuCEU� .
SECTION 5-USE GROUP AND CONSTRUCTION TYPE
USE GROUP(Check as applicable) CONSTRUCTION TYPE
A Assembly ❑ A-1 0 A-2 0 A-3 0 1A ❑
A-4 0 A-5 0 1B ❑
B Business 2A 0
E Educational ❑ 2B 0
F Factory ❑ F-1 ❑ F-2 ❑ 2C ❑
H High Hazard 0 3A j ❑
I Institutional 0 I-1 0 I-2 ❑ 1-3 ❑ 3B
M Mercantile 0 4 0
R Residential 0 R-1 0 R-2 0 R-3 0 5A 0
S Storage 0 5-1 0 S-2 0 5B ❑
U Utility ❑ Specify:
M Mixed Use 0 Specify -.... _
S Special Use ❑ Specify. - -
COMPLETE THIS SECTION IF EXISTING BUILDING UNDERGOING RENOVATIONS,ADDITIONS AND/OR CHANGE IN USE
Existing Use Group: _ _: Proposed Use Group:
Existing Hazard Index 780 CMR 34): Proposed Hazard Index 780 CMR 34): •
SECTION 6 BUILDING HEIGHT AND AREA
BUILDING AREA EXISTING PROPOSED NEW CONSTRUCTION OFFICE USE ONLY
Floor Area per Floor(sf)
111 92)4-101st
. ... _ 2n°
3° 3m _._- .. .._ ..
.. . . CN .... _
41h
Total Area(sf) Total Proposed New Construction(sf)
Total Height(ft)
Total Height ft _.. __...
7.Water Supply(M.G.L.c.40,§54) 7.1 Flood Zone Information: 7.3 Sewage Disposal System:
Public lla' Prorate El Zone Outside Flood Zone Municipal On site disposal system
Version!.?Commercial Building Permit May 15,7000
8. NORTHAMPTON ZONING
Existing Proposed Required by Zoning
This column to be filled in by
Building Depzmnen(
Lot Size
Frontage
Setbacks Front
Side L R _ L
R
Rear
Building Height
Bldg Square Footage
Open Space Footage
(Lot area minus bldg&paved
parking)
#of Parking Spaces
(volume&Location)
A. Has a Special Permit/Variance/Finding ever been issued for/on the site?
NO Q DONT KNOW in YES Q
IF YES, date issued:
IF YES: Was the permit recorded at the Registry of Deeds?
NO Q DON'T KNOW Q YES Q
IF YES: enter Book Page and/or Document 8
B. Does the site contain a brook, body of water or wettands? NO Q DONT KNOW A YES Q
IF YES, has a permit been or need to be obtained from the Conservation Commission?
Needs to be obtained Q Obtained Q , Date Issued:
C. Do any signs exist on the property? YES Q NO Q
IF YES, describe size, type and location:
D. Are there any proposed changes to or additions of signs intended for the property? YES V NO Q
tF YES, describe size, type and location:
E. Will the construction activity disturb(clearing,grading,excavation,or filling)over 1 acre or is it part of a common plan
Mat will disturb overt acre? YES Q NO vr4
IF YES,then a Northampton Storm Water Management Permit from the DPW is required.
Va.sion1.7 Commercial Sutldtng Penna May 5,2000
SECTION 9-PROFESSIONAL DESIGN AND CONSTRUCTION SERVICES-FOR BUILDINGS AND STRUCTURES SUBJECT TO
CONSTRUCTION CONTROL PURSUANT TO 760 CMR 116(CONTAINING MORE THAN 38,000 C.F.OF ENCLOSED SPACE)
9.11 Registered Architect:
_ Not Applicable 0
Name(Registrant) /VIA, 8�3
55-
Cretan Number/G!(7�JNG^1 /FW\ n RegisCe 13l201
1D/address
..
Expiration Date
Signature Telephone
9.2 Registered Professional Engineer(s):
Name Area of Responsiblity
Address Registration Number
-.n..
Signature Telephone Expiration Gate
Name Area of Responsibility
Address Registration Number
Signature Telephone Expiration Date
Name Area of Responsibility
Address Reg station Number
Signature Telephone Expiration Date
Name Area of ResponsibiIity
Address _ _.. Regslrafion Number .. ..
