32C-001 (3) Code Review Thomas Douglas Architects Inc
Dani Fine Photography, Northampton, MA 196 Pleasant St.
Northampton, MA
413 -585 -0641
709.2 Mechanical, Altered existing systems.
The following requirements will be met:
In mechanically ventilated spaces, existing mechanical ventilation systems that are
altered, reconfigured, or extended shall provide no less than 5 cfm per person of
outdoor air and not less than 15cfm of ventilation air per person.
711 and 607 Energy Conservation:
Level 1 and 2 alterations are permitted without requiring the entire building to
comply with the International Energy Conservation Code. Alterations (new
construction) shall comply with the International Energy Conservation Code.
The new replacement windows will have a maximum U value of 0.4
No changes are proposed to the building's existing front entry door. (All new front
entrance doors have a maximum U value of o.8)
No changes are proposed to the other building exterior doors.
This project: None of the existing exterior walls are being altered, so no new
insulation is required.
The existing roof is not being modified.
8o6 Accessibility
CMR 521
3.3. b. If the work costs sioo,000 or more, then the work being performed is
required to comply with 521 CMR. In addition, an accessible public entrance and
an accessible toilet room shall be provided.
3.3. If the work performed, including the exempted work, amounts to 3o% or
more of the full and fair cash value of the building, the entire building is required
to comply with 521 CMR.
The construction costs will NOT exceed 3o% of the assessed value of the entire
building. The tenant work area will be fully accessible. There are no existing or
proposed toilets.
Schedule:
Start construction spring 2012
Completion in 1 month
End of Document
5 of 5
Code Review Thomas Douglas Architects Inc
Dani Fine Photography, Northampton, MA 196 Pleasant St.
Northampton, MA
413 -585 -0641
building will be maintained. The building is fully sprinkled. No new fire
separations are required.
7 Fire alarm and detection:
A fire alarm system is installed throughout the building. Devices will be repaired
and replaced as required.
The existing building -wide system reports to a central station.
The existing building -wide system has horn strobes & pull stations in common
areas and exits.
705 Means of Egress 705.3.1.1 Single - exit buildings (and spaces)
One means of egress is compliant in this tenant space. The occupancy will be less
than 5o and travel distance does not exceed 75 feet.
705.3.1.2 Fire Escapes
None are proposed.
7 Panic Hardware
Panic hardware is only required for A uses with occupancies over ioo. This project
does not have those uses or occupancies.
705.5.1 Corridor Doors
The corridor outside of the tenant area is not required to be fire resistant.
705.5.2 Transoms
There are no existing transoms.
7 Other Corridor openings
Not applicable.
705.7 Means of Egress lighting
All means of egress shall have compliant exit signs. This project will include a new
exit sign placed at the tenant space exit.
705.7 Exit Signs
All means of egress shall have compliant egress lighting. This project will include
new emergency lighting placed as shown on the drawings.
705.9 Handrails
No stairs or handrails are in this work area.
705.9 Guards
No guards are in this work area.
4 of 5
Code Review Thomas Douglas Architects Inc
Dani Fine Photography, Northampton, MA 196 Pleasant St.
Northampton, MA
413 -585 -0641
Level 2 work requirements:
701.3 Compliance
The work area comprises less than 5o% of aggregate area of this floor. The work
area includes reconfiguration of the space, the addition of new doors, and the
reconfiguration of systems (HVAC). Most of this project will be classified as a level
2 project. Part of the project will be classified as a level i project. The alterations
will follow level 2 guidelines.
Areas:
The work area for this tenant space is 1,26o square feet.
The entire an floor of Thornes Market is 15,493 square feet.
Windows may be added without the light and ventilation requirements of the IBC
This project will have replacement windows installed in existing openings on the
exterior walls.
New electrical equipment must comply with section 708
This project will have some new electrical work.
Length of dead end corridors, comply with 705.6. None exist in this project.
Minimum ceiling height of newly created habitable and occupied spaces shall be 7
feet. This project has compliant ceiling heights.
703.2.1 Existing Vertical openings:
Other than existing windows, there are no vertical openings in this tenant space
703.4 Interior finishes:
Interior finishes: All newly installed wall and ceiling finishes will comply with the
IBC
7o4 Fire Protection:
704.2 Automatic sprinkler systems
• The building is fully sprinkled. Existing distribution will be modified with
the new wall locations.
