MEANS OF EGRESS, OCCUPANCY:
Basement:
• All floors will have 2 means of egress
• Maximum occupancy allowable for 1s` floor: 30 per gross sq ft = 99
• Maximum occupancy allowable for 2" & 3rd` floor: 100 per gross sq ft = 30
• Panic hardware is not required for egress doors. (1017.4.2, less than 100
occupants).
• Exit signs and emergency lighting will be installed.
• Each exit door will be at least 36" wide.
HANDICAPPED ACCESSIBILITY:
We will spend more than 30% of the assessed value of the building.
The entry door will provide at grade access to the elevator lobby. The elevator
will access all floors except the attic. The attic will be for residential use and does
not need to be accessible because there are less than 20, group 2 units. Section
9.4
New toilet rooms will be built to meet accessible standards.
A LULA elevator is allowed because the building is less than 3000 square feet per
story. 28.12.1
All public areas will have accessible routes within the spaces. There is an
employee only area on the ls` and 2° floors that is not accessible. Employee only
areas are not governed by the AAB since they are not spaces available to the
general public, i.e. public use areas
All public stairs, corridors, and doors will be built to accessible standards
PARKING
No new parking is required
4 of 5
196 Pleasant Street Thomas Douglas Architects Inc
Code Review 136 West Street
Northampton, MA
413 -585 -0641
• New Pull stations will be installed at all exits from each floor.
• ADA Strobe units will be installed in the public bathrooms.
• New addressable smoke and heat detectors (automatic fire detection system) will be
installed throughout the entire building.
• New fire extinguishers will be installed in appropriate locations. 51b. ABC required
at exits based on NFPA standards relative to maximum travel distance. We will
install a sign above each extinguisher.
• A new red strobe light will be installed by the Pleasant Street front entrance at the
sidewalk level in a location acceptable to the Northampton Fire Department.
• A new Knox box will be installed by the Pleasant Street front entrance at the sidewalk
level in a location acceptable to the Northampton Fire Department. It will be
mounted 4.5' from grade and located on the exterior wall directly below the red
strobe light. It will contain keys, engraved key tags and contact numbers.
• The system will be supervised by a UL approved service company.
HEIGHT AND AREA LIMITATIONS:
• With Construction type IV, separated uses and sprinkler systems, all uses in the
buildings are within allowable height and area limitations. This type IV
construction is rated as a 1 hour assembly
FIRE SEPARATIONS:
• With a sprinkler system and heavy timber type IV construction:
• Fire separations required between M use and B use: 1 hour
• Fire separations required between B use and R2 use: 1 hour
• Corridor fire resistance rating A, B, M, R uses (1011.4): 0 hour
• Interior Stairway enclosures (1019): 2 hour for stairs connecting 4 stories or
more.
• This type IV construction is rated as a 1 hour assembly
FIRE RESISTANCE RATINGS OF EXTERIOR WALLS 602
Fire separation M R2 B
distance
Less than 5 feet 1 1 1
Greater than 30 0 0 0
3 of 5
196 Pleasant Street Thomas Douglas Architects Inc
Code Review 136 West Street
Northampton, MA
413 -585 -0641
Floor Existing Use Proposed Use Renov Total Allowable Height
ated Area and areas
Areas For type IV
construction
ls` floor A2r Tavern M Mercantile 2927 2982 Sprinkled
and Bar Hazard index 3 5 story 41,000
Hazard index 5
2 ❑d fl B Business B Business 2927 2927 Sprinkled
Hazard index 2 Hazard index 2 6 story 72,000
3rd fl B Business B Business 2927 2927 Sprinkled
Hazard index 2 Hazard index 2 6 story 72,000
Attic fl B Business R2 Residential 2062 2062 Sprinkled
Hazard index 2 Hazard index 2 5 story 41,000
Total Areas 10,898 10,898
SPRINKLER SYSTEMS:
• All floors of the building will be sprinkled:
FIRE ALARM SYSTEMS:
• The building will have a new fire alarm system installed on all floors.
• The Fire Alarm Control Panel will be located next to the first floor front entry door
• A new graphic representation will be located next to the Fire Alarm control Panel
(FACP). This panel will be an engraved label with 1" white letters on a red
background "Fire Alarm Control Panel" and list zones in 1/2" lettering.