Signature Telephone Expiration 0ata
9.3{G'eneral Contractor
y 0-47, 4 (�Fly WC. tn'S Not Applicable 0 ..—
Company Name:
Re�sJponSbie InnCharge of Construct= i, {
-{a Pim w Y11�ah.., s iNG\+'�Q '\O '1 vv‘
Address f \ The>
4(3-la ?-191,
{
(3 sa ?-191-
' Signature Telephone
•
Version1.7 Commercial Building Permit May IS,2000
1 SECTION 10-STRUCTURAL PEER REVIEW(780 CMR 110.11)
Independent Structural Engineering Structural Peer Review Required Yes 0 No 0
SECTION 11 -OWNER AUTHORIZATION-TO BE COMPLETED WHEN ------_
OWNERS`AGENTA .. OR CONTRACTOR APPLIES FOR BUILDING PERMIT
I, C.Sy,_uiiPt,�tn�yu.l tt(K ( ,as Owner of the subject property
hereby authorize Mark- Sat€46 vl :.....� _.. . to
- 51 t o ore Ohalff, n ail matters relative to work authorized bythis beading permit application
9pp
0 �..._..... _...... Date
Y'Vsc q V 51.442 wait':a.by _ _ ,as Owner/Authorized
Agent hereby declare that the statements and information on the foregoing application are true and accurate,to the best of my knowledge
and belief.
Signed nunder the pains and penalties of perjury._
1/4
Print Name , p _.
Signature of Owner/Agent Dam
SECTION 12-CONSTRUCTION SERVICES
10.1 Licensed Construction Supervisor: Not Applicable ❑
Name of License Heider V‘AsAksit. ._ yWfGviF 4S— Oc3'-13'
•• 111 ii��
NAA
V(i (\�� {' y1,1t� ,{� License�N(umberO
i'*'inEq � `-OC& c�CZACibt ✓1, rima. '1^a 2,— 01-4— ..._
Address CA -9-? Expiration Date
1.i_ � `o3-5-a 4 .3973
Signature Telephone
SECTION 13-WORKERS'COMPENSATION INSURANCE AFFIDAVIT(M,G,L.c. 162,§25C(6))
Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result
in the denial of the issuance of the building permit.
Signed Affidavit Attached Yes at, No 0
The Commonwealth ofAfassachusetts i
—_.....=: Department of Industrial Accidents
-� - Office of Investigations
'.,
600 Washington Sheet
Boston,MA 02.111
wn'w.mass.gov/dia
Workers' Compensation Insurance_Affidavit: Builders/Contractors/Electricians/Plumbers
Applicant Information ',� ,t Please Print Legibly
Name (Business/O+ganizat�i000ivindividual): yy\W✓a,(}k �/v}hy.`�v{t.�)n _
Address: c'r IX i a.ti.-�,i� l eow(yo�.,.,, `corn C..%
_ City/State/Zip: 5` VVis O',a' Phone#: '-1 ti-Ai d - i3 ti
Are you an employer? Check the appropriate box: Type of project(required):
1.( jarn a employer with oa _ q. 0 I am a general contractor and 1 —
employees(full and/or part-time).* have Aired the sub-contractors6. _ New construction
2.0 t am a sole proprietor or partner- listed on the attached sheet, 7. 0 Remodeling
ship and have no employees These sub-contractors have 8. U Demolition
workin for me in any capacity. employees and have workers'
g P e = 9. 0 Building addition
[No workers' comp.insurance comp. insuran.;e.
required.] 5. 0 We are a corporation and its 10.0 Electrical repairs or additions
'] I am a homeowner doing all work officers have exercised their I I.J Plumbing repairs or additions •
myself. o workers' right of exemption per MCL
[N comp. 12.0 Roof repairs
insurance required.]r c. I52,§/(4),and we have no
employees. rNo workers' 13.�,Other Tv) eKe4 leA + to^S
comp. insurance required.]
"Any applicant that checks box 51 must also fill out the section below showing their workers'compensation policy information.
Homeowners who submit this affidavit indicating they are doing all work and than hire outside contractors must submita new affidavit indicating such.
:Contractors that check this box must attached an additional sheet showing the name of the sub-contactors and state whether or not those entities have
employees. If the sb-contactors have employees,they must provide their workers'camp.policy number.
I am an employer that is providing workers'compensation insurance for my employees. Below is the policy and job site
information. /�
Insurance Company Name: f- -t W\ (I✓� vcq,,, � _ „_
Policy.or Self-ins.Lie.#: t) ts1C - ((')�} - (,p0"Aq Expiration Date: LO-
lob Site Address: t-{O 'imp LtL 5.4 ere Q,}.- City/State/Zip: , lWL' nrnl7kin ✓ ..-
Attach a copy of the workers' compensation policy declaration page(showing the policy number and expiration date).
