31D-102 (11) SHEPHERD ENGINEERING, INC.
1308 GRAFTON STREET•WORCESTER,MA 01604•(508)757 7793 •FAX: (508)753 2309
15. Fire extinguishing system control equipment location—
16. Fire protection system room location-
17. Fire protection equipment identification and operation signs-
18. Fire protection systems alarm/supervisory signal transmission method and location
The existing control panel is capable of multiple 24VDC-power outputs. All auxiliary manual controls are
supervised so that all switches must be returned to the normal automatic position to clear system trouble. Each
independently supervised circuit shall include discrete panel readout to indicate disarrangement conditions per
circuit. The incoming power to the system shall be supervised so that any power failure must be audibly and
visually indicated at the control panel. A green "power on" LED shall be displayed continuously while
incoming power is present. The System Expansion Modules shall be electrically supervised for module
placement. Should a module become disconnected from the controls, the system trouble indicator must
illuminate and audible trouble signal must sound.
The system shall contain multiple supervised signaling line circuits. The alarm activation of any initiation
circuit shall not prevent the subsequent alarm operation of any other initiation circuit. There shall be
independently supervised and independently fused indicating appliance circuits for alarm horns and flashing
alarm lamps. Disarrangement conditions of any circuit shall not affect the operation of other circuits. The
system shall have provisions for disabling and enabling all circuits individually for maintenance or testing
purposes.
19. Testing Criteria to be used for final system acceptance
All fire protection systems shall be tested as a system with all equipment ready for operation.
Tests shall be performed on the following equipment and devices:
Alarm notification devices and circuits
Alarm indicating appliances and circuits
Supervisory-signal initiating devices and circuits
Signaling line circuits
Primary and secondary power supplies
The tests shall meet all the requirements of NFPA 72-2010 and NFPA 1 2015,the 8th edition Commonwealth
of Massachusetts 780 CMR 907.0, Section 2-08 Alarm Systems and the Northampton Fire Department Fire
Alarm Standards.
END OF NARRATIVE
Smith College Stoddard Hall Page 3
SHEPHERD ENGINEERING INC.
1308 GRAFTON STREET•WORCESTER,MA 01604•(508)757 7793 •FAX: (508)753 2309
switch,the following shall occur:
a. All fire alarm visuals within the building of alarm shall be activated.
b. All fire alarm horns within the building of alarm shall be activated.
b. CPU shall record the alarm;description of event shall be displayed on Information Management
System computer.
C. Fire department shall be notified via the existing monitoring system approved by the City of
Northampton.
Upon the activation of a sprinkler system tamper switch,the following shall occur:(Existing)
a. Trouble shall be annunciated on the fire alarm panel requiring acknowledgement and
investigation.
2. Building and site access
3. Fire hydrants—Not part of this project
4. Type/description and design layout of the automatic sprinkler system
5. Automatic sprinkler systems control equipment
6. Type/description and design layout of the automatic standpipe system
7. Standpipe hose valves—
8. Fire department siamese connections—
9. Type/description and design layout of the fire protective signaling system
Installation of new and relocation of existing ADA compliant audio/visual devices throughout first floor
renovated space. The audible appliances shall have a sound level at least 15 dBA above the average ambient
sound level or 5 dBA above the maximum sound level having a duration of at least 60 seconds, which ever is
greater, measured 5 feet above the floor. All audible/visual and visual notification appliances shall be mounted
80 inches above the finished floor to the bottom of the devices. New smoke detector installed within the Janitor
Room OOJ2. New fixed temp. heat detector located within renovated Staff Lounge OOK. New manual pull
station located at the means of egress as you exit the space in Lobby OOL.
10. Fire protective signaling system control equipment and remote annunciator location
The existing main fire alarm signaling control equipment is Simplex Company #2001 series, hard-wired,
located in the Basement Sprinkler Room.
11. Type/description and design layout of the smoke control or exhaust system
12. Smoke control system control equipment location
13. Building life safety system feature integrated into fire protective signaling system
See 9. & 10.
14. Type/description and design layout for the fire extinguishing systems—
Smith College Stoddard Hall Page 2
SHEPHERD ENGINEERING INC.
1308 GRAFTON STREET•WORCESTER,MA 01604•(508)757 7793 •FAX: (508)753 2309
Smith College Stoddard Hall
23 Elm Street
!;
Northampton, MA ��`��
February 6, 2015 ROBERT ,
J.
