Loading...
32A-255 (15) From:Office To:Dave Claxton Date:3/13/2006 Time:2:59:18 PM Page 6 of 6 903. 1.1 (1.c) TESTING CRITERIA SECTION 1 -Testing Criteria FIRE SPRINKLER SYSTEM-WET 1. Hydrostatically test all system piping at a pressure of 200 psi for two hours without a loss in pressure. 2. Opening of the inspectors test connection shall initiate an alarm at the main fire alarm panel within 90 seconds. 3. 2°drain test shall be conducted. Static and Residual pressures must be recorded on test certificate. 4. All supervisory switches shall be tested and shall register a trouble condition an the main alarm panel. FIRE SPRINKLER SYSTEM—DRY 1. Pnuematically test system at a pressure of 40 psi for 24 hr.Maximum pressure loss is 1 '/z psi. 2. Hydrostatically test at a pressure of 200 psi for two hours without a loss in pressure. 3. Conduct system operational test from inspectors test connection. Local alarm must sound within l minute. Central station must receive alarm and trouble signals. 4. Working test of dry valve. 5. Water delivery time to inspectors test:60 seconds FIRE ALARM SYSTEM All features,devices,components,and modes of operation shall be tested for acceptance in accordance with the code and NFPA 72. SECTION 2-Approval Requirements 1. Approval of local authorities is required. 2. All test certificates,as required by NFPA 13 and 72,are required to be provided by every fire protection contractor. 3. The sprinkler contractor shall inform Rybak Engineering when the system piping is roughed in and prior to installation of the ceilings. 4. Rybak Engineering will provide a certificate of completion for the fire sprinkler system only. The responsibility of other fire protection systems is by others. cram umce Io.DaveClaxton Date:3113/2006 Time:2:59:18 PM Page 5 of 6 903. 1.1 (1.b) SEQUENCE OF OPERATION WET SPRR-4nER SYSTEMS System operates automatically upon the fusing of a single fire sprinkler. Operational Sequence: 1. The activation of a single sprinkler will discharge water and close the contacts of a flow switch. 2. Closed contact on the flow switch will activate fire alarm system(upon 30 second delay). DRY SPR1NICER SYSTEM System operates automatically upon the fusing of a single fire sprinkler. Operational Sequence: 1. The activation of a single sprinkler will allow the air to exhaust the system and discharge water. 2. The dry valve will activate the system pressure switch- Water will be delivered to the activated sprinklers. Water delivery delay must not exceed 60 seconds. GENERAL NOTE: all supervisory and alarm contacts are to be relayed to the fire alarm panel. The main fire alarm panel is required to be supervised by a central station service. rrom:umce io:naveuaxton mate snsiluuo time:r.5a:iuvm t'agr3at d SECTION 4-Fire Protection Systems to be installed a) Water supply,fire mains and hydrants—existing 4"fire service and existing 4"standpipes to remain b) Automatic sprinkler systems— Floors 2,3,4,and 5 are fed by zone controls connected to the existing standpipe system. The first floor is fed by the existing first floor zone control located in the basement. The basement is to be fed from the existing basement zone control located in the basement riser room. Sprinklers in guest rooms are residential sprinklers. Sprinklers in all other areas are quick response standard spray. c) Fire alarm systems and components— The existing fire alarm system is extended to comply with 917.4.1. The existing system also provides fire suppression system supervision required by 923.0. d) Seismic considerations—all new systems require seismic design compliance. SECTION 5-Features Used in the Design Methodology a) Building occupant notification and evacuation procedures The building fire alarm system monitors the building fire sprinkler system and manual pull stations and other detectors. Activation of these