Entire House d 1872 27710 27934 1494 1494
Other equip loads 0 660
Equip. @ 0.92 RSM 26307
Latent cooling 3593
TOTALS 1872 27710 29900 1494 1494
Printout certified by ACCA to meet all requirements of Manual J 7th Ed.
'�- '1' wrightsoft° Right - Suite® Universal 7.1.05 RSU07086 2012 - Oct -19 15:43:28
A( \\phfile\profiles$\rsisson\My Documents1320 -2 TURKEY HILL RD.,NORTHAMPTON,MA.rup Calc = MJ7 Ori Page 2
, ,
Load Short Form Job:
Date: Oct 19, 2012
wrlght»soft Entire House By:
Project Information
For:
320 -2 TURKEY HILL RD., NORTHAMPTON, MA
Design Information
Htg Clg Infiltration
Outside db ( °F) 0 87 Method Simplified
Inside db ( °F) 70 75 Construction quality Best
Design TD ( °F) 70 12 Fireplaces 0
Daily range - M
Inside humidity ( %) 50 50
Moisture difference (gr /Ib) 50 24
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make
Trade Trade
Model Cond
GAMA ID Coil
ARI ref no.
Efficiency 80 AFUE Efficiency 0 EER
Heating input 0 Btuh Sensible cooling 0 Btuh
Heating output 0 Btuh Latent cooling 0 Btuh
Temperature rise 0 °F Total cooling 0 Btuh
Actual air flow 1494 cfm Actual air flow 1494 cfm
Air flow factor 0.054 cfm /Btuh Air flow factor 0.053 cfm /Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.89
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft (Btuh) (Btuh) (cfm) (cfm)
KITCHEN 181 2343 3382 126 181
MASTER BATH 95 1658 1230 89 66
HALUCLOSETS(2) 117 401 120 22 6
1/2 BATH 24 82 25 4 1
MASTER BEDROOM 217 3259 3592 176 192
1 ST. FL. BEDROOM 1 264 7822 8558 422 458
DINING RM. 202 1186 318 64 17
2ND.FL.BEDROOM 2 264 5051 5734 272 307
2ND.FL.HALL 202 1919 1436 103 77
2ND.FL.BEDROOM 3 231 3383 3384 182 181
BASEMENT RM. 77 60'5 155 33 8
Printout certified by ACCA to meet all requirements of Manual J 7th Ed.
•�- -44- ryraghtsoft. Right -Suite® Universal 7.1.05 RSU07086 2012 - Oct -19 15:43:28
llphfifelprofifes$YsissonWy Documents1320 -2 TURKEY HILL RD.,NORTHAMPTON,MA.rup Calc = MJ7 Ori Page 1
Project Summary Job:
Date: Oct 19, 2012
• wrightsoft Entire House By:
Pro - ect Information
For:
320 -2 TURKEY HILL RD., NORTHAMPTON, MA
Notes:
Desi • n Information
Weather: Springfield Westover AFB, MA, US
Winter Design Conditions Summer Design Conditions
Outside db 0 °F Outside db 87 °F
Inside db 70 °F Inside db 75 °F
Design TD 70 °F Design TD 12 °F
Daily range M
Relative humidity 50 %
Moisture difference 24 gr /lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 25191 Btuh Structure 25395 Btuh
Ducts 2519 Btuh Ducts 2539 Btuh
Central vent (0 cfm) 0 Btuh Central vent (50 cfm) 660 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 27710 Btuh Use manufacturer's data n
Rate /swing multiplier 0.92
Infiltration Equipment sensible load 26307 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Best
Fireplaces 0 Structure 2786 Btuh
Ducts 0 Btuh
Heating Cooling Central vent (50 cfm) 807 Btuh
Area (ft 1872 1872 Equipment latent load 3593 Btuh
Volume (ft 17577 17577
Air changes /hour 0.30 0.20 Equipment total load 29900 Btuh
Equiv. AVF (cfm) 88 59 Req. total capacity at 0.70 SHR 3.1 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make
Trade Trade
Model Cond
GAMA ID Coil
ARI ref no.