704.1.1, 1018 Corridor Ratings
One of the proposed new walls will be a corridor wall for the public corridor
outside of this tenant space.
According to table 1018.1 his wall is required to have a o hour fire rating.
704.2.2.1 Mixed Uses
Table 508.4, IBC
Table 508.4 of the IBC does not require fire separations between B uses.
The proposed work area does not include any mixed uses. There is no change of
use groups for this space. The existing tenant separations within the overall
3 of 5
Code Review Thomas Douglas Architects Inc
Dani Fine Photography, Northampton, MA 196 Pleasant St.
Northampton, MA
413 -585 -0641
Fire Resistive Required Types of Building Element Type 3B
Construction, Table 601
Primary Structural o
Frame
Bearing walls, Exterior 2
Bearing walls, Interior o
Nonbearing walls and i
partitions, exterior
Nonbearing walls and o
partitions, interior
Floor construction and o
secondary members
Roof construction and o
secondary members
Work Area Method Calculations
See below for areas
Level i -work requirements:
602.1 Interior finishes: All newly installed wall and ceiling finishes shall comply
with the IBC
603 Fire Protection:
Alterations shall be done in a manner that maintains the level of fire protection
provided.
604 Means of Egress
Repairs shall be made in a manner that maintains the level of protection provided
for the means of egress.
6o6 Structural:
There are no structural changes in this project.
607 Energy Conservation:
See 711 below
2 of 5
Code Review Thomas Douglas Architects Inc
Dani Fine Photography, Northampton, MA 196 Pleasant St.
Northampton, MA
413 -585 -0641
CODE REVIEW APRIL 30, 2012
Dani Fine Photography
2nd Floor Tenant, #27o
Thornes Market
150 Main Street, Northampton, MA
Applicable Building Code: MA 780 CMR Eighth Addition
IBC, IEBC International EXISTING Building Code, 2009
ZONING DISTRICT: CB
PROPOSED RENOVATIONS:
PROJECT DESCRIPTION:
• Remove the existing Hair Salon
• Cap all plumbing for Hair Salon. There are no existing toilets in this space.
There is no proposed plumbing in this space.
• Install new interior walls, reception desk, and new entry door.
Use Groups
• No Change of use groups
• Existing uses
• B, Business
Construction Type
• 3B
Sprinkler System
• The building is fully sprinkled. Existing distribution will be modified with
the new wall locations.
Fire and Smoke Alarm & Detection
• A fire alarm system is installed throughout the entire building. It will be
upgraded and modified as necessary during this renovation.
According to the IEBC this renovation is being reviewed as:
Work Area Method, Chapter 4
1 of 5
REGISTERED ARCHITECTURAL AND ENGINEERING SERVICES
CONSTRUCTION CONTROL AFFIDAVIT
PROJECT NUMBER:
PROJECT TITLE: Dani Fine Photography
PROJECT LOCATION: 2nd floor, suite #270, 150 Main Street, Northampton, MA
NAME OF BUILDING: Thornes Market, Northampton, MA
SCOPE OF PROJECT: Interior renovations
In accordance with Section 116.0 of the Massachusetts State Building Code, I, Thomas G Douglas
Mass. Registration No. 8944 being a registered professional engineer /architect hereby certify that I have
prepared
or directly supervised the preparation of all design plans, computations and specifications concerning:
xx ENTIRE PROJECT xx ARCHITECTURAL STRUCTURAL
MECHANICAL FIRE PROTECTION ELECTRICAL
OTHER (specify)
For the above named project and that, to the best of my knowledge, such plans, computations and
specifications meet the applicable provisions of the Massachusetts State Building Code. All acceptable
engineering practices and all applicable laws for the proposed project.
I further certify that I shall perform the necessary professional services and be present on the construction
site on a regular and periodic basis to determine that the work is proceeding in accordance with the
documents approved for the building permit and shall be responsible for the following as specified in
Section 116.2
1. Review, for conformance to the design concept, shop drawings, samples and other submittals which are
submitted by the contractor in accordance with the requirements of the construction documents.
2. Review and approval of the quality control procedures for all code - required materials.
3. Be present at intervals appropriate to the stage of construction to become, generally familiar with the
progress and quality of the work and to determine, in general, if the work is being performed in a manner
consistent with the construction documents.
