32C-179 (45) • The FD connection for sprinkler system is to be 4" Storz connection with an attached chain, in addition a sign reading "Fire Department Connection" in 3" white letters on a red background is to be mounted above the connection. Also an electric bell, which activates upon water flow, must be located above this sign. • The Fire Alarm/Sprinkler system must be supervised by either a direct connection to the Northampton Public Safety Dispatch or by a UL listed Central station. • Carbon Monoxide detectors are required within ten feet of bedrooms and on every habitable level of the structure. • Stamped sprinkler plans need to be submitted to Fire Department as soon as possible for approval. • Fire alarm plans needs to be submitted for approval as soon as possible. • Fire alarm and fire suppression work permits shall be obtained. •Page 2 L Northampton / Department r I Memorandum To: Tony Patillo From: Duane Nichols Date: October 4, 2006 CC: Brian Duggan Re: Sleep Med 332 Pleasant St. Secondary to a review of the plans and fire protection narrative that was submitted to me for review, I concur with the issuance of a building permit for this property subject to the following conditions: • A Fire Department Emergency Access Key Box is required on the exterior of the structure near the entrance to control equipment; a red 120-candela strobe light that actuates upon an alarm condition is required above the Emergency Access Key Box. • Engraved key tags are required for the keys in Emergency Access Key Box. • A graphic representation of the structure must be installed at the Fire Alarm Control Panel (FACP) and/or Fire Alarm Annunciator and/or Communicator. • The Fire Alarm Control Panel and Fire Alarm Annunciator must be labeled with red engraved signage with one-inch white lettering "Fire Alarm Control Panel' and/or "Fire Alarm Annunciator". Also engraved signage listing all fire alarm zone locations installed near panels. •Page 1