24D-320 (10) ,03/07/2005 14:31 4135847504 CUNSTRUCT ASSUCIATES HAUL by/b'L
,de Compliance Report-Yale House Renovation-pop 9 of 1 I
Table 1017.2-Spaces with One Means of Egress
Use Group Maximum Occupant Load Maximum Travel Distance
R 10 75'
S 30 100'
Exception 1:Boiler rooms require two cgress doorways where area exceeds 500 SP and
individual thel-fired equipment exceeds 400,000 BTU input capacity. No boiler room exceeds
this area,therefore this exception does not apply,and only one doorway is required from
each boiler room.
1017.3 Size of doors:32"minimum width,80"minimum height. (Exceptions: Interior egress
doors withza dwelling units,29%"width,78"minimum height;no minimum width for storage
closets less than 10 SF;no width requirements for doors in R-2 which are not required for means
of egress.)
1017.4 Door hardware:Shall comply.
1021.0 Guards: Shall comply
1022.0 Handrails: Shall comply
1023.0 Exit Signs and Lights: Shall comply
1024.0 Means of Egress Lighting: Shall comply
1025.9 Fiore Escapes
1025.1.2 Existing foe escapes: Accepted as component of:means of egress
1025.1.4 Limitations.Shall not constitute more than 50%of required number of exits or exit
capacity. Note: 50%of required number of exits accommodated by internal stair, Second fire
escape provides a third means of egress over and above required exits.
10253 Construction
10253.2 Opening protectives:Doors and windows along fire escape to be protected with%
boor protectives. This would only apply to alterations,and none are being proposed along
the north fire escape. Where are alterations along the south fire escape,but this escape
provides a third means of egress which is an additional rather than a.required means of
egress. Therefore,it need not comply with this requirement.
Chapter 12-Xnterfior Environment
Room dimonsion,lighting and ventilation requirements shall comply.
1214.0 Sound Transmission Control in Residential Buildings
1214.2 Air-Borne noise: Walls,floorlceilings between units and units 8t common areas: STC 45
for air-bonne noise.
1214.3 Structure-borne sound: Floor-ceiling assemblies 11C 45.
Chapter 13-Energy Conservation
See Chapter 34,
.03/07/2005 14:31 413b841504 UU4Nb 1 NUU 1 A55UU1A l t5 F Atat !71/t�L
01yD _ JdO
�,n " Hobie Iselin, General Contractor
Construction Supvr. Lic.#039073
,rr
{ A r
faxt r a n S m
to: Tony Patillo
tax: 1587-1272
from: Hobie Iselin —36 Service Center, Northampton MA
Telephone #413.584-1224
date: FMarrh 7, 2005 Fax: L 13) 584-7504
fe: Code review for Round Hill Rd.
pages: 2
Hi Tony,
Attached is the page in question from the code report by Mary Kraus for Round Hill Rd.
The existing fire escape egress doors are single swing multi-pane french doors, untempered glass,
with no built-in weatherstripping in poor condition. I would like to replace these with similar doors in
the same jamb in the same opening, but with tempered, insulated glass and full weatherstripping.
Mary is of the opinion that the new doors would have to comply with the code requirement of% hour
rating. It seems logical to me to change the doors to make them more attractive, safer and more
energy efficient, but I won't change them if I will be required to make them solid fire rated doors.
Thanks for taking a look at this.
Hobie
® KRAUS-FITCH ARCHITECTS, INC.
Environmentally inspired design
73 ��
Yale House Renovation
88 Round Hill Road,Northampton,MA
Site Report— 1/21/05
Structural and framing:
• The new structural elements are installed according to plans and code requirements. This
includes LVL beams in attic, and beams and columns in all units.
• Rough framing is complete.
• Strapping is near completion.
Mechanical:
• Unit 1: 75%complete.
• Unit 2: duct installation complete.
• Unit 3: interior installation complete.
• Unit 4: interior installation complete.
Plumbing:
• Rough waste piping is complete.
• Supply piping complete in Unit 4.
Electrical:
• Rough electrical installation has begun in Unit 4.
Finish carpentry:
• Flooring installation is in progress in Unit 3.
Respectfully submitted,
/ Mary Kraus AIA
Principal Architect
110 Pulpit Hill Road,Amherst MA 01002 413.549.5799 Fax: 413.549.7918 www.krausfitch.com
1
KRAUS-FITCH ARCHITECTS, INC.
Environmentally inspired design
1/26/05
Addendum to Code Compliance Report — Yale House Renovation
88 Round Hill Road, Northampton, MA.
The following requirements shall be added to the Code Compliance Report dated 1/20/05:
Fire escapes:
♦ Both existing fire escapes shall be compliant with code requirements for loads. A structural
engineer shall be engaged to verify compliance.
Fire protective signaling systems:
♦ All fire detection devices in the S-1 storage areas(including both heat detectors and smoke
detectors) shall be wired to provide notification in R-2 areas above.
♦ Horn/strobes shall be placed in common areas.
110 Pulpit Hill Road,Amherst MA 01002 413.549.5799 Fax: 413.549.7918 www.krausfitch.com
o? � - Sad
® KRAUS-FITCH ARCHITECTS, INC.
Environmentally inspired design
TRANSMITTAL
PROJECT#: 04-29
DATE: 2/18/05
TO: Anthony Patillo, Building Commissioner RE: Yale House, 88 Round Hill Road
Building Inspections
2112 Main Street
Northampton, MA 01060
ENCLOSED:
NO: DATE: DESCRIPTION:
1 1/26/05 Addendum to Code Compliance Report
REMARKS:
I spoke with Hobie Iselin of Construct Associates on 1/25/05 to inform him of the issues,
reflected in the attached Addendum,that you had brought to my attention. He understood all the
issues and was prepared to address them as required.