Failure to secure coverage as required under Section 25A ofMGL c. 152 can lead to the imposition of criminal penalties of a
fine up to$1,500.00 and/or one-year imprisonment,as well as civil penalties in the farm of a STOP WORK ORDER and a fine
of up to$250.00 a day against the violator. Be advised that a copy of this statement may be forwarded to the Office of
Investigations of the DIA for insurance coverage ver' nation
I do here( t cent e• hep a_',f�Jenaltie that the information provided abate is true and correct
Sj rature: 2_/ -<t .Date'_.. g 8- aot (O
Phone N: LI/3 -' 1r� /=T$i
Official use only. Do not trite in this area,to be completed by city or town official
City or Town: Permit/License#
Issuing Authority(circle one):
1.Board of Health 2.Building Department 3.City/Town Clerk 4.Electrical Inspector 5. Plumbing Inspector
6.Other
Contact Person: Phone b:
City of Northampton 212 Main Street, Northampton, NLA 01060
Solid Waste Disposal Affidavit
In accordance of the provisions of MGL c 40, 554, I acknowledge that as
a condition of the building permit all debris resulting from the construction
activity governed by this Building Permit shall be disposed of in a properly
licensed solid waste disposal facility, as defined by MGL c 111, S 150A.
Address of the work: t(10 ✓\ono \.,c \c, 5a . - -t \-
The debris will be transported by: -t
The debris will be received by: Ucct&t QrNcl, r
`
Building permit number:
Name of Permit Applicant OA k 5 uv4Fi-i
Date Signature of Permit Applicant
Initial Construction Control Document
Tg rY To be submitted with the building permit application by a
_ j Registered Design Professional
for work per the 8t11 edition of the
Massachusetts State Building Code, 780 CMR, Section 107
Project Title: Renovations for Northampton Veterinary Clinic Date: 29 July,2016
Property Address: 190 Nonotuck Street,Florence,MA 01062
Project: Check(x)one or both as applicable: New construction X Existing Construction
Project description: Demolition in preparation for limited interior renovations
I Richard E.Katsanos MA Registration Number:8355 Expiration date:08/31/2016 ,am a registered design
professional, and I have prepared or directly supervised the preparation of all design plans, computations and
specifications concerning`:
Arch iteetura I Structural Mechanical
Fire Protection Electrical X Other: demolition
for the above named project and that to the best of my knowledge,information,and belief such plans,computations and
specifications meet the applicable provisions of the Massachusetts State Building Code, (780 CMR), and accepted
engineering practices for the proposed project. I understand and agree that I(or my designee)shall perform the necessary
professional services and be present on the construction site on a regular and periodic basis to:
I. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the
contractor in accordance with the requirements of the construction documents.
2. Perform the duties fur registered design professionals in 780 CMR Chapter 17,as applicable.
3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and
quality of the work and to determine if the work is being performed in a manner consistent with the approved
construction documents and this code.
Nothing in this document relieves the contractor of its responsibility regarding the provisions of 780 CMR 107.
When required by the building official, I shall submit fietdtprogress reports(see item 3.)together with pertinent
comments, in a form acceptable to.the building official.
Upon completion of the work, I shalt submit to the building official a'Final Construction Control Docume��.ni,
Enter m the space to the right a"wet"or 5` ,p.T`r'A4'0
electronic signature and seal: jj. ><:• in ygs5`S
� H rtr
, P i
3 4 4
Phone number: 413-585-1512 Email: Richard,Katsanos@liAlArehitecdure,com 4104AR Illll/
4Rrtht
WI
f
TS
Building Official Use Onh r
Building Official Name: Permit No.: Date
Note I.indicate with an•x'project design plans.computations and specifications that you prepared or directly'tapas:ised.II'other Is chosen.
provide a description.
