17A-255 (4)
AIR LEAKAGE REPORT Date: March 07,2013 Rating No.: 040-12 Building Name: 121 Oak St Rating Org.: Power House Energy Consulting Owner's Name: Phone No.: 413-835-5162 Property: 121 Oak St Rater's Name: Matt Turcotte Address: Northampton,MA 01062 Rater's No.: 1497133 Builder's Name: Jeffrey Morin Weather Site: Northampton,MA Rating Type: Confirmed File Name: 040-12 121 Oak St FINAL.big Rating Date: 1/4/13 Blower door test Whole House Infiltration Heating Cooling Natural ACH: 0.06 0.04 ACH @ 50 Pascals: 0.99 0.99 CFM @ 25 Pascals: 243 243 CFM @ 50 Pascals: 382 382 Eff.Leakage Area: [sq.in] 21.0 21.0 Specific Leakage Area: 0.00008 0.00008 ELA/100 sf shell: [sq.in] 0.35 0.35 Duct Leakage Leakage to Outside Units ducts CFM @ 25 Pascals: 11 CFM25/CFMfan: 0.0118 CFM25/CFA: 0.0058 CFM per Std 152: N/A CFM per Std 152/CFA: N/A CFM @ 50 Pascals: 17 Eff.Leakage Area: [sq.in] 0.95 Thermal Efficiency: N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage: 0.1038 Ventilation Mechanical: Balanced Sensible Recovery Eff.(%): 60.0 Total Recovery Eff.(%): 20.0 Rate(cfm): 67 Hours/Day: 18.0 Fan Watts: 72.0 Cooling Ventilation: Natural Ventilation ASH RAE 62.2-2010 Ventilation Requirements For this home to comply with ASHRAE Standard 62.2-2010 Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings,a minimum of 49 cfm of mechanical ventilation must be provided continuously, 24 hours per day. Alternatively,an intermittently operating mechanical ventilation system may be used if the ventilation rate is adjusted accordingly. For example,a 98 cfm mechanical ventilation system would need to operate 12 hours per day,as long as the system operates to provide required average ventilation once each hour. REM/Rate-Residential Energy Analysis and Rating Software v12.99 This information does not constitute any warranty of energy cost or savings. @ 1985-2012 Architectural Energy Corporation,Boulder,Colorado. t ENERGY STAR Qualified Homes, Version 3 (Rev. 06) Thermal Enclosure System Rater Checklist ----------- Must I Builder Rater 5.Air Sealing Correct; Verified' Verified' N/A 5.1 Penetrations to unconditioned space fully sealed with solid blocking or flashing as needed and gaps sealed with caulk or foam 5.1.1 Duct/flue shaft ❑ ❑ ❑ 5.1.2 Plumbing/piping ❑ ❑ ❑ 5.1.3 Electrical wiring ❑ ❑ ^ ❑ 5.1.4 Bathroom and kitchen exhaust fans ❑ ❑ ❑ 5.1.5 Recessed lighting fixtures adjacent to unconditioned space ICAT labeled and fully ,J gasketed.Also,if in insulated ceiling without attic above,exterior surface of fixture ❑ ❑ ❑ l� insulated to a R-10 in CZ 4 and higher to minimize condensation potential. 5.1.6 Light tubes adjacent to unconditioned space include lens separating unconditioned and ❑ ❑ +� ❑ conditioned space and are fully gasketed 22 5.2 Cracks in the building envelope fully sealed foam,or equivalent material.Foam gasket also placed beneath sill plate if resting atop ❑ ❑ ❑ concrete or masonry and adjacent to conditioned space 23 5.2.1 All sill plates adjacent to conditioned space sealed to foundation or sub-floor with caulk, 5.2.2 At top of walls adjoining unconditioned spaces,continuous top plates or sealed blocking ❑ ❑ ❑ using caulk,foam,or equivalent material 5.2.3 Drywall sealed to top plate at all unconditioned attic/wall interfaces using caulk,foam, drywall adhesive(but not other construction adhesives),or equivalent material.Either ❑ ❑ ❑ apply sealant directly between drywall and top plate or to the seam between the two from the attic above. 