initiating devices will activate a building wide fire alarm and require complete building activation- Work By Others b) The attic area is of noncombustible construction. Combustible wood planking shall be removed from the space to omit sprinkler protection. c) Installation of heat detectors located in the combustible concealed space above the Northampton Room located on the second floor. This area cannot be sprinklered without extensive demolition. Future renovation will require additional sprinklers. Haul.vuwc 1V.VQVC41aXlUll Late:611J12UW lime:413U:18PM Page 3 of 6 FIRE PROTECTION SYSTEMS NARRATIVE REPORTS The scope of this project consists of the installation of a complete fire sprinkler system,installed in accordance with NFPA 13. Sprinklers are provided in all areas excluding the following areas: 1. Combustible concealed space above the Northampton Room. 2. Attic Space. 3. Bathrooms under 55 sq ft within guest rooms. 4. All closets within guest rooms. The building was previously equipped with a partial sprinkler system and alarm system. These systems have been modified to provide full sprinkler protection. 903. 1.1 (1.a) BASIS (METHODOLOGY) OF DESIGN SECTION 1 -Building Description a) Building"Use"Group—Mixed"Use"R-1 &A-3 b) Total square footage of building(newly protected portion)56,800 sq ft total c) Building height—Approx.62' d) Number of floors above grade—5,first,second,third,fourth,and fifth e) Number of floors below grade—1,basement f) Square footage per floor(newly protected portion) Basement: 12,895 First: 11,804 Second: 9,407 Third: 7,655 Fourth: 7,537 Fifth: 7,502 g) Type(s)of occupancies(hazards):guest rooms,common rooms,mechanical room,banquet hall, meeting rooms,restaurant h) Hazardous material usage and storage—storage is not allowed in the attic i) High storage of commodities within a building usually over 12 R—none allowed SECTION 2-Applicable Laws,Regulations and Standards Note that this project was undertaken by the hotel for firesafety concerns and was not mandated by regulation. a) NFPA Standards and Edition used for design of each specific fire protection system - NFPA 13,2002 edition"Installation of Sprinkler Systems" - NFPA 72,2002 edition"National Fire Alarm Code" SECTION 3—Design Responsibility for Fire Protection Systems Fire Sprinkler System:Rybak Engineering,Inc. Fire Alarm: By owner rrom:umce io:uaveurwon Late:3!1312006 Time:2:59:18PM Page 2 of 6 Fire Sprinklers Retrofit Project Narrative Report for The Hotel Northampton Northampton,Massachusetts Fire Sprinkler System Engineer: Rybak Engineering,Inc. General Contractor 132 Forest Avenue pioneer Contractors Warren,Massachusetts 01083-0709 PO Box 1145 (413)436-5500 Northampton,MA 01061 413-586-5491 March 13,2006 ,Pioneer Contractors Pi Con,Inc. T P.O Box 1145 Northampton, MA. 01061 Voice 413-586-5491 Fax 413-527-5099 E-mail ioneercontrac@yahoo.com To: Anthony Patillo, Commissioner From: David Claxton Northampton Building Department Fax: 413-587-1272 Pages: Phone: 413-587-1240 Date: 3/20/2006 Re: The Hotel Northampton CC: Fire Sprinkler Project ❑ Urgent X For Review ❑ Please Comment ❑ Please Reply ❑ Please Recycle • Comments: Attached please find the Fire Sprinkler Plans for the above on Guest Floors 2 thru 5 noted as: FP-O, FP-1.1-2, FP-B.1 thru 3, FP-2.1 thru 2, &FP-3,4,5 Fire Narrative All prepared by Rybak Engineering, Inc, Fire Protection Engineers The scope of work entails: Removal of the existing suspended acoustical ceilings Installation of fire sprinkler piping &appliances as per drawings Fire Stopping as required Installation of new ceiling system A complete set of these documents has been sent to the Northampton Fire Department with the fire sprinkler permit application by Warehouse Mechanical Contractors. =off-(IV.If p�,Oy . ofItz� 4 .3.Rch nc r(16' o DEPARTMENT Of' 13U1LDr\1G 1NSPPcT1O1,S — 212 Main Strect ' Municipal Building Northampton, ATass. 