Version 06_11. 2013
Existing Conditions Evaluation Report
Massachusetts Building Code 780 CMR 8th Edition
International Existing Building Code 2009
Renovations for
Northampton Veterinary Clinic
190 Nonotuck Street
Florence, Massachusetts 01062
July 29, 2016
,max ,5AN03
%6 ,0'
¢,rf✓rr-krriV+11, ;
As prepared by
Richard E. Katsanos, AIA, Principal
HI Al Architecture
,4(w tl cxn,:c.'lir A Ummp6m. tllapxa II; ,-I'+i_ t R i .'.,;; _t i.iahv. tir _om
Massachusetts Building Code 780 CMR 8th Edition
International Existing Building Code 2009
Renovations for
Northampton Veterinary Clinic
190 Nonotuck Street
Florence, Massachusetts 01062
Purpose
This Report is in conformance with Massachusetts Building Code 780
CMR 8th Edition and the International Existing Building Code 2009
regarding alterations to an existing building located at 190 Nonotuck
Street, Florence, Massachusetts.
Visual Observation Only
The extent of this review is limited to visual inspection of existing facilities
and/or as-built documentation only, No destructive testing was performed
as part of this analysis.
Project Description
The project consists of an interior renovation of approximately 4,296
square feet of existing interior space. The majority of existing spaces shall
remain with finishes upgrades. Approximately 25% of the floor space shall
be reconfigured with a new layout.
Grade level access is provided via the main entrance doors and vestibule.
Two additional means of egress serve the suite, one leading directly to the
exterior and one leading to an existing common egress access corridor
shared with other tenant spaces.
All new work within the suite shall be accessible in compliance with AAB,
„u,,111 .tleCt,'+111tt' \o§rtiokiiipton. vivrono !r. .1H? to a c ,- ..t.co,dar,d :\ ktun
GENERAL EXISTING PROPERTY INFORMATION
A. PROPERTY NAME:
Florence Medical Center
B. ADDRESS:
190 Nonotuck Street, Florence, Massachusetts 01062
C. BUILDING USE:
The building was originally constructed as, and is currently used for B
(Business) occupancy.
D. BUILDING USE GROUP:
B- Business (Business) as defined by the Massachusetts Building Code,
780 CMR 8"h Edition.
E. CONSTRUCTION CLASSIFICATION:
Type 3B
Foundation: concrete slab on grade
Exterior Walls: split face CMU masonry
Int, Load Bearing: CMU
Roof: flat membrane roofing on steel framing and deck
F. HAZARD INDEX:
Existing and proposed Hazard Index is 4 as defined by the Massachusetts
Building Code, 780 CMR, 8th Edition (IEBC Table 912.4)
�. otlu 4 ,rl.5,I,t, 1.1 „ptnt4V 9r„n d1= . .�❑ td..❑ .,S,y. { ,a- h: ,,_ .,.,.,
CLASSIFICATION OF WORK
The proposed project work area is classified as Alteration - Level 2 per
IEBC Section 404 and therefore complies with the provisions of Chapter 6
and Chapter 7 for the following reasons:
- The project is not a repair, therefore IEBC Section 402 does not apply
- The project exceeds the limitations defined under Level 1 Alterations
as specified in IEBC Section 403:
Level 1 alterations include the removal and replacement or the
covering of existing materials, elements, equipment, or fixtures
using new materials, elements, equipment, or fixtures that solve the
same purpose.
- The project meets the limitations defined under Level 2 Alterations as
specified in IEBC Section 404:
Level 2 alterations include the reconfiguration of space, the addition
or elimination of any door or window, the reconfiguration or
extension of any system, or the installation of any additional
equipment.
- The project is below the threshold triggering Level 3 Alterations as
specified in IEBC Section 404:
Level 3 alterations apply where the work area exceeds 50 percent
of the aggregate area of the building.
- The project does not involve a change of occupancy, therefore IEBC
Section 406 does not apply.
- The project does not involve an addition, therefore IEBC Section 407
does not apply.
- The project does not impact the exterior or substantial interior
configuration of a historic building, therefore IEBC Section 408 does
not apply.
- The project does not involve a relocated building, therefore IEBC
Section 409 does not apply.
,Ir. Suite I. A 1cn�,L.:.. AIAwool) AI}. r:_ fid, lI „'^A': .,,LLrr.kit,4c.,,,-u
ALTERATIONS LEVEL 2
Section 701 General
This project work area will comply with all requirements for Alteration
Level 1 as specified in Chapter 6 and all requirements of Level 2 as
specified in Chapter 7. No portion of the proposed project work area
alters the existing conditions such that the building will become less safe
than its existing condition. Requirements regarding flood hazard areas
are not applicable to this project
Section 702 Special Use and Occupancy
Not applicable.
Section 703 Building Elements and Materials
703.2 Vertical Openings
No new or existing vertical floor openings are within the project work area.
