Loading...
39-292 *'� � - Bob Walker From: Hayley Triggs <Hayley.Triggs@generac.com> Sent: Monday, May 23, 2016 2:28 PM To: Bob Walker Subject: CLEARANCE Good Afternoon Bob, Thank you for contacting Generac Power Systems, Inc. Customer support. The clearance for a 16KW is as follows: No operable windows or openings in the all permitted within 1.52 in (5ft) from any point of the generator. Allow sufficient room on all sides of the generator for maintenance and servicing. Clearance from the ends and from of the generator must be 3 ft. This includes shrubs,bushes and trees. Clearance from the back of the generator must be a minimum of 18 in. Clearance at the top should be a minimum of 5 ft. from any structure overhand or projections from the wall. DO NOT install under wooden decks or structures unless there is at least 5 ft. of clearance above the generator. Please also keep in mind that you always want to check with city codes. If you are still concerned about the clearance of the unit, please contact a Generac Power Systems, Inc. Service dealer. Also below, you will find a screen shot of what we require for clearance for our units. &-cb n 3: Site Semon and Pmpar an Sit* "n i s i Yarn NYANM�M AMM I'lLlMw egwf WA L�9 y d A4+Mr'w�s w/�m�Ws�.n�'8rt £M yHsiMw 9 1f✓+rvy+Mi4 k4 +TV.ibY+9e't MMfMMW Nt wwvHwawaN x+`Nuw A13�/Yi vh. t >�AN YMb k�M�WM�a� ,#0.ppMfM W NK MWw Mal�a N W NM;rMw /W wLf,s�'(YSl T+rR'vxd'! bgli MevAa M!�ax:MllbM >�,twJNx MwM 3NwM.£:bY W�1#n1t W 'St4M p+w15!'a4Yb.Mw'✓.I(vW+„WE dt .._._..._..,.,„....,..1—.--r-....,.......... m,SMXT+,rmf,4” eiMks:M A'M�'XrM Yaf 3Hs +'twFaN✓�YSIf vlal.R(4'wd%lw w vvNUMa fM£'t isMT ah b'An.a�w.ygy�{y.Mp,. r,MrMMY YM wwgs<t M»M N%J aMa SIA Mw q •MUMM✓�W GgMINSeM NWb NMk�w4 MyN A7 tYlF,yX� •�. G!`e M3t�xab a riles' aMm%rM,w a ,. M.NMarvr+w wwxM MN,w N'W'w5z 4M,w#F wn ..,, � Skxk+Mv+S:WnIN.M .•.�,•�� ... 4 /� {.3MM(dMY' Nbn.MlpeflM'ewu!pvµ.. Mees>b my rMM ewMp N 6s.'i rW iidulN.4�f..LI�jY1NpgIx 7y1�7pNYfwAN t/NjK/lY 1+N1 JPXW,T9M9A ANI,.NH 7ty p* N Mw�,. •ib4i*r*�&wawOrt hop wow*MNwaw rMw vs„NmaN rnprlr«eyu w.v4..NAr�ikuq aK'aA *a^"'"r"m4 ae4siyiw t A"wo wlwwyA 4Mi4f3C9p �Tl.riNFHF/5f6Ut d-r+NIIN W.Ta�Y 4P]Ifo NI w w IAfIaICNdf N NIYM. , '�friV 54, FIA"4*4 •h7wwN o aac W bf m"o, Slf#wt'z�fjm b6 iu'PA OV l '$p 9A.Y4'i+2.t.'w,M�'F'A 67 wTMY - �mY0�.71W4 41%71 St�tilY 9N }�"flq 7$#MGvAwlmw. wwlaN#h SY.SNW9yICe W/k+Nvw SaJGYA*At AYk wt r 11ViGii'kW SNSM rW'M.fu w5r ifNMl Imd w0N1¢�N1NAgA �I.w''k in YV?dkwOPi¢Y!TrM'.01 7wf�kw' 'M/p+aR>:tpT✓4 GMkiJLtm/by f¢arHl.,!j,CAtk,3YpN, IY,IAIIMSM11fl�1Y'1.v{'.AA 4C/o plNXgf'ibCuiyVNs If you have any questions or concerns, please feel free to give me call. Thank you, i Hayley Triggs GENERAC Customer Support Representative Generac Power Systems—Waukesha,WI Hayley.Triggs@generac.com Ph: 1888-436-3722 Ext:2758 CONFI€7ENTIA_I TY SFATEMEN"9.1 his email and any attachment is Far the solei use of the intended recipient and may contain private..confidential andlor privileged information. If you are not the intended recipient,any dissemination,distribution or copying is strictly prohibited.If YOU have received this transmission in error,please:notify Generac irnmediately by return email and delete the message;and all copies and attachments from your system. 2 Section 3: Site Selection and Preparation Section 3: Site Selection and Preparation Site Selection No operable windows or openings in the wall permitted Existing Wall within 1.52 m(5 ft)from any point of the generator. 5 ft 18 in(457 mm) 5 ft / 1 (1.52 m)� Minimumi Distance (1.52 m) . —3 ft(0.91 m)—. Top of Generator . 3 ft 0.91 m These guidelines are based upon fire testing of Allow sufficient room on all sides of the the generator enclosure and the manufacturer's generator for maintenance and servicing. requirement for air flow for proper operation. Clearance from the ends and front of the 3 ft(0.91 m) local codes may be different and more restrictive generator must be 3 ft m (0.91). This includes than what is described here. shrubs, bushes and trees. Clearance from the back of the generator must be a minimum of 18 in(457 mm).Clearance at the top should be a NOTE: Removable fence panels for servicing minimum of 5 ft (1.52 m) from any structure, cannot be placed less than 457 mm (18 in) in overhang or projections from the wall. front of the generator. DO NOT install under wooden decks or structures unless there is at least 5 ft(1.52 m) of clearance above the generator. _ _ _ X " — 5ft(1.52m) i Minimum Distance - - — —� 5ft(1.52m) Minimum Distance Clearance from operable windows, doors or any openings in the wall. 000607 Figure 3-1. Installation Guidelines Install the generator set, in its protective enclosure, • Install the generator on high ground where water outdoors, where adequate cooling and ventilating air is levels will not rise and endanger it. It should not always available(Figure 3-1). Consider these factors: operate in or be subjected to standing water. • The installation of the generator must comply • Allow sufficient room on all sides of the