5.2.4 Rough opening around windows&exterior doors sealed with caulk or foam 24 ❑ ❑ ❑ 5.2.5 Marriage joints between modular home modules at all exterior boundary conditions fully ❑ ❑ ❑ bf sealed with gasket and foam !'� 5.2.6 All seams between Structural Insulated Panels(SIPs)foamed and/or taped per ❑ ❑ ❑ manufacturer's instructions 5.2.7 In multifamily buildings,the gap between the drywall shaft wall(i.e.common wall)and the ❑ ❑ ❑ structural framing between units fully sealed at all exterior boundaries 5.3 Other openings 5.3.1 Doors adjacent to unconditioned space(e.g.,attics,garages,basements)or ambient ❑ ❑ / ❑ conditions gasketed or made substantially air-tight 5.3.2 Attic access panels and drop-down stairs equipped with a durable?R-10 insulated cover that is gasketed(i.e.,not caulked)to produce continuous air seal when occupant is not ❑ ❑ ❑ accessing the attic 25 5.3.3 Whole-house fans equipped with a durable a R-10 insulated cover that is gasketed and ❑ ❑ ❑ either installed on the house side or mechanically operated z5 Rater Name: AaA �;� Rater Pre-Drywall Inspection Date: /'� Rater Initials: Rater Name: a �_� uy"/�'- _._ Rater Final Inspection Date: ��— Rater Initials: Builder Employee: Builder Inspection Date: Builder Initials: Notes: 1. At the discretion of the Rater, the builder may verify up to eight items specified in this Checklist. When exercised, the builder's responsibility will be formally acknowledged by the builder signing off on the checklist for the item(s)that they verified. 2. For Prescriptive Path: All windows, doors, and skylights shall meet or exceed ENERGY STAR Program Requirements for Residential Windows, Doors, and Skylights–Version 5.0 as outlined at www.enerctvsta r.gov/wind Lv s. For Performance Path:All windows,doors and skylights shall meet or exceed the component U-factor and SHGC requirements specified in the 2009 IECC–Table 402.1.1. If no NFRC rating is noted on the window or in product literature (e.g., for site-built fenestration), select the U-factor and SHGC value from Tables 4 and 14, respectively, in 2005 ASHRAE Fundamentals, Chapter 31. Select the highest U-factor and SHGC value among the values listed for the known window characteristics (e.g., frame type, number of panes, glass color, and presence of low-e coating). Note that the U- factor requirement applies to all fenestration while the SHGC only applies to the glazed portion.The following exceptions apply: a. An area-weighted average of fenestration products shall be permitted to satisfy the U-factor requirements; b. An area-weighted average of fenestration products>_50%glazed shall be permitted to satisfy the SHGC requirements; c. 15 square feet of glazed fenestration per dwelling unit shall be exempt from the U-factor and SHGC requirements, and shall be excluded from area-weighted averages calculated using a)and b),above: d. One side-hinged opaque door assembly up to 24 square feet in area shall be exempt from the U-factor requirements and shall be excluded from area-weighted averages calculated using a)and b),above: e. Fenestration utilized as part of a passive solar design shall be exempt from the U-factor and SHGC