703.3 Smoke barriers
This section applies to I-2 occupancies and therefore does not apply to
this project.
703.4 Interior finishes
All new interior finishes, including wall, ceiling, floor, and trim materials to
be installed under this project work area will comply with Massachusetts
Building Code 780 CMR 8th Edition.
703.5 Guards
The existing rear exit is not code compliant in that there is a step down at
the threshold and the exterior landing and steps are not dimensionally
correct, nor is there a railing or guard. This will be corrected under this
project.
Section 704 Fire Protection
704.2 Automatic sprinkler systems
„t
i.qrric 5,,,t,I,v.r1< „}«.,,.'Il 4o- ;=r t,,,,ti , t�r_,r.
nta
704.3 Standpipes
nta
704.4 Fire alarm and detection
A fire alarm system (Notifier brand), consisting of horntstrobe units, smoke
detectors and manual pull stations, compliant with the International Fire
Code, exists within this suite Notification consists of horn and strobe
devices. The project will modify this fire alarm system.
Section 705 Means of Egress
The existing and new egress requirements within the project work area
are compliant with Massachusetts Building Code 780 CMR 8th Edition and
NFPA Life Safety Code 101.
705.3 Number of Exits:
Unchanged. Three exists serve the suite,
705.4.1 Egress doorways —two egress doorways required
Unchanged. Three egress doors serve the suite—two direct exits to the
exterior and on to an existing common egress access corridor serving
multiple tenants.
705.4.2 Egress doorways -door swing
Based on occupant load, the exit doors do not need to swing in the
direction of travel. Existing doors at the main entrance and vestibule and
the rear exit swing in the direction of travel, while the door leading to the
common exit access corridor swing into the suite.
705.4.3 Egress doorways - door closing
Existing doors at the main entrance and vestibule, the rear exit and the
door leading to the common exit access corridor each have a door closer.
705.4.4 Panic hardware
nta—calculated occupancy below 49 occupants
nit.,[duvt.bnik I. North uiplm, \OHNO Ln
705.5 Openings in corridor walls
Corridors in this occupancy are not required to be rated.
705.6 Dead end corridors
There are no dead end corridors within the project work area.
705.7 means of egress lighting
Egress lighting consists of battery pack emergency light units. Existing
and new units shall be located as required by code.
705.8 Exit signs
Existing compliant fixtures remain unchanged. Several new internally
illuminated exit signs shall be installed as part of this project indicating
egress.
705.9 Handrails
Rear exit steps shall have code compliant handrails.
705.10 Guards
Rear exit steps shall have code compliant guards.
Section 706 Accessibility
In accordance with Massachusetts Architectural Access Board 521 CMR,
because the project construction cost exceeds $100,000.00 but is less
than 30% of the replacement cost for the entire building, all new work
within the project work area is required to conform to the requirements of
Massachusetts Building Code 780 CMR 8th Edition Section 605 and 706
and Massachusetts Architectural Access Board 521 CMR.
All newly built components of the project shall be in compliance with
Massachusetts Building Code 780 CMR 8th Edition Section 605 and 706
Massachusetts Architectural Access Board 521 CMR.
el Gotl, 9r,•o�Sua:1. . rf6x,pb ,.A IA(Sitio 1[I '.FI] tavif „-Kh t ..:hma n . .,
Section 707 Structural
The scope of this project work area does not affect any existing structural
systems, nor does it affect applied loads on existing structural systems.
Section 708 Electrical
708.1 New Installations
Convenience outlet wiring, lighting, and data wiring are included in the
project and shall comply with the requirements of the Massachusetts
Electrical Code.
708.2 Existing Installations
B-Business occupancy does not apply
708.3 Residential occupancies
B-Business occupancy does not apply
Section 709 Mechanical
709.1 Reconfigured or converted spaces
Existing HVAC ductwork and diffusers shall be relocated and rebalanced
at renovated areas to provide mechanical ventilation to all spaces within
the project area.
709.2 Altered existing systems
The existing and modified HVAC system shall provide at least the code
minimum 5 CFM per occupant (215 CFM) of outside air and 15 CFM per
occupant (645 CFM) of ventilation air.
709.3 Local exhaust
A new anesthesia scavenging system serving the animal operating room
shall be directly vented to the building exterior.
suit.. vn ' t.o.
Section 710 Plumbing
710.1 Minimum fixtures
Because the occupant bad of the project work area story shall not be
increased more than 20 percent, existing plumbing fixture quantities are
not required to be modified.
