32C-179 (45) • The FD connection for sprinkler system is to be 4" Storz connection with an
attached chain, in addition a sign reading "Fire Department Connection" in 3"
white letters on a red background is to be mounted above the connection.
Also an electric bell, which activates upon water flow, must be located above
this sign.
• The Fire Alarm/Sprinkler system must be supervised by either a direct
connection to the Northampton Public Safety Dispatch or by a UL listed
Central station.
• Carbon Monoxide detectors are required within ten feet of bedrooms and on
every habitable level of the structure.
• Stamped sprinkler plans need to be submitted to Fire Department as soon as
possible for approval.
• Fire alarm plans needs to be submitted for approval as soon as possible.
• Fire alarm and fire suppression work permits shall be obtained.
•Page 2
L
Northampton
/
Department
r I
Memorandum
To: Tony Patillo
From: Duane Nichols
Date: October 4, 2006
CC: Brian Duggan
Re: Sleep Med 332 Pleasant St.
Secondary to a review of the plans and fire protection narrative that was submitted to
me for review, I concur with the issuance of a building permit for this property subject
to the following conditions:
• A Fire Department Emergency Access Key Box is required on the exterior of
the structure near the entrance to control equipment; a red 120-candela
strobe light that actuates upon an alarm condition is required above the
Emergency Access Key Box.
• Engraved key tags are required for the keys in Emergency Access Key Box.
• A graphic representation of the structure must be installed at the Fire Alarm
Control Panel (FACP) and/or Fire Alarm Annunciator and/or Communicator.
• The Fire Alarm Control Panel and Fire Alarm Annunciator must be labeled
with red engraved signage with one-inch white lettering "Fire Alarm Control
Panel' and/or "Fire Alarm Annunciator". Also engraved signage listing all fire
alarm zone locations installed near panels.
•Page 1