(Efficiency KAEUF.Th Efficiency 0 EER
Heating input 0 Btuh Sensible cooling 0 Btuh
Heating output 0 Btuh Latent cooling 0 Btuh
Temperature rise 0 °F Total cooling 0 Btuh
Actual air flow 1494 cfm Actual air flow 1494 cfm
Air flow factor 0.054 cfm /Btuh Air flow factor 0.053 cfm /Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.89
Printout certified by ACCA to meet all requirements of Manual J 7th Ed.
-1-1-1- wrightscaft Right - Suite® Universal 7.1.05 RSU07086 2012 - Oct -19 16:00:37
ACCA \ \phfile\proflles$Vsisson \My Documents1320 -2 TURKEY HILL RO.,NORTHAMPTON,MA.rup Calc = MJ7 Ori Page 1
M {
INSURANCE COVERAGE:
I have a current liability insurance policy or its equivalent which meets the requirements of M.G.L. Ch. 112 Yes ❑ No ❑
If you have checked Yes, indicate the type of coverage by checking the appropriate box below:
A liability insurance policy Other type of indemnity ❑ Bond ❑
OWNER'S INSURANCE WAIVER: I am aware that the licensee flnaq not havR the insurance coverage required by Chapter 112 of the
Massachusetts General Laws, and that my signature on this permit application waivasthis requirement.
Check One Only
Owner ❑ Agent ❑
Signature of Owner or Owner's Agent
By checking this boxD, I hereby certify that all of the details and information I have submitted (or entered) regarding this application are true and
accurate to the best of my knowledge and that all sheet metal work and installations performed under the permit issued for this application will be
in compliance with all pertinent provision of the Massachusetts Building Code and Chapter 112 of the General Laws.
Duct inspection required prior to insulation installation: YES NO
Prngreye Ifl pPrtionC
natP CorlimPnts
final InepPetion
Date Comments
Type of License:
By aMaster 3 7 a I
Title ❑ Master - Restricted
City/Town ❑Journeyperson
Signature of Licensee
Permit #
❑Journeyperson- Restricted 3 7
License Number:
Fee $ ❑
Check at www maac dnviripl
Inspector Signature of Permit Approval
mmonwealth of Massachusetts
oci 25 2012 City Of Northampton
of • Sheet Metal Permit
� � - • r .�t' �� Permit # S/V / 3 02
5139.
Estimated Job Cost: $ � o Permit Fee: $ �� 6U
Plans Submitted: YES .)4 NO Plans Reviewed: YES NO
Business License # _ Applicant License #
Business Information: Property Owner / Job Location Information:
Name: N/lq n s_) QI L ( h I j i h . 0'4 "4-Ik Name: 13 41 4 )
I'�C
Street: a- ITC C � - 14....0 Street: a I c r k n i 1 # ?