• This fire protective signaling system (alarm control panel) will monitor the sprinklers
and smoke detectors for the renovated space.
• Horn /strobe units will be installed in all public areas. (917.4.1 and 917.5)
2 of 5
1 196 Pleasant Street Thomas Douglas Architects Inc
Code Review 136 West Street
Northampton, MA
413- 585 -0641
CODE REVIEW January 15, 2010
196 Pleasant Street
Northampton, Ma
Applicable Building Code: MA 780 CMR Seventh Addition
ZONING DISTRICT: Central Business
PROPOSED RENOVATIONS:
PROJECT DESCRIPTION:
• Interior renovations of entire building for business use
• Addition of a new rear exterior covered egress stair
• Renovations include:
• New LULA elevator
• New exit and emergency lights
• New mechanical, electrical, plumbing systems
• New Sprinklers for entire building
• New toilet rooms
Assessed $450,400
Value
Construction More than 30% of assessed value of buildings.
cost
Construction IV Heavy timber: columns and beams are solid wood 8" nominal
Type dimensions
Floor is 3" t &g solid wood decking with 2 layers 3/4" wood finish floor
Uses Mixed- separated
Building 43 feet to ridge
height
Fire Yes- the building will be fully sprinkled
suppression
system J I
Fire alarm Yes- a new system will be installed
system
1 of 5
196 Pleasant Street Thomas Douglas Architects Inc
Code Review 136 West Street
Northampton, MA
413 -585 -0641
MEANS OF EGRESS, OCCUPANCY:
Basement:
• All floors will have 2 means of egress
• Maximum occupancy allowable for ls` floor: 30 per gross sq ft = 99
• Maximum occupancy allowable for 2 " & 3rd` floor: 100 per gross sq ft = 30
• Panic hardware is not required for egress doors. (1017.4.2, less than 100
occupants).
• Exit signs and emergency lighting will be installed.
• Each exit door will be at least 36" wide.
HANDICAPPED ACCESSIBILITY:
We will spend more than 30% of the assessed value of the building.
The entry door will provide at grade access to the elevator lobby. The elevator
will access all floors except the attic. The attic will be for residential use and does
not need to be accessible because there are less than 20, group 2 units. Section
9.4
New toilet rooms will be built to meet accessible standards.
A LULA elevator is allowed because the building is less than 3000 square feet per
story. 28.12.1
All public areas will have accessible routes within the spaces. There is an
employee only area on the ls` and 2 " floors that is not accessible. Employee only
areas are not governed by the AAB since they are not spaces available to the
general public, i.e. public use areas
All public stairs, corridors, and doors will be built to accessible standards
PARKING
No new parking is required
4 of 5
196 Pleasant Street Thomas Douglas Architects Inc
Code Review 136 West Street
Northampton, MA
413 -585 -0641
• New Pull stations will be installed at all exits from each floor.
• ADA Strobe units will be installed in the public bathrooms.
• New addressable smoke and heat detectors (automatic fire detection system) will be
installed throughout the entire building.
• New fire extinguishers will be installed in appropriate locations. 51b. ABC required
at exits based on NFPA standards relative to maximum travel distance. We will
install a sign above each extinguisher.
• A new red strobe light will be installed by the Pleasant Street front entrance at the
sidewalk level in a location acceptable to the Northampton Fire Department.
• A new Knox box will be installed by the Pleasant Street front entrance at the sidewalk
level in a location acceptable to the Northampton Fire Department, It will be
mounted 4.5' from grade and located on the exterior wall directly below the red
strobe light. It will contain keys, engraved key tags and contact numbers.
• The system will be supervised by a UL approved service company.
HEIGHT AND AREA LIMITATIONS:
• With Construction type IV, separated uses and sprinkler systems, all uses in the
buildings are within allowable height and area limitations. This type IV
construction is rated as a 1 hour assembly
FIRE SEPARATIONS:
• With a sprinkler system and heavy timber type IV construction:
• Fire separations required between M use and B use: 1 hour
• Fire separations required between B use and R2 use: 1 hour
• Corridor fire resistance rating A, B, M, R uses (1011.4): 0 hour
• Interior Stairway enclosures (1019): 2 hour for stairs connecting 4 stories or
more.