FIGUERIDO
780 CMR 907.1.1 -Fire Protection Construction Documents o� No.29029
1. a. Basis(methodology)of design
Section 1 -Building Description
Refer to the Architect
Section 2-Applicable Laws Regulations and Standards
o 780 CMR 8th Edition Massachusetts State Building Code.
o NFPA 72—2010 edition standards and NFPA 12015.
o Sections of M.G.L. 148—Fire Prevention.
• Sections of 527 CMR—Fire Prevention Regulations.
• Approved local by-laws or ordinances—Section 2-08 Alarm Systems.
0
Section 3 -Design Responsibility for Fire Protection Systems
Shepherd Engineering,Inc.
1308 Grafton Street
Worcester,MA 01604
(508)757-7793
Robert J.Figuerido
MA PE#29029
Section 4-Fire Protection Systems Being Installed
Installation of new and relocation of existing hard-wired fire alarm devices to protect the renovated areas
located on the first floor. New and relocated wall mounted ADA compliant audio-strobes will be installed
throughout the renovated space to match that which is currently operating within the building. Devices
shall be installed to meet the requirements of ADA and NFPA-72(2010)and NFPA 12015.
Section 5-Features Used in the DesijZn Methodology
Building occupants will be notified of an alarm condition through the use of existing and new horn strobe
audio/visual units, individually,by space. Upon completion of the installation fire alarm manufacturer of a
factory trained technician shall test the system devices as outlined in NFPA 72—2010 and NFPA 1 2015,
edition and 780 CMR, 8th edition,Massachusetts State Building Code, Chapter 9 as required. In addition,
all alarms and trouble conditions will sound at the fire alarm control panel until acknowledged and reset.
Section 6-Special Consideration and Description
Not Applicable
1. b. Sequence of Operation
Section 1:
Upon the activation of a new or existing manual pull station,smoke detector or an existing sprinkler flow
Smith College Stoddard Hall Page 1
Initial Construction Control Document
To be submitted with the building permit application by a
Registered Design Professional
for work per the 8th edition of the
Massachusetts State Building Code, 780 CMR, Section 107
Project Title: Smith College Stodard Hall G2 Lecture Hall Date: January 27,2015 Construction Documents
Property Address: Smith College,23 Elm Street,Northampton, MA
Project: Check(x)one or both as applicable: New construction X Existing Construction
Project description: Renovations to Stoddard Hall G2 Lecture Hall and adjacent Toilet Rooms and Staff Lounge.
1 Robert J. Figuerido MA Registration Number: 29029 Expiration date: June 30, 2016,am a registered design
professional, and I have prepared or directly supervised the preparation of all design plans,computations and
specifications concerning':
Architectural Structural Mechanical
Fire Protection X Electrical X Other: Fire Alarm
for the above named project and that to the best of my knowledge, information,and belief such plans,computations and
specifications meet the applicable provisions of the Massachusetts State Building Code, (780 CMR),and accepted
engineering practices for the proposed project. I understand and agree that I(or my designee)shall perform the necessary
professional services and be present on the construction site on a regular and periodic basis to:
1. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the
contractor in accordance with the requirements of the construction documents.
2. Perform the duties for registered design professionals in 780 CMR Chapter 17,as applicable.
3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and
quality of the work and to determine if the work is being performed in a manner consistent with the approved
construction documents and this code.
Nothing in this document relieves the contractor of its responsibility regarding the provisions of 780 CMR 107.
When required by the building official,I shall submit field/progress reports(see item 3.)together with pertinent
comments, in a form acceptable to the building official. Upon completion of the work, I shall submit to the building
official a`Final Construction Control Document'.
c�
Enter in the space to the right a"wet"or
electronic signature and seal: o J.
FIGUER100
Phone number: 508.757.7793 Email: bobf @shepherdengineeringinc.com
r�
Building Official Use Only
Building Official Name: Permit No.: Date:
Note 1.Indicate with an`x'project design plans,computations and specifications that you prepared or directly supervised.If`other' is chosen,
provide a description.
