10-016 (3) �4 The mast was analyzed based on the LFRD design specifications for Steel Hollow Structural Structures (AISC section 16.2). The mast is loaded by a combination of flexure and axial compression. The mast is 127" long, diameter =10 ", wall thickness = 0.19" and yield strength = 42 ksi The mast is not a compact section (D /t =57), K =2.1 (ref. Table C -C2.1) Flexural Analysis is based on Section 5.1, Equation 5.1 -2 applies. Axial Compression analysis is based on section 4.2. Euler buckling equation K =2.1. The combined loading analysis is based on section 7.1. 3 blowing the snow or for daily dumping at 60 Deg. Due to the variability of snow density, it can be difficult to relate snowfall depths directly to a force. The concept of water equivalent for a given snowfall is used to convert snow load to a force in pounds per square foot (lb/ ft2). The design load of 151b/ ft2 is equal to a water depth of 2.9 ". Listed below are data for a number of past extreme snow events showing both the snow depth accumulation and the water equivalent. Feb. 14, 2007 Northern VT: Maximum snow depth: 36in, Max water equivalent: 2in Dec. 11, 2008 Coastal New England: Ice storm, ice accumulations up to 1in. Dec. 20, 2009 Coastal New England: 18 -20in snow, 1 -1.5in water equivalent Feb. 1 -2, 2011 New England: 15 -20in snow, 1.5in max water equivalent Mar. 6 -7, 2011 Northern VT: 20 -30in snow, 2.5in max water equivalent The snowfall totals for these events were taken from the National Climate Data Center's Storm Event Data Base. The Water equivalents were taken from the National Weather Service Advance Hydrologic Prediction Service's archival data for 24hr observed precipitation. C. Tracker Structural Analysis The tracker support system, consisting of the mast and base bolts were designed to meet the requirements of the AISC Manual for Steel Construction, LFRD, 3rd edition. I2 2.3 Topographic factor Kzt = 1.0 2.4 Gust effector factor Gf =0.85 2.5 Enclosure classification is open 3 Internal pressure coefficient GCpi =0 4 (Table 27.3 -1) Velocity pressure exposure coefficient Kz =0.62 5 (Eq. 27.3 -1) Determine velocity pressure qz 6 (Fig. 27.4 -1) Determine external pressure coefficient based on tracker vertical angle 7 (Eq. 27.4 -3) Determine wind pressure p= qzGCN 5. (27.4.7) Minimum Design Wind Load p= 161b /ft2 for open buildings. We apply this load on the vertical projected area of the track er at a given angle from horizontal. Section 3.2 in Chapter 2 defines the basic load combinations and factors. 1. Some loads are not applicable 1. Live load L =0 2. Rain load Lr =0 3. Earthquake load not considered E =0 2. The load equations reduce to 1. 1.4D 2. 1.2D + 0.5S 3. 1.2D + 1.6S + 0.5W 4. 1.2D + 1.0W+ 0.5S 5. 1.2D + 0.2S 6. 0.9D +1.0W 7. 0.9D 3. Due to the design of the structure, snow will not accumulate and it will either blow off or slide off. The governing load equation is F =1.2D + 1.0W B. Snow Load The All Sun Solar tracker has been rated for a snow load of 151b /ft2. This is based on an extreme single event. Our analysis is based on the tracker having an active control system that will change the angle of the tracker to 60 Deg each morning. Snow does not accumulate due to wind ,Ntt AIIEarth Renewables, Inc. ��■■ t, 94 Harvest Lane, Williston, VT 05495 N �f��TUr{JIn�ST Phone 802- 872 -9600 'TRACKERS '° allearthrenewables.com Tracker wind and snow loading analysis using ASCE7 -10 (Drawing NET1809 RevB) A. Wind Analysis ASCE 7 does not specifically address solar trackers. The closest match is an open sided shed roof structure. Our analysis is based on the tracker having an active control system that will reduce the angle of the tracker with respect to the ground to less than or equal to 7.5 degrees in the event of a high wind event. The control system for the tracker will also reduce snow load on a frequent basis by dumping. Chapter 26 discusses the general requirements for MWFRS (Main Wind Force Resisting Structure. Figure 26.1 -1 directs us to Chapter 27 for the shed roof analysis. Our analysis is for a relatively flat urban setting with significant number of trees/ shrubs nearby. We do not include topographic effects or other site specific conditions. The following factors are from Chapter 26. 