• This type IV construction is rated as a 1 hour assembly
FIRE RESISTANCE RATINGS OF EXTERIOR WALLS 602
Fire separation M R2 B
distance
Less than 5 feet 1 1 1
Greater than 30 0 0 0
3 of 5
196 Pleasant Street Thomas Douglas Architects Inc
Code Review 136 West Street
Northampton, MA
413 -585 -0641
Floor Existing Use Proposed Use Renov Total Allowable Height
ated Area and areas
Areas For type IV
construction
1 floor A2r Tavern M Mercantile 2927 2982 Sprinkled
and Bar Hazard index 3 5 story 41,000
Hazard index 5
2 " fl B Business B Business 2927 2927 Sprinkled
Hazard index 2 Hazard index 2 6 story 72,000
3rd fl B Business B Business 2927 2927 Sprinkled
Hazard index 2 Hazard index 2 6 story 72,000
Attic fl B Business R2 Residential 2062 2062 Sprinkled
Hazard index 2 Hazard index 2 5 story 41,000
Total Areas 10,898 10,898
SPRINKLER SYSTEMS:
• All floors of the building will be sprinkled:
FIRE ALARM SYSTEMS:
• The building will have a new fire alarm system installed on all floors.
• The Fire Alarm Control Panel will be located next to the first floor front entry door
• A new graphic representation will be located next to the Fire Alarm control Panel
(FACP). This panel will be an engraved label with 1" white letters on a red
background "Fire Alarm Control Panel" and list zones in 'h" lettering.
• This fire protective signaling system (alarm control panel) will monitor the sprinklers
and smoke detectors for the renovated space.
• Horn /strobe units will be installed in all public areas. (917.4.1 and 917.5)
2 of 5
196 Pleasant Street Thomas Douglas Architects Inc
Code Review 136 West Street
Northampton, MA
413 -585 -0641
CODE REVIEW January 15, 2010
196 Pleasant Street
Northampton, Ma
Applicable Building Code: MA 780 CMR Seventh Addition
ZONING DISTRICT: Central Business
PROPOSED RENOVATIONS:
PROJECT DESCRIPTION:
• Interior renovations of entire building for business use
• Addition of a new rear exterior covered egress stair
• Renovations include:
• New LULA elevator
• New exit and emergency lights
• New mechanical, electrical, plumbing systems
• New Sprinklers for entire building
• New toilet rooms
Assessed $450,400
Value
Construction More than 30% of assessed value of buildings.
cost
Construction IV Heavy timber: columns and beams are solid wood 8" nominal
Type dimensions
Floor is 3" t &g solid wood decking with 2 layers 3/4" wood finish floor
Uses Mixed- separated
Building 43 feet to ridge
height
Fire Yes- the building will be fully sprinkled
suppression
system
Fire alarm Yes- a new system will be installed
system
1 01
I .
b „ ,� Crzt of in fl��m�rton 1.. = * *_
Y / /;; �6� z e
$ 4 .4. ji d ,�iassxchusctts , '-t
DEPARTMENT OF BUILDING INSPECTIONS ---: _ 1�
INSPECTOR 212 Main Street • Municipal Building
Northampton, MA 01060 ," ow 5
CONSTRUCTION CONTROL DOCUMENT
(for professional r- ngineers/Architects responsible for Entire Project)
Project Title: I q co PG Efts Acu 7 S 7 Date: (. 1 ti • (C)
Project Location: (16 PGEfS pJ 7 S f Map: 32 0 Parcel: I G Co Zone: G 13
Scope of Project: /N 7C 2 t D It. X. a v O V g T Ion, s
In accordance with the sixth edition Massachusetts State Building Code, 780 CMR SECTION 116.0:
I, Trio ►ti's Acs n o v a` �, 5 Mass. Registration Number bet 14
Being a registered professional Engineer /Architect hereby CERTIFY that I have prepared or directly
supervised the preparation of all design plans, computations and specifications concerning:
jEntire Project
for the above named project and that to the best of my knowledge, such plans, computations and
specifications meet the applicable provisions of the Massachusetts State Building Code, all acceptable
engineering practices and all applicable laws for the proposed project.