Version 06 11 2013
Initial Construction Control Document
To be submitted with the building permit application by a
Registered Design Professional
for work per the 8th edition of the
r
Massachusetts State Building Code, 780 CMR, Section 107
Project Title: Stoddard Hall Renovations Date: 2/6/15
Property Address: Smith College-23 Elm St.-Northampton
Project: Check(x)one or both as applicable: _New construction X Existing Construction
Project description: Auditorium and First Floor Renovations
I Peter G.Radzim MA Registration Number: 46907 Expiration date: 6/30/16, am a registered design professional, and
I have prepared or directly supervised the preparation of all design plans,computations and specifications concerning':
Architectural Structural X Mechanical
Fire Protection Electrical Other:
for the above named project and that to the best of my knowledge, information,and belief such plans,computations and
specifications meet the applicable provisions of the Massachusetts State Building Code,(780 CMR),and accepted
engineering practices for the proposed project. I understand and agree that I(or my designee) shall perform the necessary
professional services and be present on the construction site on a regular and periodic basis to:
1. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the
contractor in accordance with the requirements of the construction documents.
2. Perform the duties for registered design professionals in 780 CMR Chapter 17, as applicable.
3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and
quality of the work and to determine if the work is being performed in a manner consistent with the approved
construction documents and this code.
Nothing in this document relieves the contractor of its responsibility regarding the provisions of 780 CMR 107.
When required by the building official,I shall submit field/progress reports(see item 3.)together with pertinent
comments, in a form acceptable to the building official.
Upon completion of the work, I shall submit to the building official a `Final Construction Control Document'.
Enter in the space to the right a"wet"or 3H OF ,
electronic signature and seal: PETER G. G� e�`e 'r� FRANCIS J.STRAMAGUA
RAD21M NOTARY PUBLIC
MECHANICAL `� Commonwealth of Massachusetts
No.46907 My Commission Expires on
February 12,2021
Z/`/IS
Phone number: (781)935-7228 Email: pradzim @vavint.com
Building Official Use Only
Building Official Name: Permit No.: Date:
Note 1.Indicate with an`x'project design plans,computations and specifications that you prepared or directly supervised.If`other' is chosen,
provide a description.
Initial Construction Control Document
_ To be submitted with the building permit application by a
Registered Design Professional
for work per the 8th edition of the
a
Massachusetts State Building Code, 780 CMR, Section 107
Project Title: Stoddard Hall Renovations Date: 2/6/15
Property Address: Smith College-23 Elm St.-Northampton
Project: Check(x)one or both as applicable: —New construction X Existing Construction
Project description: Auditorium and First Floor Renovations
I Peter G.Radzim MA Registration Number: 46907 Expiration date: 6/30/16, am a registered design professional, and
I have prepared or directly supervised the preparation of all design plans,computations and specifications concerning':
Architectural Structural Mechanical
Fire Protection Electrical X Plumbing
for the above named project and that to the best of my knowledge, information,and belief such plans,computations and
specifications meet the applicable provisions of the Massachusetts State Building Code, (780 CMR),and accepted
engineering practices for the proposed project. I understand and agree that I (or my designee) shall perform the necessary
professional services and be present on the construction site on a regular and periodic basis to:
1. Review, for confori'nance to this code and the design concept, shop drawings, samples and other submittals by the
contractor in accordance with the requirements of the construction documents.
2. Perform the duties for registered design professionals in 780 CMR Chapter 17,as applicable.
3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and
quality of the work and to determine if the work is being performed in a manner consistent with the approved
construction documents and this code.
Nothing in this document relieves the contractor of its responsibility regarding the provisions of 780 CMR 107.
When required by the building official, I shall submit field/progress reports(see item 3.)together with pertinent
comments, in a form acceptable to the building official.
Upon completion of the work,I shall submit to the building official a `Final Construction Control Document'.
Enter in the space to the right a"wet"or tw Of
electronic signature and seal: PETER G
RADZIM : *"a.& FRANCIS J.STRAMAGLIA '
MECHANICAL NOTARY PUBLIC
No.48907 Commonwealth of Massachusetts
My Commission Expires on
February 12 2021
N,
z/oc&
Phone number: (781)935-7228 Email: pradzim @vavint.com /
Building Official Use Only
Building Official Name: Permit No.: Date:
Note 1. Indicate with an`x'project design plans,computations and specifications that you prepared or directly supervised.If`other' is chosen,
provide a description.
Initial Construction Control Document
To be submitted with the building permit application by a
Registered Design Professional
for work per the 81h edition of the
ti yJevewa Massachusetts State Building Code, 780 CMR, Section 107
Project Title: Stoddard Hall Renovations Date: 2/6/15
Property Address: Smith College-23 Elm St.-Northampton
Project: Check(x)one or both as applicable: _New construction X Existing Construction
Project description: Auditorium and First Floor Renovations
I Peter G.Radzim MA Registration Number: 46907 Expiration date: 6/30/16, am a registered design professional, and
I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning':
Architectural Structural Mechanical
X Fire Protection Electrical Plumbing
for the above named project and that to the best of my knowledge, information,and belief such plans, computations and
specifications meet the applicable provisions of the Massachusetts State Building Code, (780 CMR),and accepted
engineering practices for the proposed project. I understand and agree that I (or my designee) shall perform the necessary
professional services and be present on the construction site on a regular and periodic basis to:
1. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the
contractor in accordance with the requirements of the construction documents.