1. (Table 1.5 -1) Risk Category I - Low risk to human life in event of failure. 2. (26.5.1) Basic Wind Speed - Use site appropriate wind speed. 3. (26.6, Table 26.6 -1) Directionality Factor kd= 0.85, use load combinations in Section 2.3. 4. (26.7.2) Surface Roughness B - Urban conditions. 5. (26.7.3) Exposure Category B - Consistent with surface roughness B. 6. (26.7.4.1) Not applicable as we have open sided building. 7. (26.7.4.2) Not applicable. 8. (26.8) Not applicable. Kzt = 1.0 9. (26.9) Gust - Effect Factor Gf =0.85 for this analysis. 10. (26.10, Table 26.11 -1) Internal pressure coefficient GCpi =0 Chapter 27 is used to calculate the loads on the tracker using the requirements for a mono sloped, open sided structure. 1. (27.7.1) Part 1 applies 2. (27.1.2) The tracker is currently being tested to determine its dynamic response. 3. (27.1.3) The tracker is currently being tested to determine its dynamic response. 4. (27.2, Table 27.2 -1) This defines the relevant code sections. 1 Risk Category 1 2 Determine Wind load parameters 2.1 Wind directionality factor kd= 0.85 2.2 Exposure category B I I i 1 1 THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF REVISIONS ALLEARTH RENEWABLES, INC. ANY REPRODUCTION IN PART OR WHOLE WITHOUT REV. DESCRIPTION DATE APPROVED THE WRITTEN PERMISSION OF ALLEARTH RENEWABLES, INC IS PROHIBITED. — __ D D ■Ill [ 19' -6 3/4" ] 234.8 1 1 1 T 1 M_ 0000000000 1 1 e C 90° C [ 1 1' -5 "] �„ 137.1 [ 10' -1 1 3/4"] [ 10 "] [ 10' -7 3/41 — 131.8 010.0 127.8 B B Ip 1) The tracker controller automatically moves the tracker to the stowed position (horizontal) if the wind speed exceeds 30 mph for 5 seconds as measured by the anemometer located on the tracker. CAD GENERATED DRAWING, 2)Design ice /snow load = 151bf /ftA2. This is intended for single storm event as DO NOT ALLEARTH RENEWABLES the tracker control will execute specific actions to clear the accumulated snow MANUALLY UPDATE A A on a frequent / daily basis and snow will not accumulate on the panels for extended periods of time. AIIEarth Renewables S24 Tracker 3) Design wind speed = 1 10MPH at lOm height. DRAWN SHE PART# REV. B. BENNER 3/23/12 RESPONSIBLE ENG APPROVAL A NET1569 -S24 0001.REL SCALE CAD FILE NET 1569_Tracker_Mcmasi_Assembly SHEET 1 :40 FOLDER: C: \0_SW DATA\ 1 OF 1 8 I 7 1 6 ' 5 ' 4 I 3 2 1 1 8 I 7 6 I 5 4 4 I 3 I 2 I 1 THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OR HN Ns ALLEARTH RENENABLES. INC. ANY REPRODUCTION IN PART OR WHOLE WITHOUT E. DESCFMMH DATE ARP /MAE° THE W*ITTEN PERMISSION GEALLEARFH RENIEWABLE . INC. IS PROHIBITED A 31553 =.8 was 35 1002 APB A ftavisea l3r &p B.G -0.dS. wos cspC&0 =1.0 II/1/12 APB W _ 1 12.73" D •N ERN N ■' a n 4X X 1.063 Me�eeM!MI \,..s„ Fw D 111111111111 1.1 Y Projected Lv. Height ' � Fwgt ■IIIINIIII�I a\ 14- � ■ li�lI ■ � � X ti '� v — • I I. I ■ ■ICI \ I SCALE SECTION A -2 + FH---1 � Fv C Width Panel Panel Hgt Approx. A A C Model 1 2.73" (ft) Hgt (ft) to Base (ft) Wit (Ibf) W Y X FA1 FA2 20 21.67 16.25 11.50 2900 24 21.67 19.50 11.50 3100 Base Foundation Forces due to wind/ ice loads + dead loads .- Anchor Bolts Load Case Wind Speed Snow /Ice Angle a F,, (lbf) FH (lbf) oV FAT or FAO (Ibf) F - .. ! ,,I P, �4d ; mph Ibf /ft Deg min /max min /max Ibf U: °a 4 `. Wind (2,4) 95 0 7.5 - 21940/20030 3390/9310 854 : - ": a' .,,, t i ^ i Wind (3) 161bf /ft 28 - 30,520/33,620 3100 3200 B 8 = - . AEW4N4G.af . ■ R Snow (5) 0 I 15 0 4735 9470 0 -dcF p1E� _ ' I , NOTES: 1) Compressive loads are positive values. 