01060 tip'O MCC 1 Z'S CO iVIP 1 N S ATTID N. M S URA-N CF A F IT)A�rlj.- . I Pioneer Contractors (li ansxljxrn�i ttcc _�ch-a--p,-�•�c�-paJ-pJ-a�sf-h>��ir��s�/-r�si�era�rt: P.O. Box 1145 Northampton, MA. 01061 {phone=') 413-5.86-5491 - (szr�t/ci t}•/stair./a p) do hereby cernfj under Lhc pains and penalties of perJury.., _hal (� ) I am an employer providing the tollowlne «-orkcr's cotnocns_EDo, coveragc Cor In) etnplovccs \vortDng on this job` Liberty Mutual Insurance WC5-31S-499822-054 6/30/06 (Insur-an Corer ,c�) (Pcbc; Nu_ •r) F::•pirzu on Dare) ( ) I am a sole proorletor, general con=dor or homeowner (ci:cie oee) and have hired the cooLT acLors listed below wbo have the following worker's cocnensation pokiest (iNf1IDC of ConmCiOr) (1nSt r311U^ COITIp1Tl}'/PGt)Ci � t1n1LC:) �_??)lidL•?n DIIC)' (Name of Coocmmor) Ras -anc; Company/Policy Number) (Ei-Dirat)on Due) (Name of Connacior) (Lnsuranc; Compan)•/PoUq N;rmb,-_r) (E_xpimdoo Datc) I (Name of Coatracaor) (Lasuranc_- Comrzffy/Poticy Numbs) - (Expira600 Date). (ntl�.ch bocal `UCCt irooc�-uO• to at ,j_iafortaadoo Pc-L iains to ay oo=--corz) . ( ) I am a sole proprietor and have no one worLaDg for me. ' ( ) I am..a home owDer performing all the work- myself NOTE:pl—tx-wire •bo cruplay Pcr on to&m,i.-,.-,= rrxiir-orz oo.d..clL:Z of ao(C O'1!`:7 L 'l-3'r"tII%%-Ev l Lbc bomoo'N•DCS r=u4=oC oo LS,--Cr-o,� tb,C_ L:oo( o_.c d=cd to tC .alployc3 uN c the kui;�_ r -.'�A,=(GL1 12-=1 5 ( )}.=-pPliation by n bomma-oc far:G _or pcnnit rt_y U_c 1c� nsyc of as a•.,foyer uod,d-Wor'r-ola Coaap__Lioo Aei t undcrL.,nd that a oopy or lhi,ml<mmt may tx r«�.n,•ded to Lba Daxrtmmc or Ind+ar,;.J nceem�orGo.or t+>;.,�.no=roc th. oova�c vcirCiion o�d th:t f it-rc to tccu=tovRZr�uodcy scclioa 25A of MGL 152 can(cd to the i iiim of c imioal prnallio ooaair. of•ync of up to S 1_�DO.OQ ancvcx iagn-isoomc=of up w ooc yc Lod a\-3 pw„hia in do focm of a Stop Wort Order and a fim of S 100.00 t d;y a&,i=aDt� For dy.•: -'�•�u+c only f Permit N mber Lot Sipn.1LUrL of Li Versionl.7 Commercial Building Permit May 15,2000 SECTION 10-STRUCTURAL PEER REVIEW(780 CMR 110,11) Independent Structural Engineering Structural Peer Review Required Yes No SECTION 11 -OWNER AUTHORIZATION-TO BE COMPLETED WHEN OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT Star Northampton, Inc. as Owner of the subject property hereby authorize Pioneer_ Contractors to act on my behalf, in all matters elative to work authorized by this building permit application. 2 (f^u �..-�-� -. 3/17/06 Signature of Owner Date i David Claxton as M"/Authonzed Agent hereby declare that the statements and information on the foregoing application are true and accurate, to the best of my knowledge and belief. Signed under the pains and penalties of pertury Print Name 3/17/06 Signature of Owner/Agent Date SECTION 12-CONSTRUCTION SERVICES 10.1 Licensed Construction Supervisor: Not Applicable ❑ Name of License Holder:,—-D,2,%i i_ri -A,_ P.1 g• k.an 017B90 License Number P_fl. Ri)< 1145, _Nnrt-h.am,ptnr-t4..._.tIA. .. .nl061. _. 1/19/0 i �Ict�L`� Address Expiration Date Sigridture Telephone SECTION 13 WORKERS'COMPENSATION INSURANCE AFFIDAVIT(M.G.L c.152,§25C(6)) Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result in the denial of the issuance of the b 'ding permit. Signed Affidavit Attached Yes No 0 Version 1.7 Commercial Building Permit May 15,2000 8. NORTHAMPTON ZONING Existing Proposed Required by Zoning This column to be tilled in by Building Department Lot Size Frontage Setbacks Front Side L: __. R.w_. ..._.' L:. ......... R:_... Rear .. Building Height Bldg. Square Footage - % Open Space Footage % (Lot area minus bldg&paved v parking) � #of Parking Spaces Fill: (volume&Location) A. Has a Special Permit/Variance/Findin ver been issued for/on the site? NO DONT KNOW YES Q IF YES, date