Pursuant to Section 116.4, I shall submit periodically, a progress report together with pertinent comments
to the Building Department. Upon Completion of the Work, I shall submit a final report as to the
satisfactory completion and readiness of the project for occupancy.
ORIGINAL SIGNATURE I 1 VV 1 ; , o l
SEAL
DATE April 30, 2012
Code Review Thomas Douglas Architects Inc
Dani Fine Photography, Northampton, MA 196 Pleasant St.
Northampton, MA
413 -585 -0641
709.2 Mechanical, Altered existing systems.
The following requirements will be met:
In mechanically ventilated spaces, existing mechanical ventilation systems that are
altered, reconfigured, or extended shall provide no less than 5 cfm per person of
outdoor air and not less than 15cfm of ventilation air per person.
711 and 607 Energy Conservation:
Level 1 and 2 alterations are permitted without requiring the entire building to
comply with the International Energy Conservation Code. Alterations (new
construction) shall comply with the International Energy Conservation Code.
The new replacement windows will have a maximum U value of 0.4
No changes are proposed to the building's existing front entry door. (All new front
entrance doors have a maximum U value of o.8)
No changes are proposed to the other building exterior doors.
This project: None of the existing exterior walls are being altered, so no new
insulation is required.
The existing roof is not being modified.
8o6 Accessibility
CMR521
3.3. b. If the work costs sioo,000 or more, then the work being performed is
required to comply with 521 CMR. In addition, an accessible public entrance and
an accessible toilet room shall be provided.
3.3. If the work performed, including the exempted work, amounts to 3o% or
more of the full and fair cash value of the building, the entire building is required
to comply with 521 CMR.
The construction costs will NOT exceed 3o% of the assessed value of the entire
building. The tenant work area will be fully accessible. There are no existing or
proposed toilets.
Schedule:
Start construction spring 2012
Completion in 1 month
End of Document
5 of 5
Code Review Thomas Douglas Architects Inc
Dani Fine Photography, Northampton, MA 196 Pleasant St.
Northampton, MA
413 -585 -0641
building will be maintained. The building is fully sprinkled. No new fire
separations are required.
7 Fire alarm and detection:
A fire alarm system is installed throughout the building. Devices will be repaired
and replaced as required.
The existing building -wide system reports to a central station.
The existing building -wide system has horn strobes & pull stations in common
areas and exits.
705 Means of Egress 705.3.1.1 Single - exit buildings (and spaces)
One means of egress is compliant in this tenant space. The occupancy will be less
than 5o and travel distance does not exceed 75 feet.
705.3.1.2 Fire Escapes
None are proposed.
7 Panic Hardware
Panic hardware is only required for A uses with occupancies over ioo. This project
does not have those uses or occupancies.
705.5.1 Corridor Doors
The corridor outside of the tenant area is not required to be fire resistant.
705.5.2 Transoms
There are no existing transoms.
7 Other Corridor openings
Not applicable.
7 Means of Egress lighting
All means of egress shall have compliant exit signs. This project will include a new
exit sign placed at the tenant space exit.
705.7 Exit Signs
All means of egress shall have compliant egress lighting. This project will include
new emergency lighting placed as shown on the drawings.
705.9 Handrails
No stairs or handrails are in this work area.
705.9 Guards
No guards are in this work area.
4 of 5
Code Review Thomas Douglas Architects Inc
Dani Fine Photography, Northampton, MA 196 Pleasant St.
Northampton, MA
413 -585 -0641
Level 2 work requirements:
701.3 Compliance
The work area comprises less than 5o% of aggregate area of this floor. The work
area includes reconfiguration of the space, the addition of new doors, and the
reconfiguration of systems (HVAC). Most of this project will be classified as a level
2 project. Part of the project will be classified as a level 1 project. The alterations
will follow level 2 guidelines.
Areas:
The work area for this tenant space is 1,260 square feet.
The entire 2nd floor of Thornes Market is 15,493 square feet.
Windows may be added without the light and ventilation requirements of the IBC
This project will have replacement windows installed in existing openings on the
exterior walls.
New electrical equipment must comply with section 708
This project will have some new electrical work.
Length of dead end corridors, comply with 705.6. None exist in this project.
Minimum ceiling height of newly created habitable and occupied spaces shall be 7
feet. This project has compliant ceiling heights.