Furthermore, I understand and AGREE that I shall perform the necessary professional services to
determine that the above mentioned portions of the work proceed in accordance with the documents
approved for the building permit and shall be responsible for the following as specified in section 116.2.2:
1. Review of shop drawings, samples and other submittals of the contractor as required by the
construction documents as submitted for the building permit, and approval for the
conformance to the design concept.
2. Review and approval of the quality control procedures for all code - required controlled
materials.
3. Be present at intervals appropriate to the stage of construction to become generally familiar
with the progress and quality of the work and to determine, in general, if the work is being
performed in a manner consistent with the construction documents.
I shall submit periodically, in a form acceptable to the building official, a progress report together with
pertinent comments. Upon completion of the work, I shall submit to the building official a final report as
to the satisfactory completion and readiness of the project for occvyta, . _,
: 4 :
Signature and Seal of registered professional:
a �a � '+ '
Fax 413 -587 -1272 - phone 413 -587 -1240
Pioneer Contractors
Pi Con, Inc.
I P.O Box 1145
Northampton, MA. 01061
Voice 413 - 586 -5491
Fax 413 - 527 -5099
E -mail pioneercontracaC�.vahoo.com
Cell 413.626.7267
To: Anthony Patillo, Commissioner From: David Claxton
Northampton Building Department
Fax: 413 - 587 -1272 Pages: 15 & Plans & Check
Phone: 413- 587 -1240 Date: 1/18/2010
Re: 196 Pleasant St. CC:
❑ Urgent X For Review ❑ Please Comment ❑ Please Reply ❑ Please Recycle
• Comments:
Attached please find the following for interior build -out as per plans submitted:
-3 sets Plans— Thomas Douglas Architects dated 1/13/2010
-1 copy – Building Permit Application w/Workman's Comp. Ins. Affidavit
-1 copy– Construction control Affidavit—Thomas Douglas Architects
-2 copies —Code Review & Fire Narrative
-Check # 13836 for $2700.00
Please call w /questions.
Thanks. rtie--•
Northampton t=�
y @WIr C� f asaachnsctlss W
DEPARTMENT OF BUILDDtG INSPECTIONS _ ; W
•
• 212 Main Street Municipal Building e
• Northampton, Mass. 01060 ` r"
WORKER'S COMPENSATION INSURANCE Ai+'1tLUAVTT
Pioneer Contractors -
(licenseeiperwi ttee)
with a principal place of business/residence at:
•
•
P.O. Box ■• 11.11• .. u i 01.061 (phone) 586 5491
(str..t/ci ty /staihi p )
do hereby certify, under the pains and penalties of perjury, that:
(V I am an employer providing the following worker's compensation coverage for my
employees working on this job:
Wcc 5005957
Associated Employers Insurance f'g —_ —_ _ 6/
(:risu.r Corapany) (Policy Number) (Expiration Date)
( ) I am a sole proprietor, general contractor or homeowner (circle one) and have hired
the contractors listed below who have the following worker's compensation policies:
(Name of Contractor) (Insurance Company/Policy Number) (Epiration Date)
(Name of Contractor) (Insurance Company/Policy Number) (Ex Date)
(Nause of Contractor) (Insurance Company/Policy Number) (Expiranon Daze)
(Name of Contractor) (Insurance Company/Policy Number) (Expiration Date)
(attach additional sheet if naraa y to mc}udc information pertaining to all oo dractors)
( ) I am a sole proprietor and have no one working for me.
( ) I am a home owner performing all the work myself.
•
NOTE: please be aware that while bomcomscra who unploy pusoas to do mainframe, construction or repair work on a dwethng of
aot more than throe units is which the bomoowocr resides oc on tho g-ounas appurtenant thereto arc not gcocralty coca to be
msployn under tho worker nacapcssation Act (GL152,f3 1(5)), application by a homeowner fora Heroic oc permit may aro Y the
legal stoats of an ocaployar under tho Workcus Compaasation Act
I understand that a copy of this ctaiom,mt may be forwarded to tho Doportvoccet of Industrial Auidm& Ofoo of la uraocc for the
coverage verification and that failta to segue covcrago under scctioa 25A of MGL 152 can lead to the imposition of criminal penalties
consisting of a fine of up to S1,500.00 and/or imptisonmazL of up to one year and civil penattia in the form of a Stop Work Ordc and a
fmn of 5100.00 a day against too,
For dcpa al use only
f Permit Number _
`/� gyp# _ Lot #
Sips hu•e of Liccusce/Pcrm.i
• Srr3saan'� - r - _ - - --
Version1.7 Commercial Building Permit May 15, 2000
r•
SECTION 10- STRUCTURAL PEER REVIEW (780 CMR 110.11)
Independent Structural Engineering Structural Peer Review Required Yes 0 No 0
SECTION 11 - OWNER AUTHORIZATION - TO BE COMPLETED WHEN
OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT V 01/4.. CX--- Uk , as Owner of the subject property
hereby authorize RI c.N. , <+Z,' (", `��'� c ( to
act on my behalf, in all matters relative to work authorized by this building permit application.