issued: IF YES: Was the permit recorded at the Registry of Deeds? NO DONT KNOW YES IF YES: enter Book i Page and/or Document # B. Does the site contain a brook, body of water or wetlands? NO DON'T KNOW C) YES IF YES, has a permit been or need to be obtained from the Conservation Commission? Needs to be obtained (D Obtained Q , Date Issued: " C. Do any signs exist on the property? YES NO C) IF YES, describe size, type and location: D. Are there any proposed changes to or additions of signs intended for the property ? YES Q NO IF YES, describe size, type and location E. Will the construction activity disturb(clearing,grading,eexation, or filling)over 1 acre or is it part of a common plan that will disturb over 1 acre? YES 0 NO IF YES,then a Northampton Storm Water Management Permit from the DPW is required. . ` . ' Vooionl.7 Commercial Building Permit May 15,2000 SECTION 9-PROFESSIONAL DESIGN AND CONSTRUCTION SERVICES-FOR BUILDINGS AND STRUCTURES SUBJECT TO CONSTRUCTION CONTROL PURSUANT TO 780 CMR 116(CONTAINING MORE THAN 35,000 C.F.OF ENCLOSED SPACE) 9.1 Registered Architect: Not Applicable El Name(Registrant): Registration Number Address Expiration Date Signature Telephone 9.2 Registered Professional Engineer(s): Name Area of Responsibility Address �e`g­istr.tion Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone I Expiration Date 9.3 General Contractor Pioneer, Contractors__ _ Not Applicable Company Name: Responsible In Charge of Construction Address Signatu#16 Telephone 1 1 Version 1.7 Commercial Building Permit May 15,2000 SECTION 4-CONSTRUCTION SERVICES FOR PROJECTS LESS THAN 35,00Q CUBIC FEET OF ENCLOSED SPACE Interior Alterations dExisting Wall Signs ❑ Demolition❑ Repairs❑ Additions ❑ Accessory Building❑ Exterior Alteration ❑ Existing Ground Sign❑ New Signs❑ Roofing❑ Change of Use E3 Other El Brief Description 'Enter a brief description here. Installation of new acoustical suspended ceilings ' n Of Proposed Work: , Guest corridors 2nd, 3rd, 4th & 5th floors after installation of fire SECTION 5-USE GROUP AND CONSTRUCTION TYPE USE GROUP(Check as applicable) CONSTRUCTION TYPE A Assembly A-1 ❑ A-2 ❑ A-3 ❑ 1A ❑ ❑ A-4 ❑ A-5 ❑ 1B ❑ B Business ❑ 2A er E Educational ❑ 2B I ❑ F Factory ❑ F-1 ❑ F-2 ❑ 2C ❑ H High Hazard ❑ 3A ❑ I Institutional ❑ I-1 ❑ 1-2 ❑ 1-3 ❑ 3B ❑ M Mercantile ❑ / 4 ❑ R Residential R-1 R-2 ❑ R-3 ❑ 5A ❑ S Storage ❑ S-1 ❑ S-2 ❑ 5B ❑ U Utility El Specify: M Mixed Use ❑ Specify S Special Use ❑ Specify:, COMPLETE THIS SECTION IF EXISTING BUILDING UNDERGOING RENOVATIONS,ADDITIONS AND/OR CHANGE IN USE Existing Use Group: _.... ..... ..... .. ...... Proposed Use Group: . . Existing Hazard Index 780 CMR 34):1 . ._ _-..._ w , n _ Proposed Hazard Index 780 CMR 34): SECTION 6 BUILDING HEIGHT AND AREA BUILDING AREA EXISTING PROPOSED NEW CONSTRUCTION OFFICE USE ONLY Floor Area per Floor(sf) 1St ? _......_ _.._._ .._: e 2nd 2nd 3� . s _ 3rd 4 t 4tn Total Area(sf) _ Total Proposed New Construction�sf Total Height(ft) _ .. _..... .._.. .. _ __, Total Height ft 7.Water Supply(M.G.L.c.40,§54) 7.1 Flood,Zone Information: 7.3 Sewage D' posal System: Public Private E] Zone Outside Flood Zonej/ Municipal On site disposal system[] r Versionl.7 Commercial Building Permit May 15,2000 V City of Northampton t0is tit p Building rtment � " x 9 De P � �� �� ti � r 212 Main Street mo Room 100 ? Northampton, MA 01060 � �racturt Ifi phone 413;587-1240 Fax 413-587-1272 fct� ti � ian � i L�tICATION TO CONSTRUCT,REPAIR,RENOVATE,CHANGE THE USE OR OCCUPANCY OF,OR DEMOLISH ANY BUILDING OTHER THAN A ONE OR TWO FAMILY DWELLING SECTION 1 -SITE INFORMATION 1.1 Property Address: This section to be completed by office The Hotel Northampton ; Map Lot Unit 36 King St. Zane Overlay District F Elm St,District CS District' SECTION 2 PROPERTY OWNERSHIP/AUTHORIZED AGENT 2.1 Owner of Record: S-tar _Northampton IRC.- �� - 36- Kina- St.