703.2.1 Existing Vertical openings:
Other than existing windows, there are no vertical openings in this tenant space
703.4 Interior finishes:
Interior finishes: All newly installed wall and ceiling finishes will comply with the
IBC
704 Fire Protection:
704.2 Automatic sprinkler systems
• The building is fully sprinkled. Existing distribution will be modified with
the new wall locations.
704.1.1, 1018 Corridor Ratings
One of the proposed new walls will be a corridor wall for the public corridor
outside of this tenant space.
According to table ioi8.1 his wall is required to have a o hour fire rating.
704.2.2.1 Mixed Uses
Table 508.4, IBC
Table 508.4 of the IBC does not require fire separations between B uses.
The proposed work area does not include any mixed uses. There is no change of
use groups for this space. The existing tenant separations within the overall
3 of 5
Code Review Thomas Douglas Architects Inc
Dani Fine Photography, Northampton, MA 196 Pleasant St.
Northampton, MA
413 -585 -0641
Fire Resistive Required Types of Building Element Type 3B
Construction, Table 6m
Primary Structural o
Frame
Bearing walls, Exterior 2
Bearing walls, Interior o
Nonbearing walls and 1
partitions, exterior
Nonbearing walls and o
partitions, interior
Floor construction and o
secondary members
Roof construction and o
secondary members
Work Area Method Calculations
See below for areas
Level i -work requirements:
602.1 Interior finishes: All newly installed wall and ceiling finishes shall comply
with the IBC
603 Fire Protection:
Alterations shall be done in a manner that maintains the level of fire protection
provided.
604 Means of Egress
Repairs shall be made in a manner that maintains the level of protection provided
for the means of egress.
6o6 Structural:
There are no structural changes in this project.
607 Energy Conservation:
See 711 below
2 of 5
Code Review Thomas Douglas Architects Inc
Dani Fine Photography, Northampton, MA 196 Pleasant St.
Northampton, MA
413 -585 -0641
CODE REVIEW APRIL 30, 2012
Dani Fine Photography
2nd Floor Tenant, #27o
Thornes Market
150 Main Street, Northampton, MA
Applicable Building Code: MA 780 CMR Eighth Addition
IBC, IEBC International EXISTING Building Code, 2009
ZONING DISTRICT: CB
PROPOSED RENOVATIONS:
PROJECT DESCRIPTION:
• Remove the existing Hair Salon
• Cap all plumbing for Hair Salon. There are no existing toilets in this space.
There is no proposed plumbing in this space.
• Install new interior walls, reception desk, and new entry door.
Use Groups
• No Change of use groups
• Existing uses
• B, Business
Construction Type
• 3B
Sprinkler System
• The building is fully sprinkled. Existing distribution will be modified with
the new wall locations.
Fire and Smoke Alarm & Detection
• A fire alarm system is installed throughout the entire building. It will be
upgraded and modified as necessary during this renovation.
According to the IEBC this renovation is being reviewed as:
Work Area Method, Chapter 4
1 of 5
REGISTERED ARCHITECTURAL AND ENGINEERING SERVICES
CONSTRUCTION CONTROL AFFIDAVIT
PROJECT NUMBER:
PROJECT TITLE: Dani Fine Photography
PROJECT LOCATION: 2 floor, suite #270, 150 Main Street, Northampton, MA
NAME OF BUILDING: Thornes Market, Northampton, MA
SCOPE OF PROJECT: Interior renovations
In accordance with Section 116.0 of the Massachusetts State Building Code, I, Thomas G Douglas
Mass. Registration No. 8944 being a registered professional engineer /architect hereby certify that I have
prepared
or directly supervised the preparation of all design plans, computations and specifications concerning:
xx ENTIRE PROJECT xx ARCHITECTURAL STRUCTURAL
MECHANICAL FIRE PROTECTION ELECTRICAL
OTHER (specify)
For the above named project and that, to the best of my knowledge, such plans, computations and
specifications meet the applicable provisions of the Massachusetts State Building Code. All acceptable
engineering practices and all applicable laws for the proposed project.
I further certify that I shall perform the necessary professional services and be present on the construction
site on a regular and periodic basis to determine that the work is proceeding in accordance with the
documents approved for the building permit and shall be responsible for the following as specified in
Section 116.2
1. Review, for conformance to the design concept, shop drawings, samples and other submittals which are
submitted by the contractor in accordance with the requirements of the construction documents.