2) Given forces are maximum values determined using multiple load combinations per ASCE 7 -10 Sec. 27.4.3 Exposure B, Kz =0.62, Kd =1, Kzt =1, h =20', kd =1 A UNLESS OTHERWISE SPECIFIED CAD GELIERASED DRAWING, A 3 ) F orces are calculated Per ASCE 7 -10 Sec. 27.4.7 DIMENSIONS ARE IN INCHES Do NOT A LLEA RTH RENEWABLES 4) The tracker controller automatically moves the tracker to the parked (a =0) position if the wind speed TOLERANCES ARE MANUALLY UPDATE exceeds 30 mph for 5 seconds as measured by the anemometer located on the tracker. +Y' X 030 , I An angle of 7.5° was chosen for the wind loading analysis to allow for installation of the tracker on a slope. xx , 015 NET1809 Tracker Wind and Snow Loads DO NOT 5) Design ice /snow load =15 Ibf /ftA2. This is intended for single storm event as the tracker control will execute DALE DRAWING N xxa / 00$ F « F specific actions to clear the accumulated snow on a frequent/ daily basis and snow will not accumulate 0 WAB° °'h 9/6/11 E RA „ INT • NET1809 a on the panels for extended periods of time. BY APPF D B INTERPRET DWG HH 3RD ANGLE RIOlECT/ON N1^ SCALE 6 1 OF 1 8 1 7 1 6 1 5 t 4 I 3 1 2 I 1 1 I 1 i 1 THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF REVISIONS ALLEARTH RENEWABLES, INC. ANY REPRODUCTION IN PART OR WHOLE WITHOUT REV. DESCRIPTION DATE APPROVED THE WRITTEN PERMISSION OF ALLEARTH RENEWABLES, INC IS PROHIBITED. -- -- -- -- C [ 16' -3 3/41 195.66 D 1 ■ , 1 M O: :.QQco 00 1 _ B 90° C �� C [ 10' -1 1 3/4 "] [11-51 131.80 137.11 [10 '] [10'- 73/4 "] 0 10.0 127.8 -. 1 B B 1 1) The tracker controller automatically moves the tracker to the stowed position (horizontal) if the wind speed exceeds 30 mph for 5 seconds as measured by the anemometer located on the tracker. CAD GENERATED NOTAWI "G" ALLEARTH RENEWABLES 2)Design ice /snow load = 151bf /ftA2. This is intended for single storm event as the tracker control will execute specific actions to clear the accumulated snow MANUALLY UPDATE A A on a frequent / daily basis and snow will not accumulate on the panels for extended periods of time. AIIEarth Renewables S20 Tracker 3) Design wind speed = 120MPH at 10m height. DRAWN ;ZE' PARTS REV. B. BENNER 3/27/12 N ET1 569 -S20 0001.REL RESPONSIBLE ENG APPROVAL A SHEET SCALE CAD FILE: NETI569 _Tracker_Minimast_Assembly of 1:40 FOLDER. C_ \O_SW DATA\ 1 o1 1 8 1 7 1 6 5 t 4 3 3 2 1 , :� tom iw- X - 0 Array Tracker n u ......v.nww ,.> v.u ....,vtw.,^wn i k Wire underground H Inordut ,00.11000, , SECTION 8 - CONSTRUCTION SERVICES 8.1 Licensed Construction Supervisor: Not Applicable ❑ Name of License Holder : Phillip Baunsgard CS -106113 License Number llEdward Ave. Southampton, Ma. 01073 6/7/2015 Address Expiration Date 413 247 - 6045 Signature Telephone t0 6 9. Re • istered Home Improvement Co a ctor: Not Applicable ❑ NorthEast Solar Design Assoc. 169641 Company Name Registration Number Ann Bronner 7/14/2013 Address Expiration Date 136 Elm St. Hatfield, Ma. 01038 Telephone 4132476045 SECTION 10- WORKERS' COMPENSATION INSURANCE AFFIDAVIT (M.G.L. c. 152, § 25C(6)) Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result in the denial of the issuance of the building permit. Signed Affidavit Attached Yes ❑ No ❑ 11. - Home Owner Exemption The current exemption for "homeowners" was extended to include Owner - occupied Dwellings of one (1) or two(2) families and to allow such homeowner to engage an individual for hire who does not possess a license, provided that the owner acts as supervisor. CMR 780, Sixth Edition Section 108.3.5.1. Definition of Homeowner: Person (s) who own a parcel of land on which he /she resides or intends to reside, on which there is, or is intended to be, a one or two family dwelling, attached or detached structures accessory to such use and/ or farm structures. A person who constructs more than one home in a two -year period shall not be considered a homeowner. Such "homeowner" shall submit to the Building Official, on a form acceptable to the Building Official, that he /she shall be responsible for all such work performed under the building permit. As acting Construction Supervisor your presence on the job site will be required from time to time, during and upon completion of the work for which this permit is issued. Also be advised that with reference to Chapter 152 (Workers' Compensation) and Chapter 153 (Liability of Employers to Employees