2. Perform the duties for registered design professionals in 780 CMR Chapter 17,as applicable.
3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and
quality of the work and to determine if the work is being performed in a manner consistent with the approved
construction documents and this code.
Nothing in this document relieves the contractor of its responsibility regarding the provisions of 780 CMR 107.
When required by the building official, I shall submit field/progress reports(see item 3.)together with pertinent
comments, in a form acceptable to the building official.
Upon completion of the work, I shall submit to the building official a `Final Construction Control Document'.
Enter in the space to the right a"wet"or jA of P"t s
electronic signature and seal: P.EP o 5 •` 'A" FRANCIS J.Y PUBLIC
GLIA 1
'� b —_-�� NOTARY PUBLIC
I
RADZ01 Commonwealth of Massachusetts'
MECHANICAL :' My Commission Expires on
No.46907 � - February 12,2021
,... Z/4�I�s
Phone number: (781) 935-7228 Email: pradzim @vavint.com
Building Official Use Only
Building Official Name: Permit No.: Date:
Note 1. Indicate with an`x'project design plans,computations and specifications that you prepared or directly supervised.If`other' is chosen,
provide a description.
Final Construction Control Document
To be submitted at completion of construction by a
Registered Design Professional
,W for work per the 8th edition of the
M Jev
Massachusetts State Building Code, 780 CMR, Section 107.6.4
Project Title: Smith College - Stoddard Hall Date: 02-11-2015 Permit No.
Property Address: Northampton, MA
Project: Check(x)one or both as applicable: New construction X Existing Construction
Project description: Lecture Hall Riser Framing and Exterior Ramp
I, Rober A. Johnson MA Registration Number: 38492 Expiration date: June 2016, am a registered design professional,
and hereby certify that I have prepared or directly supervised the preparation of all design plans, computations and
specifications concerning':
Entire Project Architectural X Structural Mechanical
Fire Protection Electrical Other:
for the above named project. I certify that 1, or my designee,have performed the necessary professional services and was
present at the construction site on a regular and periodic basis to determine that the work proceeded in accordance with
the requirements of 780 CMR and the design documents prepared by me and approved as part of the building permit and
that I or my designee:
1. Have reviewed,for conformance to this code and the design concept, shop drawings, samples and other submittals
by the contractor in accordance with the requirements of the construction documents.
2. Have performed the duties for registered design professionals in 780 CMR Chapter 17, as applicable.
3. Have been present at intervals appropriate to the stage of construction to become generally familiar with the
progress and quality of the work and to determine if the work was performed in a manner consistent with the
construction documents and this code.
Enter in the space to the right a"wet"or _ Aseal:
electronic signature and sea
Phone number: (508) 892-4884 Email: Rob @jsengineers.com !� A'
Building Official Use Only
Building Official Name: Permit No.: Date:
Note 1. Indicate with an `x'project design plans,computations and specifications that you prepared or directly supervised. If`other'is chosen,
provide a description.
Trial Version 10 09 2012
Juster Pope Frazier LLC
Architecture I Planning
82 North Street
Northampton,Massachusetts
www.justerpopefrazier.com
4 1 3 5 8 6 1 6 0 0
CONSTRUCTION CONTROL AFFADAVIT
Date: March 04,2015
Project Title: Stoddard Hall Renovations
Project Location: Smith College, Northampton,Massachusetts
Nature of Building: Interior renovations of an auditorium and related improvements.
In accordance with section 116.0 of the Massachusetts State Building Code, I, Kevin J.
Chrobak, Registration Number 8603, being a registered professional architect, hereby certify
that I have prepared or directly supervised the preparation of all design plans, computations,
and specifications concerning:
_HVAC X Architectural _Structural _Mechanical
_Fire Protection _Electrical _Plumbing _Other
For the above named project and that, to the best of my professional knowledge, such plans,
computations and specifications meet the provisions of the Massachusetts State Building Code
including all amendments as of the date above, and all applicable laws and ordinances for the
proposed use and occupancy. I further certify that I shall perform the necessary professional
services and be present on the construction site on a regular and periodic basis to determine
that the work is proceeding in accordance with the documents approved for the building permit
and shall be responsible for the following as specified in section 780 CMR 116.0 8`h edition of
the Massachusetts State Building Code.