1131 19
Signature of Owner Date
PWy1'e-Cc' (A/NrC/t 6( ta \Y c _ as Owncr /Authorized
Agent hereby declare that the statements and information on the foregoing application are true and accurate, to the best of my knowledge
and belief.
Signed under the pains and penalties of perjury.
Print Name
iwto
Signatur: of C nner /Agent Date
SECTION 12 - CONSTRUCTION SERVICES
10.1 Licensed Constructions Supervisor: Not Applicable ❑
Name of License Holder : %� C`� k ' (.....A3)c"'1 ( - 1SctO
License Number
9 b • , , y; t�.D , M4 ' nr Rio( ,q l IZ
Address Expiration Date
Signat re Telephone
SECTION 13 - WORKERS' COMPENSATION INSURANCE AFFIDAVIT (M.G.L. c. 152, § 25C(6))
Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result
in the denial of the issuance of the building permit.
Signed Affidavit Attached Yes No 0
Versionl.7 Commercial Building Permit May 15, 2000
SECTION 9- PROFESSIONAL DESIGN AND CONSTRUCTION SERVICES - FOR BUILDINGS AND STRUCTURES SUBJECT TO
CONSTRUCTION CONTROL PURSUANT TO 780 CMR 116 (CONTAINING MORE THAN 35,000 C.F. OF ENCLOSED SPACE)
9.1 Registered Architect:
l Ho t4S 4 U Co to S Not
Applicable ❑
Name (Registrant): 814
3 G W E 5 T 51" Wo R 1 H PrrA t iON, Registration Number
Address .31. 1 0
—
-� -• 413 5056641 Expiration Date
Signature Telephone
9.2 Registered Professional Engineer(s):
Name Area of Responsibility
Address Registration Number
Signature Telephone Expiration Date
Name Area of Responsibility
Address Registration Number
Signature Telephone Expiration Date
Name Area of Responsibility
Address Registration Number
Signature Telephone Expiration Date
Name Area of Responsibility
Address Registration Number
Signature Telephone Expiration Date
9.3 General Contractor
p c ry, e eAN vv ''; KS Not Applicable ❑
Company Name:
Th
Responsible In Charge of Construction
r
■• j 7a 1Ai • 10‘
Address
/ t� -1P9(
Sig ure b Telephone `_
Version1.7 Commercial Building Permit May 15, 2000
8. NORTHAMPTON ZONING A1.*
Existing Proposed Required by Zoning
This column to be filled in by
Building Department
Lot Size 5 t 0 0 N C /tie CA w„ fC
Frontage eC NC.
Setbacks Front T! G
Side L: R: L: NG R:
Rear 1kJ C
Building Height
41 F+ NG
Bldg. Square Footage 0861 I 84
Open Space Footage
(Lot area minus bldg & paved Sc �l N ('
parking)
# of Parking Spaces 0 N G
0
Fill: 0 N C
(volume & Location)
A. Has a Special Permit /Variance /Finding ever been issued for /on the site?
NO DON'T KNOW 0 YES Q
IF YES, date issued:
IF YES: Was the permit recorded at the Registry of Deeds?
NO 0 DON'T KNOW YES
IF YES: enter Book Page and /or Document #
B. Does the site contain a brook, body of water or wetlands? NO 0 DON'T KNOW (3 YES
IF YES, has a permit been or need to be obtained from the Conservation Commission?