Section 711 Energy Conservation
711.1 Minimum requirements
Level 2 Alterations to existing buildings or structures are permitted without
requiring the entire building or structure to comply with the energy
requirements of the international Energy Conservation Code or
international Residential Code.
Areas of major reconfiguration shall have a new code compliant thermal
envelope constructed at the roof level, to replace the existing thermal
insulation laying directly on the suspended acoustic ceiling system. This
area shall be separated from other above ceiling areas where the thermal
insulation lays directly on the suspended acoustic ceiling system and shall
remain.
END OF EXISTING CONDITIONS REVIEW REPORT
=+4 Gwl _, rt,SuhrLA t.. n b.n, ti\ T : 4 IT 1 mt. i -{_ m, vm
{ Initial Construction Control Document
I To be submitted with the building permit application by a
s 1 111 Registered Design Professional
• for work per the 8th edition of the
Massachusetts State Building Code, 780 CMR, Section 107
Project Title: Renovations for Northampton Veterinary Clinic Date: 18 August,2016
Property Address: 190 Nonotack Street,Florence,MA 01062
Project: Check(x)one or both as applicable: New construction X Existing Construction
Project description: Limited interior renovations
I Richard E. Katsanos MA Registration Number: 8355 Expiration date: 08/31/2017 . am a registered design
professional, and 1 have prepared or directly supervised the preparation of all design plans,computations and
specifications concerning':
X Architectural Structural Mechanical
Fire Protection Electrical Other:
for the above named project and that to the best of my knowledge, information,and belief such plans,computations and
specifications meet the applicable provisions of the Massachusetts State Building Code, (780 CMR), and accepted
engineering practices for the proposed project. I understand and agree that I(or my designee)shall perform the necessary
professional services and be present on the construction site on a regular and periodic basis to:
I. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the
contractor in accordance with the requirements of the construction documents_
2. Perform the duties for registered design professionals in 780 CMR Chapter 17,as applicable.
3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and
quality of the work and to determine if the work is being performed in a manner consistent with the approved
construction documents and this code.
Nothing in this document relieves the contractor of its responsibility regarding the provisions of 780 CMR 107.
When required by the building official, I shall submit field/progress reports (see item 3.)together with pertinent
comments, in a form acceptable to the building official.
Upon completion of the work, I shall submit to the building official a 'Final Construction Control Document'.
Enter in the space to the right a"wet"or aNtteci
electronic signature and seal: oisrzan.,�a�®e nyaan„a Erc„:���� �o SPry o9 m
Richard E. ON.cn=alann,d E.Xa„xnoe,o
AtChtte(141!0.CU. aw y
el�aim.,mxanano,� nin,mwa w ,vyo i'tl9
Katsanos o.,e,o,b.ne,a,,15.44.54-04'00'
Phone number:413-585-1512 Email:Richard.Katsanos@HA[Architecture.com
3
�MMr tt. .
Building Official Use Only
Building Official Name: Permit No.: Date:
Note 1.Indicate with an'x'project design plans,computations and specifications that you prepared or directly supervised_ If'other' is chosen,
provide a description.
Version 06_11_2013
Existing Conditions Evaluation Report
Massachusetts Building Code 780 CMR 8th Edition
International Existing Building Code 2009
Renovations for
Northampton Veterinary Clinic
190 Nonotuck Street
Florence, Massachusetts 01062
August 18, 2016
Q�NttEcr
R
5
h rP 4Ay 1�
�4
it
Richard
Katsa nos A,chlee wecrync 20 60a„rr ,
As prepared by
Richard E. Katsanos, AtA, Principal
H I Al Architecture
nAt ti a-I.',mitt ! ANEI ttit \IV11 . 5.I I_ lav41 4 — _ rdr, tm..en.0
Massachusetts Building Code 780 CMR 8th Edition
International Existing Building Code 2009
Renovations for
Northampton Veterinary Clinic
190 Nonotuck Street
Florence, Massachusetts 01062
Purpose
This Report is in conformance with Massachusetts Building Code 780
CMR 8th Edition and the International Existing Building Code 2009
regarding alterations to an existing building located at 190 Nonotuck
Street, Florence, Massachusetts.
Visual Observation Only
The extent of this review is limited to visual inspection of existing facilities
and/or as-built documentation only. No destructive testing was performed
as part of this analysis.