SEAL
A
SG RE
PI t \-NING AND SUS rAiN ABi Iri-Y`O,i- 'oiI oKn I A NI1'"T')N
p7nnninf;.consu cutum.uunng.uor[hampton G7S Pistoric•con5nuuut� aliou-cc nlr it i�uvinu ss rchikrlurc
tt n
Sarah 1 ttV Ilc+,,L'uiis<rrcutiom,4'resercatiou,8 Iand U,(c Planner•ni�e�lk}d��na rthar���tomua.gne yi3-� "'-�'��3
January 14, 2015
Peter Gagnon
Smith College Capital Improvements
126 West Street
Northampton MA 01063
RE: Elm Street Historic District Certificate of Nonapplicability
29 Elm Street (Stoddard Hall)
Accessibility Ramp Installation
Dear Mr. Gagnon:
Thank you for submitting an application for a Certificate of Nonapplicability for installation of
an accessible ramp within the Elm Street Local Historic District, as shown in the plans prepared
by Juster Pope Frazer, dated December 3,2014. In accordance with §195-5 B(1), the work
proposed is an'access device and ramp not facing a street and not altering the historic cliaracter of a
structure,'and is exempt from Historic District Review.
This Certificate is issued by staff to the Northampton Historical Commission, acting on behalf of
the Director of Planning and Sustainability. No further Local Historic District Review is
required for this project.
Thank you,
Sarah L LaValley
(;ity flail«�*to Main Street•NorthzPMptoll,NIA o06o•�vw��ti�.r�cer�t3��zn�tc���rna, c��=,'t)�'tl ti� �3 's 0 l
E3 oa.0 o f 3u;Id
e:lse. CS-057407
JAMES E MADIGAN
PO BOX 206"0
WORCESTER MA 01602
:n ssrort,t 12/11/2015
The Commonwealth of Massachusetts Prnt ° '
Department oflndustrialAccidents
r Office of Investigations
I Congress Street, Suite 100
Boston, MA 02114-2017
www.mass.gov/dia
Workers' Compensation Insurance Affidavit: Builders/Contractors/Electricians/Plumbers
Applicant Information Please Print Legibly
Name(Business/Organization/Individual): F.W.Madigan Company,Inc. _
Address: 367 Chandler Street, PO Box 20670
City/State/Zip: Worcester, MA 01602 Phone#: 508-753-1459
Are you an employer? Check the appropriate box: Type of project(required):
1.R✓ I am a employer with 25 4. [] I am a general contractor and I 6. ❑New construction
employees(full and/or part-time).* have hired the sub-contractors
2.❑ I am a sole proprietor or partner- listed on the attached sheet. 7. ] Remodeling
ship and have no employees These sub-contractors have g, E] Demolition
working for me in any capacity. employees and have workers' 9. E] Building addition
[No workers' comp. insurance comp. insurance.t
required.] 5. E] We are a corporation and its 10.❑Electrical repairs or additions
3.❑ I am a homeowner doing all work officers have exercised their I LE] Plumbing repairs or additions
myself. [No workers' comp. right of exemption per MGL 12.❑ Roof repairs
insurance required.]t c. 152, §1(4),and we have no
employees. [No workers' 13.0 Other
comp. insurance required.]
*Any applicant that checks box#1 must also fill out the section below showing their workers'compensation policy information.
t Homeowners who submit this affidavit indicating they are doing all work and then hire outside contractors must submit a new affidavit indicating such.
$Contractors that check this box must attached an additional sheet showing the name of the sub-contractors and state whether or not those entities have
employees. If the sub-contractors have employees,they must provide their workers'comp.policy number.
I am an employer that is providing workers'compensation insurance for my employees. Below is the policy and job site
information.
Insurance Company Name: CNA
Policy#or Self-ins. Lie. #: 6014131021 Expiration Date: 7/1/2015
Job Site Address: 29 Elm Street City/State/Zip: Northampton, MA 01060
Attach a copy of the workers' compensation policy declaration page(showing the policy number and expiration date).
Failure to secure coverage as required under Section 25A of MGL c. 152 can lead to the imposition of criminal penalties of a
fine up to$1,500.00 and/or one-year imprisonment,as well as civil penalties in the form of a STOP WORK ORDER and a fine
of up to$250.00 a day against the violator. Be advised that a copy of this statement may be forwarded to the Office of
Investigations of the DIA for insurance coverage verification.