requirements, and shall be excluded from area-weighted averages calculated using a) and b), above. Exempt windows shall be facing within 45 degrees of true South and directly coupled to thermal storage mass that has a heat capacity>20 btu/ft1x°F and provided in a ratio of at least 3 sq.ft.per sq.ft.of South facing fenestration.Generally,thermal mass materials will be at least 2 in,thick. Effective for homes permitted starting 11/10/2012 Revised 9/10/2012 Page 4 of 16 ENERGY STAR Qualified Homes, Version 3 (Rev. 06) Thermal Enclosure System Rater Checklist Home Address: City: t+V l * State: 1.High-Performance Fenestration Must Builder Rater Correct Verified' Verified MIA 1.1 Prescriptive Path:Fenestration shall meet or exceed ENERGY STAR requirements 2 ❑ ❑ ❑ ❑ 1.2 Performance Path:Fenestration shall meet or exceed 2009 IECC requirements 2 ❑ ❑ ❑ ❑ 2.Quality-installed Insulation 21 Ceiling,wall,floor,and slab insulation levels shall comply with one of the following options: 2.1.1 Meet or exceed 2009 IECC levels 34.5 OR; ❑ ❑ ❑ ❑ 2.1.2 Achieve s 133%of the total UA resulting from the U-factors in 2009 IECC Table 402.1.3, excluding fenestration and per guidance in Footnote 3d,AND home shall achieve 5 50%fl of D D ❑ ❑ the infiltration rate in Exhibit 1 of the National Program Requirements 4.5 2.2 All ceiling,wall,floor,and slab insulation shall achieve RESNET-defined Grade I installation or, alternatively,Grade II for surfaces that contain a layer of continuous,air impermeable insulation ❑ ❑ ❑ ❑ R-3 in Climate Zones 1 to 4,a R-5 in Climate Zones 5 to 8 3.Fully-Aligned Air Barriers _,� 7 At each insulated location noted below,a complete air barrier shall be provided that is fully aligned with the insulation as follows: + ' •At interior or exterior surface of ceilings in Climate Zones 1-3;at interior surface of ceilings in Climate Zones 4-8.Also,include barrier at interior edge of attic eave in all climate zones using a wind baffle that extends to the full height of the insulation.Include a baffle in every bay or a tabbed baffle in each bay with a soffit vent that will also prevent wind washing of insulation in adjacent bays •At exterior surface of walls in all climate zones;and also at interior surface of walls for Climate Zones 4-8' •At interior surface of floors in all climate zones, including supports to ensure permanent contact and blocking at exposed edge e.s 3.1 Wallst0 3.1.1 Walls behind showers and tubs ❑ ❑ D 31.2 Wails behind fireplaces D ❑ D 31.3 Attic knee walls ❑ ❑ 31.4 Skylight shaft walls D ❑ ❑ 3.1.5 Wail adjoining porch roof ❑ ❑ ❑ 3.1.6 Staircase walls ❑ ❑ D 3.1.7 Double walls D ❑ ❑ 3.1.8 Garage rim/band joist adjoining conditioned space ❑ ❑ ❑ 31.9 All other exterior walls ❑ ❑ ❑ 3.2 Floors 32 1 Floor above garage ❑ D ❑ 3.2.2 Cantilevered floor ❑ ❑ ❑ 3.2.3 Floor above unconditioned basement or unconditioned crawlspace ❑ D ❑ 3.3 Ceilings10 3.31 Dropped ceiling/soffit below unconditioned attic ❑ 1 D 1 ❑ 3.12 All other ceilings D D ❑ 4.Reduced Thermal Bridging 4.1 For insulated ceilings with attic space above(i.e.,non-cathedralized),Grade I insulation extends to the inside face of the exterior wall below at these levels:CZ 1-5:2:R-21;CZ 6-8:a R-30" ❑ ❑ ❑ ❑ 4.2 For slabs on grade in CZ 4 and higher, 100%of slab edge insulated to>_R-5 at the depth specified by the 2009 IECC and