Needs to be obtained Obtained , Date Issued:
C. Do any signs exist on the property? YES O NO 0
IF YES, describe size, type and location: SEE P 4 kr/IN& s
D. Are there any proposed changes to or additions of signs intended for the property ? YES 0 NO
IF YES, describe size, type and location: SEE p2 Avow
(oS
E. Will the construction activity disturb (clearing, grading, excavation, or filling) over 1 acre or is it part of a common plan
that will disturb over 1 acre? YES 0 NO
IF YES, then a Northampton Storm Water Management Permit from the DPW is required.
Version1.7 Commercial Building Permit May 15, 2000
SECTION 4- CONSTRUCTION SERVICES FOR PROJECTS LESS THAN 35,000
CUBIC FEET OF ENCLOSED SPACE
Interior Alterations f a Existing Wall Signs ❑ Demolition ❑ Repairs 0 Additions ❑ Accessory Building ❑
Exterior Alteration ❑ Existing Ground Sign ❑ New Signs ❑ Roofing ❑ Change of Use I$, Other ❑
Brief Description Enter a brief description here.
Of Proposed Work: / /V / Ctz IDA- 1 0 VA -T f DNS
SECTION 5 - USE GROUP AND CONSTRUCTION TYPE
USE GROUP (Check as applicable) CONSTRUCTION TYPE
A Assembly A -1 ❑ A -2 ❑ A -3 ❑ 1A I 0
❑ A -4 ❑ A -5 ❑ 1B ❑ 1
B Business JR 2A ❑
E Educational ❑ 2B I ❑
F Factory ❑ F -1 ❑ F -2 ❑ 2C ❑
H High Hazard ❑ 3 A ❑
1 Institutional ❑ 1 -1 ❑ 1 -2 ❑ 1 -3 ❑ 3B 1______U
M Mercantile 0 4 _ !'._ .
R Residential ❑ R -1 ❑ R -2 g R -3 ❑ 1 5A i L] - - (�
S Storage ❑ S -1 ❑ S -2 ❑ _ 5B 0
U Utility ❑ Specify:
M Mixed Use ❑ Specify:
S Special Use ❑ Specify: _ �
-- -i
COMPLETE THIS SECTION IF EXISTING BUILDING UNDERGOING RENOVATIONS, ADDITIONS AND /OR CHANGE IN USE {
Existing Use Group: A i r t Proposed Use Group: M 13 R.2..
Existing Hazard Index 780 CMR 34): 5 2 Proposed Hazard Index 780 CMR 34):3 22 _- 1
SECTION 6 BUILDING HEIGHT AND AREA __ __ _
BUILDING AREA EXISTING PROPOSED NEW CONSTRUCTION OFFICE USE ONLY
Floor Area per Floor (sf)
is' 2990 1st 2982
2nd 2927
2n 2927
3rd 2927 3rd 2927
4
4th 2062 4 2062
Total Area (sf) 10,906 Total Proposed New Construction (sf)
10,898
Total Height (ft) 43 ft to ridge
Total Height ft 43 ft to ridge
7. Wate S upply (M.G.L. c. 40, § 54) 7.1 Flood Zone Information: 7.3 Sewage Disposal System:
Public [ Private El Zone Outside Flood Zone Municipal l On site disposal system[]
Versionl.7 Commercial BuildingPermit May 1.5, 2000
De partment use on ly
City of Northampton Stt tus- (Permit:
Building Department CurbtlDriveway Permit
212 Main Street Seer/Septicc Availability
Room 100 t etee/Well actability
Northampton, MA 01060. Two t of Structural Rine
p
hone 413- 587r1240 Fax 413 -587 -1272 i� lot/8ite Plan
Other Specify
APPLICATION TO CONSTRUCT, REPAIR, RENOVATE, A THE USE OR OCCUPANCY OF, OR DEMOLISH ANY BUILDING
OTHER TFWA FAMILY DWELLING
SECTION 1 - SITE INFORMATION
1.1 Property Address: This section to be completed by office �I
196 Pleasant STreet, Northampton, MA Map Lot Unit
Zone Overlay District
Elm St. District CB District
SECTION 2 - PROPERTY OWNERSHIP /AUTHORIZED AGENT
2.1 Owner of Record:
Manhan Narrow, LLC , Thomas Douglas 136 West STreet, Northampton, MA
Name (Print) Current Mailing Address:
413 -585 -0641
Signature Telephone
2.2 Authorized Agent:
Thomas Douglas Architect same as above
Name (Print) Current Mailing Address:
Signature f Telephone
SECTION 3 - ESTIMATED CONSTRUCTION COSTS
Item Estimated Cost (Dollars) to be Official Use Only
completed by permit applicant
1. Building (a) Building Permit Fee
Z7 iW ' Gv