-;- Northampton, MA.MA. 01060 Name(Print) Current Mailing Address: L Signature (� Telephone 2.2 Authorized Aaent: ........._..... ........._.._ ._........_..........__ _ Pioneer Contractors ? P.O. Box 1145 Northampton, MA. 01061 „_._ r . _ ......__ ........ _..h� ......... Name(Print) Current Mailing Address '.._.. 41.3-5 8 6.-5491 . Signature Telephone SECTION 3-ESTIMATED CONSTRUCTION COSTS Item Estimated Cost(Dollars)to be Official Use Only completed by ermit applicant 1. Building (a)Building Permit Fee 2. Electrical (b)Estimated Total Cost of 26 10QU.00 Construction from 6 3. Plumbing i Building Permit Fee 4. Mechanical(HVAC) a_....... W__.,. . __. 5. Fire Protection 79_ .001.Ow0L] ` 6. Total=(1 +2+3+4+5) 123 000.00 Check Number ction For Official Use Only Building Permit Number Date Issued Signature: Building Commissioner/Inspector of Buildings Date File#BP-2006-0958 APPLICANT/CONTACT PERSON Pioneer Contractors ADDRESS/PHONE PO Box 1145 NORTHAMPTON (413)586-5491 PROPERTY LOCATION 36 KING ST MAP 32A PARCEL 255 001 ZONE CB THIS SECTION FOR OFFICIAL USE ONLY: PERMIT APPLICATION CHECKLIST ENCLOSED REQUIRED DATE ZONING FORM FILLED OUT Fee Paid Buildinp,Permit Filled out Fee Paid aZ 77 Typeof Construction: INSTALL NEW SUSPE DED CEILINGS IN GUEST CORRIDORS 2ND,3RD,4TH& 5TH FLRS AFTER INSTALLATION OF FIRE SPRINKLER New Construction Non Structural interior renovations Addition to Existing Accessory_Structure Buildinp,Plans Included: Owner/Statement or License 017890 3 sets of Plans/Plot Plan THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON INFO,04ATION PRESENTED: Approved Additional permits required(see below) PLANNING BOARD PERMIT REQUIRED UNDER:§ Intermediate Project: Site Plan AND/OR `Special Permit With Site Plan Major Project: Site Plan AND/OR Special Permit With Site Plan ZONING BOARD PERMIT REQUIRED UNDER: § Finding Special Permit Variance* Received&Recorded at Registry of Deeds Proof Enclosed Other Permits Required: Curb Cut from DPW Water Availability Sewer Availability Septic Approval Board of Health Well Water Potability Board of Health Permit from Conservation Commission Permit from CB Architecture Committee Permit from Elm Street Co 'ssion 3&,31100 O Signature of Building Official Date Note:Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning requirements and obtain all required permits from Board of Health,Conservation Commission,Department of public works and other applicable permit granting authorities. *Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of Planning&Development for more information. KM ST BP-2006-0958 CIS#: COMMONWEALTH OF MASSACHUSETTS ot °32 CITY OF NORTHAMPTON Lot: -001 Permit: Building Category: BUILDING PERMIT Permit# BP-2006-0958 Project# JS-2006-1430 Est. Cost: $123000.00 Fee: $615.00 PERMISSION IS HEREBY GRANTED TO: Const. Class: Contractor: License: Use Group: Pioneer Contractors 017890 Lot Size(sq.ft.): 72614.52 Owner: STAR NORTHAMPTON INC Zoning: CB Applicant: Pioneer Contractors AT. 36 KING ST Applicant Address: Phone: Insurance: PO Box 1145 (413) 586-5491 Workers Compensation NORTHAMPTONMA01061 ISSUED ON.41412006 0:00.00 TO PERFORM THE FOLLOWING WORK.-INSTALL NEW SUSPENDED CEILINGS IN GUEST CORRIDORS 2ND,3RD,4TH & 5TH FLRS AFTER INSTALLATION OF FIRE SPRINKLER POST THIS CARD SO IT IS VISIBLE FROM THE STREET Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector Underground: Service: Meter: Footings: Rough: Rough: House# Foundation: Driveway Final: Final: Final: Rough Frame: Gas: Fire Department Fireplace/Chimney: Rough: Oil: Insulation: Final: Smoke: Final: THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF ANY OF ITS RULES AND REGULATIONS. Certificate of Occupancy Signature: FeeType• Date Paid: Amount: Building 4/4/2006 0:00:00 $615.0010799 212 Main Street,Phone(413)587-1240,Fax: (413)587-1272 Building Commissioner-Anthony Patillo