generator strictly with NFPA 37, NFPA 54, NFPA 58 and for maintenance and servicing. This unit must be NFPA 70 standards. installed in accordance with any codes that are in • Install the unit where air inlet and outlet openings place in your country or local jurisdiction for will not become obstructed by leaves, grass, snow, minimum distances from other structures. etc. If prevailing winds will cause blowing or • Clearance from the ends and front of the generator drifting, consider using a windbreak to protect the must be 3 ft(0.91 m). This includes shrubs, bushes unit. and trees. Clearance from the back of the generator must be a minimum of 18 in (457 mm). Installation Guidelines For 60 Hz Air-cooled Generators 11 Section 3: Site Selection and Preparation Clearance at the top should be a minimum of 5 ft 2. The weatherproof enclosure is constructed of non- (1.52 m) from any structure, overhang or combustible materials and it has been demon- projections from the wall. strated that a fire within the enclosure will not ignite • DO NOT install under wooden decks or structures combustible materials outside the enclosure. unless there is at least 5 ft (1.52 m) of clearance above the generator. Annex A— Explanatory Material • Install the unit where rain gutter down spouts, roof A4.1.4 (2) Means of demonstrating compliance are by run-off, landscape irrigation, water sprinklers or means of full scale fire test or by calculation procedures. sump pump discharge does not flood the unit or Because of the limited spaces that are frequently spray the enclosure, including any air inlet or outlet available for installation, it has become apparent that openings. exception (2) would be beneficial for many residential • Install the unit where services will not be affected and commercial installations. With that in mind, the or obstructed, including concealed, underground or manufacturer contracted with an independent testing covered services such as electrical, fuel, phone, air laboratory to run full scale fire tests to assure that the conditioning or irrigation. This could affect enclosure will not ignite combustible materials outside Warranty Coverage. the enclosure. • Where strong prevailing winds blow from one NOTE: Southwest Research Institute testing approves direction, face the generator air inlet openings to 18 in (457 mm) installation minimum from structure. the prevailing winds. Southwest Research is a nationally recognized third • Install the generator as close as possible to the fuel party testing and listing agency. supply to reduce the length of piping. REMEMBER The criteria was to determine the worst case fire scenario THAT LAWS OR CODES MAY REGULATE THE within the generator and to determine the ignitability of DISTANCE AND LOCATION. In the absence of items outside the engine enclosure at various distances. local codes regarding placement or clearance, we The enclosure is constructed of non-combustible recommend following these guidelines. materials, and the results and conclusions from the • Install the generator as close as possible to the independent testing lab indicated that any fire within the transfer switch. REMEMBER THAT LAWS OR generator enclosure would not pose any ignition risk to CODES MAY REGULATE THE DISTANCE AND nearby combustibles or structures, with or without fire LOCATION. service personnel response. • The generator must be installed on a level surface. The generator must be level within a 0.5 in (13 mm)all around. • The generator is typically placed on pea gravel, 's crushed stone or a concrete pad. Check local codes to see what type is required. If a concrete �p pad is required, all applicable codes should be $01"s.•"Antorio,' rexm • followed. SwRI D No. 13204.01.01 Installation Guidelines for Stationary Air-Cooled Stationary Engine Generator Assembly Generators MODEL NUMBER TBA Manufactured By The National Fire Protection Association has a standards ter . for the installation and use of stationary combustion engines. That standard is NFPA 37, its requirements limit Compliant with Clause (2) the spacing of an enclosed generator set from a structure of section 414 of NEPA 37 or wall (Figure 3-7). NFPA 37, Section 4.1.4, Engines Located Outdoors: 000sos Engines, and their weatherproof housings if provided, Figure 3-2. Southwest Research Institute Decal that are installed outdoors shall be located at least 5 ft (1.52 m)from openings in walls and at least 5 ft(1.52 m) Southwest Research Institute Decal (located inside the from structures having combustible walls. A minimum generator, next to the generator's data decal) separation shall not be required where the following http://www.swri.orgl4org/dollhrellistiabllistprodldirectorhtm conditions exist: Based on this testing and the requirements of NFPA 37, 1. The adjacent wall of the structure has a fire resis- Sec 4.1.4, the guidelines for installation of the generators tance rating of at least 1 hour. listed above are changed to 18 in (457 mm) from the 12 Installation Guidelines For 60 Hz Air-cooled Generators