2. Electrical (b) Estimated Total Cost of
lPiP w Construction from (6)
3. Plumbing Building Permit Fee
4. Mechanical (HVAC) L` rt,p GO I
5. Fire Protection ,lxoo' oot
6. Total =,(1 + 2+ 3 + 4 + 5) (Aj(3, t , ti Check Number Af3 l0 _ -
/,, �1 4 / This Section For Official Use Only
r. "di •. emit ; i m. Date
Issued
Signature:
Building Commissioner /Inspector of Buildings Date
File # BP- 2010 -0668
APPLICANT /CONTACT PERSON PIONEER CONTRACTORS
ADDRESS /PHONE PO Box 1145 NORTHAMPTON (413) 586 -5491
PROPERTY LOCATION 196 PLEASANT ST
MAP 32C PARCEL 166 001 ZONE CB(100)/
THIS SECTION FOR OFFICIAL USE ONLY:
PERMIT APPLICATION CHECKLIST
ENCLOSED REQUIRED DATE
ZONING FORM FILLED OUT
Fee Paid
Building Permit Filled out /,�g6 � ��
Fee Paid � 0 }� &
Typeof Construction:_ RENOVATE INTERIOR
New Construction
Non Structural interior renovations
Addition to Existing
Accessory Structure
Building Plans Included: 4�
Owner/ Statement or License 017890 / �
3 sets of Plans / Plot Plan ' / // 142
THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON
INF RMATION PRESENTED:
Approved Additional permits required (see below)
PLANNING BOARD PERMIT REQUIRED UNDER:§
Intermediate Project: Plan AND /OR Special Permit With Site Plan
Major Project: Site Plan AND /OR Special Permit With Site Plan
ZONING BOARD PERMIT REQUIRED UNDER: §
Finding Special Permit Variance*
Received & Recorded at Registry of Deeds Proof Enclosed
Other Permits Required:
Curb Cut from DPW Water Availability Sewer Availability
Septic Approval Board of Health Well Water Potability Board of Health
Permit from Conservation Commission Permit from CB Architecture Committee
Permit from Elm Street Commission _ Permit DPW Storm Water Management
Demolition Delay
f/A l
ij3J Signature of Building Official Date
Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning
requirements and obtain all required permits from Board of Health, Conservation Commission, Department
of public works and other applicable permit granting authorities.
* Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of
Planning & Development for more information.
BP- 2010 -0668
GIS #: COMMONWEALTH OF MASSACHUSETTS
:T b CITY OF NORTHAMPTON
Lot: -001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS
Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A)
Category: renovation BUILDING PERMIT
Permit # BP- 2010 -0668
Project # JS- 2010- 000915
Est. Cost: $450000.00
Fee: $2700.00 PERMISSION IS HEREBY GRANTED TO:
Const. Class: Contractor: License:
Use Group: PIONEER CONTRACTORS 017890
Lot Size(sq. ft.): 5401.44 Owner: MANHAN NARROW LLC
Zoning: CB(100)/ Applicant: PIONEER CONTRACTORS
AT: 196 PLEASANT ST
Applicant Address: Phone: Insurance:
PO Box 1145 (413) 586 -5491 Workers
Compensation
NORTHAMPTONMA01061 ISSUED ON:2/4/2010 0:00:00
TO PERFORM THE FOLLOWING WORK: RENOVATE INTERIOR
POST THIS CARD SO IT IS VISIBLE FROM THE STREET
Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector
Underground: Service: Meter:
Footings:
Rough: Rough: House # Foundation:
Driveway Final:
Final: Final:
Rough Frame:
Gas: Fire Department Fireplace /Chimney:
Rough: Oil: Insulation:
Final: Smoke: Final:
THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF
ANY OF ITS RULES AND REGULATIONS.
Certificate of Occupancy Signature:
FeeType: Date Paid: Amount:
Building 2/4/2010 0:00:00 $2700.00
212 Main Street, Phone (413) 587 -1240, Fax: (413) 587 -1272
Building Commissioner - Anthony Patillo