bscinfo_513_slab_edge_insulation
BSC InformationSheet 513 Slab Edge Insulation for All Climates This Information Sheet has been prepared by Building Science Corporation for the Department of Energy’s Building America Program, a private/public partnership that develops energy solutions for new and existing homes. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States government or any agency thereof. For more information about Building America go to www.buildingamerica.gov Perimeter Insulation of Monolithic Slab-Grade Beam Insulation extends to bottom of grade beam Protection board over above grade portion of rigid insulation Protection board of non-water sensitive material and coated to control absorption of water Protective membrane adhered to slab and wrapped over top of insulation Insulation material non-moisture sensitive and not subject to degradation with ground contact Slab Edge Insulation For slab on grade construction, the slab edge represents a significant heat loss potential. This is important not only to the energy performance of a building but moisture management of the building as well. In climates where the average monthly temperature for the coldest month of the year goes below 45°F, the temperature of the slab perimeter may be below the dew point of interior air for a significant period of time. Even when condensation conditions are not present on the slab surface, relatively cool temperatures near an uninsulated slab edge will tend to elevate the local relative humidity. As relative humidity rises above acceptable human control conditions (30-60% RH), so too do the risks associated with mold and mildew, fungal growth, dust mites and other pests. This is a particular concern for carpeted slabs as these tend to also provide media and cover for “biologicals.” Adding insulation outside of the slab edge will allow the inside surface temperature of the slab perimeter to more closely track interior conditions thereby reducing the potential for condensation and elevated relative humidity. The strategies available for insulating the slab edge depend upon whether the slab on grade is 1) monolithic with a grade beam, or 2) supported on grade and independent of the foundation wall. When the slab is monolithic with a grade beam, the insulation must be installed to the exterior of the slab edge/grade beam and continue vertically to the bottom of the grade beam as shown in the example to the right. The insulation material must be appropriate for ground contact. XPS, rigid fiberglass and rock wool are examples of acceptable materials. The exterior insulation will need to be protected from impact damage during construction and, subsequently, the above grade portion must be protected from UV and impact damage on the above grade portion. BSC Information Sheet 513 for All Climates Slab edge insulation © buildingscience.com2 of 2 When the slab is independent from a perimeter foundation wall, insulation may be installed either on the exterior of the foundation wall or between the foundation wall and the slab. In order for the slab to be independent of the foundation wall, a bond break is needed between the slab, which is supported on grade, and the foundation wall that supports the exterior wall structure and its loads. Insulation at the vertical slab edge and under the slab perimeter provides this bond break. The diagram to the right shows and example of a slab on grade that is structurally and thermally isolated from the perimeter foundation wall. Limiting factors on the width of the slab edge insulation in this situation are determined by attachment of floor finishes and width of foundation wall needed to support the wall structure. Whenever insulation is used in contact with ground or near ground, appropriate insect control measures must be used. Appropriate measures will vary by location. Slab on Grade Independent of Perimeter Foundation Wall Slab is insulated vertically at the edge and horizontally at the perimeter or under the entire slab Rigid insulation provides bond break between slab and foundation wall Protective membrane adhered to both slab and top of foundation wall Suggestions for Further Research: “Understanding Basements,” Building Science Digest-103, www.buildingscience.com. “READ THIS: Before You Design, Build, or Renovate,” Building Science Primer-040, www.buildingscience.com. Lstiburek, Joseph W.; Builder’s Guide Series, Building Science Press, 2006.