Project Description
The project consists of an interior renovation of approximately 4,296
square feet of existing interior space. The majority of existing spaces shall
remain with finishes upgrades. Approximately 25% of the floor space shall
be reconfigured with a new layout.
Grade level access is provided via the main entrance doors and vestibule.
Two additional means of egress serve the suite, one leading directly to the
exterior and one leading to an existing common egress access corridor
shared with other tenant spaces.
All new work within the suite shall be accessible in compliance with AAB.
„,‘„,t1„, i,+,„„„,, A rtl., pi ,n. Anii -a; ;;; . isr
GENERAL EXISTING PROPERTY INFORMATION
A. PROPERTY NAME:
Florence Medical Center
B. ADDRESS:
190 Nonotuck Street, Florence, Massachusetts 01062
C. BUILDING USE:
The building was originally constructed as, and is currently used for B
(Business) occupancy.
D. BUILDING USE GROUP:
B- Business (Business) as defined by the Massachusetts Building Code,
780 CMR 8th Edition.
E. CONSTRUCTION CLASSIFICATION:
Type 38
Foundation: concrete slab on grade
Exterior Walls: split face CMU masonry
Int. Load Bearing: CMU
Roof: flat membrane roofing on steel framing and deck
F. HAZARD INDEX:
Existing and proposed Hazard Index is 4 as defined by the Massachusetts
Building Code, 780 CMR, 8lh Edition (IEBC Table 912.4)
„�nR .utSuliI. � 0.m,pe.eArAi IJiL,i, fir. i i' ti fi .�-�r 1u,r.hia, , .w,
CLASSIFICATION OF WORK
The proposed project work area is classified as Alteration - Level 2 per
IEBC Section 404 and therefore complies with the provisions of Chapter 6
and Chapter 7 for the following reasons:
- The project is not a repair, therefore IEBC Section 402 does not apply
- The project exceeds the limitations defined under Level 1 Alterations
as specified in IEBC Section 403:
Level 1 alterations include the removal and replacement or the
covering of existing materials, elements, equipment, or fixtures
using new materials, elements, equipment, or fixtures that serve the
same purpose.
- The project meets the limitations defined under Level 2 Alterations as
specified in IEBC Section 404:
Level 2 alterations include the reconfiguration of space, the addition
or elimination of any door or window, the reconfiguration or
extension of any system, or the installation of any additional
equipment.
- The project is below the threshold triggering Level 3 Alterations as
specified in IEBC Section 404:
Level 3 alterations apply where the work area exceeds 50 percent
of the aggregate area of the building.
- The project does not involve a change of occupancy, therefore IEBC
Section 406 does not apply.
- The project does not involve an addition, therefore IEBC Section 407
does not apply.
- The project does not impact the exterior or substantial interior
configuration of a historic building, therefore IEBC Section 408 does
not apply.
- The project does not involve a relocated building, therefore IEBC
Section 409 does not apply.
ei; I AoYh, �I n, A \1/10,11 113 _r,l'_ 1,1‘ U lv laa.h LLxlun s.mt
ALTERATIONS LEVEL 2
Section 701 General
This project work area will comply with all requirements for Alteration
Level 1 as specified in Chapter 6 and all requirements of Level 2 as
specified in Chapter 7. No portion of the proposed project work area
alters the existing conditions such that the building will become less safe
than its existing condition. Requirements regarding flood hazard areas
are not applicable to this project
Section 702 Special Use and Occupancy
Not applicable.
Section 703 Building Elements and Materials
703.2 Vertical Openings
No new or existing vertical floor openings are within the project work area.
703.3 Smoke barriers
This section applies to 1-2 occupancies and therefore does not apply to
this project.
703.4 Interior finishes
All new interior finishes, including wall, ceiling, floor, and trim materials to
be installed under this project work area will comply with Massachusetts
Building Code 780 CMR Sth Edition.
703.5 Guards
The existing rear exit is not code compliant in that there is a step down at
the threshold and the exterior landing and steps are not dimensionally
correct, nor is there a railing or guard. This will be corrected under this
project.
Section 704 Fire Protection
704.2 Automatic sprinkler systems
1.4i44114.S .rtHtilt I, Nurthinlpion.VA 0114,0 I 41i... 14‘ 7Th r, ,.‘% hi. i,ii. tt:N Nun
n/a
704.3 Standpipes
n/a
704.4 Fire alarm and detection
A fire alarm system (Notifier brand), consisting of horn/strobe units, smoke
detectors and manual pull stations, compliant with the International Fire
Code, exists within this suite Notification consists of horn and strobe
devices. The project will modify this fire alarm system.