for injuries not resulting in Death) of the Massachusetts General Laws Annotated, you may be liable for person(s) you hire to perform work for you under this permit. The undersigned "homeowner" certifies and assumes responsibility for compliance with the State Building Code, City of Northampton Ordinances, State and Local Zoning Laws and State of Massachusetts General Laws Annotated. Homeowner Signature SECTION 5- DESCRIPTION OF PROPOSED WORK (check all applicable) New House ❑ Addition ❑ Replacement Windows Alteration(s) I I Roofing Ti Or Doors 0 Accessory Bldg. ❑ Demolition ❑ New Signs [0] Decks [p Siding [0] Other [0] Brief Description of Proposed Work: Install 24 panel solar hacker in yard Alteration of existing bedroom Yes No Addin new bedroom Yes No Attached Narrative Renovating unfinished basement Yes No Plans Attached Roll - Sheet 6a. If New house and or addition to existing housing, complete the following: a. Use of building : One Family Two Family Other b. Number of rooms in each family unit: Number of Bathrooms c. Is there a garage attached? d. Proposed Square footage of new construction. Dimensions e. Number of stories? f. Method of heating? Fireplaces or Woodstoves Number of each g. Energy Conservation Compliance. Masscheck Energy Compliance form attached? h. Type of construction i. Is construction within 100 ft. of wetlands? Yes No. Is construction within 100 yr. floodplain Yes No j. Depth of basement or cellar floor below finished grade k. Will building conform to the Building and Zoning regulations? Yes No . I. Septic Tank City Sewer Private well City water Supply SECTION 7a - OWNER AUTHORIZATION - TO BE COMPLETED WHEN OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT , as Owner of the subject property hereby authorize to act on my behalf, in all matters relative to work authorized by this building permit application. Signature of Owner Date I, yl v� L � J l as Owner /Authorized Agent here y declar that the stateme is nd information on the foregoing application are true and accurate, to the best of my knowledge and belief. Signe• - :er - and penalties of perjury. t/u lil✓1�- Pri -"AM . 2 /.c/� r ue of Owner /rn / Date Section 4. ZONING All Information Must Be Completed. Permit Can Be Denied Due To Incomplete Information Existing Proposed Required by Zoning This column to be filled in by Building Department Lot Size Frontage Setbacks Front Side L: R: L: _ R: ,__ Rear Building Height Bldg. Square Footage Open Space Footage (Lot area minus bldg & paved parking) # of Parking Spaces Fill: (volume & Location) A. Has a Special Permit /Variance /Finding ever been issued for /on the site? NO 0 DON'T KNOW 0 YES 0 IF YES, date issued: IF YES: Was the permit recorded at the Registry of Deeds? NO 0 DON'T KNOW 0 YES 0 IF YES: enter Book Page and /or Document # B. Does the site contain a brook, body of water or wetlands? NO 0 DON'T KNOW 0 YES 0 IF YES, has a permit been or need to be obtained from the Conservation Commission? Needs to be obtained t Obtained O , Date Issued: C. Do any signs exist on the property? YES 0 NO O IF YES, describe size, type and location: D. Are there any proposed changes to or additions of signs intended for the property ? YES 0 NO IF YES, describe size, type and location: E. Will the construction activity disturb (clearing, grading, excavation, or filling) over 1 acre or is it part of a common plan that will disturb over 1 acre? YES 0 NO 0 IF YES, then a Northampton Storm Water Management Permit from the DPW is required. G cj Department use only ��2 City of Northampton Status of Permit: 13 1% Building Department Curb Cut/Driveway Permit 212 Main Street Sewer /Septic Availability Room 100 Water/Well Availability V-Q P NP�p' O N Northampton, MA 01060 Two Sets of Structural Plans phone 413- 587 -1240 Fax 413 - 587 -1272 Plot/Site Plans Other Specify APPLICATION TO CONSTRUCT, ALTER, REPAIR, RENOVATE OR DEMOLISH A ONE OR TWO FAMILY DWELLING SECTION 1 - SITE INFORMATION 1.1 Property Address: This section to be completed by office �q Map Lot Unit "C J A ' g UCc�� �diodin �� Zone Overlay District Elm St. District CB District SECTION 2 - PROPERTY OWNERSHIP /AUTHORIZED AGENT 2.1 Owner of Record: Kathleen Maiewski 218 Audubon Rd. Northampton, Ma 01060 Name (Print) Current Mailing Address: ��Q 413-539-4878 ( /CJIa , �. • Telephone Signature 2.2 Authorized Agent: 413-247-604 0 ,� 7 1 ( /C,,- 413 - 247 -6045 /� , N- Current Mailing Address: ®/u 413- 247 -6045 Signature Telephone SECTION 3 - ESTIMATED CONSTRUCTION COSTS Item Estimated Cost (Dollars) to be Official Use Only completed by permit applicant 1. Building (a) Building Permit Fee 2. Electrical (b) Estimated Total Cost of Construction from (6) 3. Plumbing Building Permit Fee 4. Mechanical (HVAC) 5. Fire Protection !� 6. Total = (1 + 2 + 3 + 4 + 5) 37,590 Check Number 353 Q'9a This Section For Official Use Only Building Permit Number: Date Issued: Signature: Building Commissioner /Inspector of Buildings Date File # BP- 2013 -0632 APPLICANT /CONTACT PERSON NORTHEAST SOLAR DESIGN ASSOCIATES LLC ADDRESS/PHONE 136 ELM ST HATFIELD (413) 247 -6045 0 PROPERTY LOCATION 218 AUDUBON RD MAP 10 PARCEL 016 001 ZONE RR(100)/WSP(100) /WP(26)/ THIS SECTION FOR OFFICIAL USE ONLY: PERMIT APPLICATION CHECKLIST ENCLOSED REQUIRED DATE ZONING FORM FILLED OUT Fee Paid Building Permit Filled out �� 3 Fee Paid�� Typeof Construction: INSTALL GROUND SOLAR ARRAY BEHIND GARAGE New Construction Non Structural interior renovations Addition to Existing Accessory Structure Building Plans Included: Owner/ Statement or License 104454 3 sets of Plans / Plot Plan THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON INFOydATION PRESENTED: j■Approved Additional permits required (see below) PLANNING BOARD PERMIT REQUIRED UNDER: § Intermediate Project: Site Plan AND /OR Special Permit With Site Plan Major Project: Site Plan AND /OR Special Permit With Site Plan ZONING BOARD PERMIT REQUIRED UNDER: § Finding Special Permit Variance* Received & Recorded at Registry of Deeds Proof Enclosed Other Permits Required: Curb Cut from DPW Water Availability Sewer Availability Septic Approval Board of Health Well Water Potability Board of Health Pecuiit from Conservation Commission Permit from CB Architecture Committee Permit from Elm Street Commission _ Permit DPW Storm Water Management Demolition Delay 2 7 /Z Signature of Building Official Date 1 Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning requirements and obtain all required permits from Board of Health, Conservation Commission, Department of public works and other applicable permit granting authorities. * Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of Planning & Development for more information. 218 AUDUBON RD BP- 2013 -0632 GIS #: COMMONWEALTH OF MASSACHUSETTS Map:Block: 10 - 016 CITY OF NORTHAMPTON Lot: -001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A) Category: Zoning Permit BUILDING PERMIT Permit # BP- 2013 -0632 Project # JS- 2013- 000538 Est. Cost: $37590.00 Fee: $225.00 PERMISSION IS HEREBY GRANTED TO: Const. Class: Contractor: License: Use Group: NORTHEAST SOLAR DESIGN ASSOCIATES LLC 104454 Lot Size(sq. ft.): 326133/2 Owner: Northeast Solar Design Assoc Zoning: RR(100)/WSP(100)/WP(26)/ Applicant: NORTHEAST SOLAR DESIGN ASSOCIATES LLC AT: 218 AUDUBON RD Applicant Address: Phone: Insurance: 136 ELM ST 413 247 -6045 Workers Com.ensation HATFIELDMA01038 ISSUED ON:12/7/2012 0:00:00 TO PERFORM THE FOLLOWING WORK:INSTALL GROUND SOLAR ARRAY BEHIND GARAGE POST THIS CARD SO IT IS VISIBLE FROM THE STREET Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector Underground: Service: Meter: Footings: Rough: Rough: House # Foundation: Driveway Final: Final: Final: Rough Frame: Gas: Fire Department Fireplace /Chimney: Rough: Oil: Insulation: Final: Smoke: Final: THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF ANY OF ITS RULES AND REGULATIONS. Certificate of Occupancy Signature: FeeType: Date Paid: Amount: Building 12/7/2012 0:00:00 $225.00 212 Main Street, Phone (413) 587 -1240, Fax: (413) 587 -1272 Louis Hasbrouck — Building Commissioner