I do hereby certify under the pains and penalties of perjury that the information provided a ay is true and correct.
Signature:
� Date: ✓� 18 �s
Phone#: 50 3-1459
Official use only. Do not write in this area,to be completed by city or town official
City or Town: Permit/License#
Issuing Authority(circle one):
1.Board of Health 2.Building Department 3. City/Town Clerk 4.Electrical Inspector 5. Plumbing Inspector
6. Other
Contact Person: Phone#:
Versionl.7 Commercial Building Permit May 15,2000
SECTION 10-STRUCTURAL PEER REVIEW(780 CMR 110.11)
Independent Structural Engineering Structural Peer Review Required Yes 0 No G)
SECTION 11 -OWNER AUTHORIZATION-TO BE COMPLETED WHEN
OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILD PERMIT
C �1 v
as Owner of the subject property
hereby authorize to
act on my behalf, in all matters relative to work authorized by this building permit application.
Signature of Owner Date
James Madigan , as Owner/Authorized
Agent hereby declare that the statements and information on the foregoing application are true and accurate,to the best of my knowledge
and belief.
Signed under the pains and penalties of perjury.
-I—AM6!5 :E. MAot��
Print Na e
Sign to of Owner/Ag t Date
SECTION 12-CONSTRUCTION SERVICES
10.1 Licensed Construction Supervisor: Not Applicable ❑
Name of License Holder: James E Madigan 0$7467
License Number
367 Chandler St Worcester, MA 01602 (?-1111),5
Address Expiration Date
(508) 753-1459
Signa r Telephone
SECTION 13-WORKERS'COMPENSATION INSURANCE AFFIDAVIT(M.G.L.c. 152,§25C(6))
Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result
in the denial of the issuance of the building permit.
Signed Affidavit Attached Yes (�) No 0
Version 1.7 Commercial Building Permit May 15,2000
SECTION 9-PROFESSIONAL DESIGN AND CONSTRUCTION SERVICES-FOR BUILDINGS AND STRUCTURES SUBJECT TO
CONSTRUCTION CONTROL PURSUANT TO 780 CMR 116(CONTAINING MORE THAN 35,000 C.F.OF ENCLOSED SPACE)
9.1 Registered Architect:
Not Applicable ❑
Name(Registrant):
Registration Number
Address
Expiration Date
Signature Telephone
9.2 Registered Professional Engineer(s):
Name Area of Responsibility
Address Registration Number
Signature Telephone Expiration Date
Name Area of Responsibility
Address Registration Number
Signature Telephone Expiration Date
Name Area of Responsibility
Address Registration Number
Signature Telephone Expiration Date
Name Area of Responsibility
Address Registration Number
Signature Telephone Expiration Date
9.3 General Contractor
FW Madigan Company, Inc. Not Applicable ❑
Company Name:
James E Madigan
Responsible In Charge of Construction
367 Chandler St Worcester,MA 01602
Address
(508)753-1459
Sign r Telephone
Versionl.7 Commercial Building Permit May 15,2000
8. NORTHAMPTON ZONING
Existing Proposed Required by Zoning
This column to be filled in by
Building Department
Lot Size
Frontage
Setbacks Front
Side L: R: L: R:
Rear
Building Height
Bldg. Square Footage %
Open Space Footage %
(Lot area minus bldg&paved
parking)
#of Parking Spaces
Fill:
volume&Location
A. Has a Special Permit/Variance/Finding ever been issued for/on the site?
NO 0 DONT KNOW Q YES
IF YES, date issued:
IF YES: Was the permit recorded at the Registry of Deeds?
NO ® DONT KNOW Q YES
IF YES: enter Book Page and/or Document#
B. Does the site contain a brook, body of water or wetlands? NO Q DONT KNOW ® YES
IF YES, has a permit been or need to be obtained from the Conservation Commission?
Needs to be obtained ® Obtained ® , Date Issued:
C. Do any signs exist on the property? YES ® NO
IF YES, describe size, type and location:
D. Are there any proposed changes to or additions of signs intended for the property? YES ® NO
IF YES, describe size, type and location:
E. Will the construction activity disturb(clearing,grading,excavation, or filling)over 1 acre or is it part of a common plan
that will disturb over 1 acre? YES ® NO O
IF YES,then a Northampton Storm Water Management Permit from the DPW is required.