Section 705 Means of Egress
The existing and new egress requirements within the project work area
are compliant with Massachusetts Building Code 780 CMR 8th Edition and
NFPA Life Safety Code 101.
705.3 Number of Exits:
Unchanged. Three exists serve the suite.
705.4.1 Egress doorways—two egress doorways required
Unchanged. Three egress doors serve the suite—two direct exits to the
exterior and on to an existing common egress access corridor serving
multiple tenants.
705.4.2 Egress doorways - door swing
Based on occupant load, the exit doors do not need to swing in the
direction of travel. Existing doors at the main entrance and vestibule and
the rear exit swing in the direction of travel, while the door leading to the
common exit access corridor swing into the suite.
705.4.3 Egress doorways - door closing
Existing doors at the main entrance and vestibule, the rear exit and the
door leading to the common exit access corridor each have a door closer.
705.4.4 Panic hardware
n/a—calculated occupancy below 49 occupants
Utktl .,od.y,dmI NurtLiiiiplort. 1110H,0 lid 00 1,0 -.,�x f .,:IOir n:a. ,_„
705.5 Openings in corridor walls
Corridors in this occupancy are not required to be rated.
705.6 Dead end corridors
There are no dead end corridors within the project work area.
705.7 means of egress lighting
Egress lighting consists of battery pack emergency light units. Existing
and new units shall be located as required by code.
705.8 Exit signs
Existing compliant fixtures remain unchanged. Several new internally
illuminated exit signs shall be installed as part of this project indicating
egress.
705.9 Handrails
Rear exit steps shall have code compliant handrails.
705.10 Guards
Rear exit steps shall have code compliant guards.
Section 706 Accessibility
In accordance with Massachusetts Architectural Access Board 521 CMR
section 3.3.2, because the project construction cost exceeds $100,000.00
and exceeds 30% of the full and fair cash value for the project suite (the
suite being separated from the remainder of the building by fire walls,
hence being defined as the building" for this purpose), all work within the
project work area which is required to conform to the requirements of
Massachusetts Building Code 780 CMR 8"' Edition Section 605 and 706
and Massachusetts Architectural Access Board 521 CMR shall be made
to conform.
All newly built components of the project shall be in compliance with
Massachusetts Building Code 780 CMR 8th Edition Section 605 and 706
Massachusetts Architectural Access Board 521 CMR.
Section 707 Structural
The scope of this project work area does not affect any existing structural
systems, nor does it affect applied loads on existing structural systems.
Section 708 Electrical
708.1 New Installations
Convenience outlet wiring, lighting, and data wiring are included in the
project and shall comply with the requirements of the Massachusetts
Electrical Code.
708.2 Existing Installations
B-Business occupancy does not apply
708.3 Residential occupancies
B-Business occupancy does not apply
Section 709 Mechanical
709.1 Reconfigured or converted spaces
Existing HVAC ductwork and diffusers shall be relocated and rebalanced
at renovated areas to provide mechanical ventilation to all spaces within
the project area.
709.2 Altered existing systems
The existing and modified HVAC system shall provide at least the code
minimum 5 CFM per occupant (215 CFM) of outside air and 15 CFM per
occupant (645 CFM) of ventilation air.
709.3 Local exhaust
A new anesthesia scavenging system serving the animal operating room
shall be directly vented to the building exterior.
ivt EEEEEEto E. NEENIE.EEIEEENEEE. AI1 nEi.. ,i3 .,._INI2. L,. ,f ,- « , liEENIEN LEL,1,n.n, ,
Section 710 Plumbing 5e-e- M/1 r "M"^'eA iN °3 /0/' /
710.1 Minimum fixtures
Because the occupant load o e project work area story shall not be
increased more than 20 cent, existing plumbing fixture quantities are
not required to be m led.
Section 711 Energy Conservation
711.1 Minimum requirements
Level 2 Alterations to existing buildings or structures are permitted without
requiring the entire building or structure to comply with the energy
requirements of the international Energy Conservation Code or
international Residential Code.
Areas of major reconfiguration shall have a new code compliant thermal
envelope constructed at the roof level, to replace the existing thermal
insulation laying directly on the suspended acoustic ceiling system. This
area shall be separated from other above ceiling areas where the thermal
insulation lays directly on the suspended acoustic ceiling system and shall
remain.
END OF EXISTING CONDITIONS REVIEW REPORT