City /Town: o U M of9 City /Town: Al Q r T i^ n'i A T• h
Telephone: LI 1 3 G -9 Telephone: 9 13 -,s 7 - ocITg
Photo I.D. required / Copy of Photo I.D. attached: YES NO
Staff Initial
J -1 / unrestricted license
J -2 / M -2- restricted to dwellings 3- stories or less and commercial up to 10,000 sq. ft. / 2- stories or less
Residential: 1 -2 family Multi- family Condo / Townhouses Other
Commercial: Office Retail Industrial Educational
Institutional Other
Square Footage: under 10,000 sq. ft. over 10,000 sq. ft. Number of Stories: Z
Sheet metal work to be completed: New Work: r Renovation:
HVAC Metal Watershed Roofing Kitchen Exhaust System
Metal Chimney / Vents Air Balancing
Provide detailed description of work to be done:
c S 4 ( ( - <f9 ry
Fees with Building Permit: $25.00 Residential, $50.00 Commercial. Fees for jobs without a Building Permit $6.00 per $1000
Minimum fees for jobs without Building Permit $50.00 Residential, $100.00 Commercial
File # SM- 2013 -0021
APPLICANT /CONTACT PERSON WALUNAS PLUMBING & HEATING INC
ADDRESS/PHONE 218C COLLEGE HIGHWAY (413) 529 -2675
PROPERTY LOCATION 320 TURKEY HILL RD - UNIT 2
MAP 34 PARCEL 036 001 ZONE
THIS SECTION FOR OFFICIAL USE ONLY:
r t4ail
PERMIT APPLICATION CHECKLIST
ENCLOSED REQUIRED DATE
ZONING FORM FILLED OUT
Fee Paid J
Building Permit Filled out ( Fee Paid 501 3
Tvpeof Construction: INSTALL 2 ZONE GAS AIR HEAT & AC
r i r C
0
New Construction ,
Non Structural interior renovations r ■,Z )
Addition to Existing
Accessory �C)
Accessory Structure / X.+ 1
Building Plans Included:
Owner/ Statement or License 3724 M
3 sets of Plans / Plot Plan
THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON
INFO TION PRESENTED:
pproved Additional permits required (see below)
PLANNING BOARD PERMIT REQUIRED UNDER : §
Intermediate Project : Site Plan AND /OR Special Permit with Site Plan
Major Project: Site Plan AND /OR Special Permit with Site Plan
ZONING BOARD PERMIT REQUIRED UNDER: §
Finding Special Permit Variance*
Received & Recorded at Registry of Deeds Proof Enclosed
Other Permits Required:
Curb Cut from DPW Water Availability Sewer Availability
Septic Approval Board of Health Well Water Potability Board of Health
Permit from Conservation Commission Permit from CB Architecture Committee
og. o IB E Street Co s 'ssion Permit DPW Storm Water Management
alp
Signature of : uilding • icial Date
Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning
requirements and obtain all required permits from Board of Health, Conservation Commission, Department
of public works and other applicable permit granting authorities.
* Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact the Office of
Planning & Development for more information.
320 TURKEY HILL RD - UNIT 2 SM- 2013 -0021
COMMONWEALTH OF MASSACHUSETTS
CITY OF NORTHAMPTON
GIS #: 11429 jo _ " ""' T
Map: 34
Block: 036 ■ -196: ' SHEETMETAL PERMIT
Lot: 001
6 s9 �..!� -�
Permit: SHEETMETAL N
Category: SHEETMETAL
Permit # SM- 2013 -0021 PERMISSION IS HEREBY GRANTED TO:
Project # JS -2013- 000434
Est. Cost: $10,000.00 Contractor: License: Expires:
Fee Charged: $25.00 WALUNAS PLUMBING & HEATI Sheetmetal - 3724 M 12/28/2013
Balance Due: $.00 Owner: BANAS MICHAEL P
of Fixtures: Applicant: WALUNAS PLUMBING & HEATING INC
DigSafe # _ AT: 320 TURKEY HILL RD - UNIT 2
UseGroup
ConstClass
ISSUED ON: AMENDED ON: EXPIRES ON:
TO PERFORM THE FOLLOWING WORK:
INSTALL 2 ZONE GAS AIR HEAT & AC *NEED COPY OF EQUIPMENT SELECTION*
THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF
ANY OF ITS RULES AND REGULATIONS.
Signature:
Fixtures:
Floor: Type: # of Fixtures Floor: Type: # of Fixtures
Fee Type: Receipt No: Date Paid: Check No: Amount:
Sheetmetal REC- 2013 - 001692 25- Oct -12 5230 $25.00
212 Main Street, Phone:(413) 587 -1240, Fax:(413) 587 -1272, Email :Ihasbrouck ®northamptonma.gov
GeoTMS® 2012 Des Lauriers Municipal Solutions, Inc.