Version 1.7 Commercial Building Permit May 15,2000
SECTION 4-CONSTRUCTION SERVICES FOR PROJECTS LESS THAN 35,000
CUBIC FEET OF ENCLOSED SPACE
Interior Alterations Existing Wall Signs ❑ Demolition Repairs❑ Additions ❑ Accessory Building❑
Exterior Alteration ❑ Existing Ground Sign❑ New Signs❑ Roofing❑ Change of Use❑ Other❑
Brief Description F*e^ovG+ia�S 1 o e..AfV-y e-A.. P i �'L f-t.i0r rx.,e J d o„ s 4-. 4t", l%Fw;K.•. s petce
Of Proposed Work: Cv.O( c '�'it c S Fv r 9L IC/ re-$ -"o m st acc..s o N e roan d A(oa r
SECTION 5-USE GROUP AND CONSTRUCTION TYPE
USE GROUP(Check as applicable) CONSTRUCTION TYPE
A Assembly ❑ A-1 ❑ A-2 ❑ A-3 ❑ 1A ❑
A-4 ❑ A-5 ❑ 1B ❑
B Business ❑ 2A ❑
E Educational ❑ 2B I ❑
F Factory ❑ F-1 ❑ F-2 ❑ 2C ❑
H Hi h Hazard ❑ 3A ❑
I Institutional ❑ 1-1 ❑ 1-2 ❑ 1-3 ❑ 3B ❑
M Mercantile ❑ 4 ❑
R Residential ❑ R-1 ❑ R-2 ❑ R-3 ❑ 5A ❑
S Storage ❑ S-1 ❑ S-2 ❑ 5B ❑
U Utility ❑ Specify:
M Mixed Use ❑ Specify:
S Special Use ❑ Specify:
COMPLETE THIS SECTION IF EXISTING BUILDING UNDERGOING RENOVATIONS,ADDITIONS AND/OR CHANGE IN USE
Existing Use Group: Proposed Use Group:
Existing Hazard Index 780 CMR 34): Proposed Hazard Index 780 CMR 34):
SECTION 6 BUILDING HEIGHT AND AREA
BUILDING AREA EXISTING PROPOSED NEW CONSTRUCTION OFFICE USE ONLY
Floor Area per Floor(sf)
St
1St G�tQroxn.alely 5000 SF 1 SGwc
2nd are ro�e;.-a ,Le(y &Soo SF 2nd Sa04.
rd
3rd wroXt mat Gfy �5005F 3SAwt,
4m
4th &rprox.1%4fG1y Zg00 $F sGwa
Total Area(sf) 'L? t/2 S F Total Proposed New Construction(sf)
Sarw
Total Height(ft) q p� f�(y 551
Total Height ft $a&.r.•
7.Water Supply(M.G.L.c.40,§54) 7.1 Flood Zone Information: 7.3 Sewage Disposal System:
Public ❑✓ Private ❑ I Zone Outside Flood Zoned Municipal E] On site disposal system[-]
ROW5
Ras - Versionl.7 Commercial Building Permit May 15,2000
r Department use only
ity of Northampton Status of Permit:
ilding Department Curb Cut/Driveway Permit -
212 Main Street Sewer/Septic Availability
QJ\yo�,tt� Room 100 Water/Well Availability
Northampton, MA 01060 Two Sets of Structural Plans
phone 413-587-1240 Fax 413-587-1272 Plot/Site Plans
Other Specify
APPLICATION TO CONSTRUCT,REPAIR,RENOVATE,CHANGE THE USE OR OCCUPANCY OF,OR DEMOLISH ANY BUILDING
OTHER THAN A ONE OR TWO FAMILY DWELLING
SECTION 1 -SITE INFORMATION
1.1 Property Address: This section to be completed by office
29 Elm Street Map Lot Unit
Northampton, MA 01060
Zone Overlay District
Elm St.District CB District
SECTION 2-PROPERTY OWNERSHIP/AUTHORIZED AGENT
2.1 Owner of Record:
The Trustees of the S" College c/o Facilities 126 West Street Northampton, MA 01063
Management, Gary a ell Current Mailing Address:
(413) 585-2481
Signature Telephone
2.2 Authorized Ape
James Madigan 367 Chandler St Worcester, MA 01604
Name(Print) Current Mailing Address:
(508) 753-1459
Signature "� Telephone
SECTION 3- STIMATED CONSTRUCTION COSTS
Item Estimated Cost(Dollars)to be Official Use Only
completed by ermit applicant
1. Building &07 I (a)Building Permit Fee
2. Electrical t, ej7 (b)Estimated Total Cost of
J C Construction from 6
3. Plumbing Building Permit Fee
4. Mechanical (HVAC) /
5. Fire Protection '
6. Total=0 +2+3+4+ 5) 7�✓. ��� Check Number #3"'
5�
This Section For Official Use Only
Building Permit Number Date
Issued
Signature:
Building Commissioner/Inspector of Buildings Date