aligned with thermal boundary of the walls 4,5 ❑ ❑ ❑ ❑ 4.3 Insulation beneath attic platforms(e.g.,HVAC platforms,walkways)2 R-21 in CZ 1-5;a R-30 in D D D ❑ CZ 6-8 4.4 Reduced thermal bridging at above-grade walls separating conditioned from unconditioned space(rim/band joists exempted)using one of the following options: 2' 4.4.1 Continuous rigid insulation,insulated siding,or combination of the two; z R-3 in Climate Zones 1 to 4,>R-5 in Climate Zones 5 to 8",15,OR; D D ❑ D 4.4.2 Structural insulated Panels(SIPs),OR; D ❑ ❑ ❑ 4.4.3 Insulated Concrete Forms(ICFs),OR; ❑ ❑ ❑ ❑ 4.4.4 Double-wall framing t6,OR; ❑ ❑ ❑ ❑ 4.4.5 Advanced framing,including all of the items below: 4.4.5a All comers insulated a R-6 to edge' ,AND; ❑ ❑ ❑ D 4.4.5b All headers above windows&doors insulated',AND; ❑ ❑ D ❑ 4.4.5c Framing limited at all windows&doors' ,AND; ❑ ❑ ❑ ❑ 4.4.5d All interior/exterior wall intersections insulated to the same R-value as the rest of the ❑ ❑ ❑ ❑ exterior wall 20,AND; 4.4.5e Minimum stud spacing of 16 in,o.c.for 2x4 framing in all Climate Zones and,in Climate ❑ ❑ ❑ ❑ Zones 5 through 8,24 in,o.c.for 2x6 framing Effective for homes permitted starting 11/10/2012 Revised 9/10/2012 Page 3 of 16 i Registry ID: Rating Number: 040-12 owc Certified Energy Rater: Matt Turcotte 1J�1+'� 121 Oak St Rating Date: 1/4/13 � �►, v Northampton,MA 01062 Rating Ordered For: Estimated Annual Energy Cost Confirmed 5 Stars Plus Use MMBtu Cost Percent 1� Confirmed Heating 30.0 $477 29% Uniform Energy Rating System Cooling 2.0 $101 6% 9Y 9 Ys Energy Efficient Hot Water 13.4 $189 11% 1 Star 1 Star Plus 2 Stars 2 Stars Plus 3 Stars 3 Stars Plus 4 Stars 4 Stars Plus 5 Stars 5 Stars Plus Lights/Appliances 20.0 $906 54% 500-401 400-301 300-251 250-201 200-151 150-101 100-91 1 90-86 85-71 70 or Less Photovoltaics -0.0 HERS Index: 46 Service Charges $0 0% Geni:fral Information" Total $1673 100% Conditioned Area: 1899 sq.ft. HouseType: Single-family detached Conditioned Volume: 23115 cubic ft. Foundation: More than one type Bedrooms: 3 This home meets or exceeds the minimum Mechanical Systems Features criteria for all of the following: Heating: Fuel-fired air distribution,Natural gas,95.0 AFUE. Water Heating: Instant water heater,Natural gas,0.94 EF,0.0 Gal. Cooling: Air conditioner,Electric,15.5 SEER. Duct Leakage to Outside: 11.00 CFM. Ventilation System: Balanced:HRV,67 cfm,72.0 watts. Programmable Thermostat: Heating:Yes Cooling:Yes Building Shell Features Ceiling Flat: R-58 Exposed Floor: R-32 Vaulted Ceiling: R-48,R-32 Window Type: U:0.28,SHGC:0.26 Above Grade Walls: U-0.035,R-21 Infiltration: Foundation Walls: R-12.0 Rate: Htg:382 Clg:382 CFM50 Slab: R-0.0 Edge,R-0.0 Under Method: Blower door test Lights and Appliance Features_ TITLE Percent Interior Lighting: 100.00 Range/Oven Fuel: Natural gas Company Percent Exterior Lighting: 100.00 Clothes Dryer Fuel: Electric Address Refrigerator(kWh/yr): 527.00 Clothes Dryer EF: 2.73 City,State,Zip Dishwasher Energy Factor: 1.00 Ceiling Fan(cfm/Watt): 0.00 Phone# The Home Energy Rating Standard Disclosure for this home is available from the rating provider. Fax# REM/Rate-Residential Energy Analysis and Rating Software v12.99 This information does not constitute any warranty of energy cost or savings. ©1985-2012 Architectural Energy Corporation,Boulder,Colorado.