File#BP-2015-0877
APPLICANT/CONTACT PERSON F W MADIGAN CO INC
ADDRESS/PHONE P O BOX 20670 WORCESTER01602-0670(508)753-1459
PROPERTY LOCATION 29 ELM ST-STODDARD HALL
MAP 31 D PARCEL 102 001 ZONE EU(100)/URC(I00)/
THIS SECTION FOR OFFICIAL USE ONLY:
PERMIT APPLICATION CHECKLIST
ENCLOSED REQUIRED DATE
ZONING FORM FILLED OUT
Fee Paid rJ �
Building Permit Filled out
Fee Paid
Typeof Construction:_RENOVATIONS TO ENTRY RAMP, INTERIOR RENO TO
AUDITORIUM OFFICE STORAGE RESTROOM SPACE ON GROUND FLR
New Construction
Non Structural interior renovations
Addition to Existing
Accessory Structure
Building Plans Included:
Owner/Statement or License 057407
3 sets of Plans/Plot Plan
THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON
INFS,IRMATION PRESENTED:
I Approved Additional permits required(see below)
PLANNING BOARD PERMIT REQUIRED UNDER:§
Intermediate Project: Site Plan AND/OR Special Permit With Site Plan
Major Project: Site Plan AND/OR Special Permit With Site Plan
ZONING BOARD PERMIT REQUIRED UNDER: §
Finding Special Permit Variance*
Received&Recorded at Registry of Deeds Proof Enclosed
Other Permits Required:
Curb Cut from DPW Water Availability Sewer Availability
Septic Approval Board of Health Well Water Potability Board of Health
Permit from Conservation Commission Permit from CB Architecture Committee
Permit from Elm Street Commission Permit DPW Storm Water Management
Demolition Delay
f ?'
ff
Signature of Building Official Date
Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning
requirements and obtain all required permits from Board of Health,Conservation Commission,Department
of public works and other applicable permit granting authorities.
* Variances are granted only to those applicants who meet the strict standards of MGL 40A.Contact Office of
Planning&Development for more information.
29 ELM ST-STODDARD HALL BP-2015-0877
GIS#: COMMONWEALTH OF MASSACHUSETTS
Map:Block: 3 1 D- 102 CITY OF NORTHAMPTON
Lot: -001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS
Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A)
Category: renovation BUILDING PERMIT
Permit# BP-2015-0877
Project# JS-2015-001714
Est. Cost: $575000.00
Fee: $3450.00 PERMISSION IS HEREBY GRANTED TO:
Const.Class: Contractor: License:
Use Group: F W MADIGAN CO INC 057407
Lot Size(sq. ft.): 45738.00 Owner: SMITH COLLEGE OFFICE OF TREASURER
Zoning: EU(100)/URC(100)/ Applicant: F W MADIGAN CO INC
AT. 29 ELM ST - STODDARD HALL
Applicant Address: Phone: Insurance:
P O BOX 20670 (508) 753-1459 Workers Compensation
WORCESTERMA01602-0670 ISSUED ON:411712015 0:00:00
TO PERFORM THE FOLLOWING WORK: RENOVATIONS TO ENTRY RAMP, INTERIOR
RENO TO AUDITORIUM,OFFICE,STORAGE,RESTROOM SPACE ON GROUND FLR
POST THIS CARD SO IT IS VISIBLE FROM THE STREET
Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector
Underground: Service: Meter:
Footings:
Rough: Rough: House# Foundation:
Driveway Final:
Final: Final:
Rough Frame:
Gas: Fire Department Fireplace/Chimney:
Rough: Oil: Insulation:
Final: Smoke: Final:
THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF
ANY OF ITS RULES AND REGULATIONS.
Certificate of Occupancy Signature:
FeeType• Date Paid: Amount:
Building 4/14/2015 0:00:00 $3450.00
212 Main Street,Phone(413)587-1240,Fax: (413)587-1272
Louis Hasbrouck—Building Commissioner