2. Review and approval of the quality control procedures for all code - required materials.
3. Be present at intervals appropriate to the stage of construction to become, generally familiar with the
progress and quality of the work and to determine, in general, if the work is being performed in a manner
consistent with the construction documents.
Pursuant to Section 116.4, 1 shall submit periodically, a progress report together with pertinent comments
to the Building Department. Upon Completion of the Work, I shall submit a final report as to the
satisfactory completion and readiness of the project for occupancy.
ORIGINAL SIGNATURE ! y '\/1 ,
SEAL
DATE April 30, 2012
CITY OF NORTHAMPTON
Construction Debris Affidavit
In accordance with the provisions of MG.L. c. 40 § 54, all debris resulting from any work
covered by a Building Permit shall be disposed of in a properly licensed disposal facility,
as defined by M.G.L. c. 111 § 150A. ;�,
Address of Work: 6V/ E ��� 7i / rz- /v 16
The debris will be transported by: /7 ier G L. 3 &-r
The debris will be received at: /747 ' V Q vfri/
Signature of Permit Applicant
Date
Building Permit Number:
The Commonwealth of Massachusetts
Department of Industrial Accidents
Office of Investigations
600 Washington Street
= '` Boston, MA 02111 •
www.mass.gov /dia
Workers' Compensation Insurance Affidavit: Builders / Contractors /Electricians /Plumbers
Applicant Information Please Print Legibly
Name ( Business /Organization/Individual):
Address:
City /State /Zip: Phone #:
Are you an employer? Check the appropriate box: Type of project (required):
1. I am a employer with 4. El I am a general contractor and I
6. ❑ New onstruction
employees (full and/or part- time).* have hired the sub - contractors
2. ❑ I am a sole proprietor or partner- listed on the attached sheet. 7. emodeling
ship and have no employees These sub- contractors have g. Demolition
working for me in any capacity. employees and have workers' 9. ❑ Building addition
[No workers' comp. insurance comp. insurance.
required.] 5. ❑ We are a corporation and its 10.0 Electrical repairs or additions
3. ❑ I am a homeowner doing all work
officers have exercised their 11. Plumbing repairs or additions
myself. [No workers' comp. right of exemption per MGL 12.E] Roof repairs
insurance required.] t c. 152, § 1(4), and we have no
employees. [No workers' 13. ❑ Other
comp. insurance required.]
*Any applicant that checks box #1 must also fill out the section below showing their workers' compensation policy information.
t Homeowners who submit this affidavit indicating they are doing all work and then hire outside contractors trust submit a new affidavit indicating such.
Contractors that check this box must attached an additional sheet showing the name of the sub - contractors and state whether or not those entities have
employees. If the sub - contractors have employees, they must provide their workers' comp. policy number.
I am an employer that is providing workers' compensation insurance for my employees. Below is the policy and job site
information,
Insurance Company Name: , j
Policy # or Self -ins. Lic. #: Expiration Date: l / l / 2 0
Job Site Address: / M /9 1(0,- ' City /State /Zip: / ' / j ,A 19 4 -
Attach a copy of the workers' compensation policy declaration page (showing the policy number and expiration date).
Failure to secure coverage as required under Section 25A of MGL c. 152 can lead to the imposition of criminal penalties of a
fine up to $1,500.00 and/or one -year imprisonment, as well as civil penalties in the form of a STOP WORK ORDER and a fine
of up to $250.00 a day against the violator. Be advised that a copy of this statement may be forwarded to the Office of
Investigations of the DIA for insurance coverage verification.
I do hereby certify under he pa' s a d penalti. /f perjury that the information provided above is true and correct.
Signature: �7 Date:
6i
Phone #: 3
Official use only. Do not write in this area, to be completed by city or town officiaL
- City or Town: Permit/License #
Issuing Authority (circle one):
1. Board of Health 2. Building Department 3. City/Town Clerk 4. Electrical Inspector 5. Plumbing Inspector
6. Other
Contact Person: Phone #:
Version1.7 Commercial Building Permit May 15, 2000
.. .
SECTION 10- STRUCTURAL PEER REVIEW (780 CMR 110.11)
...,-"
Independent Structural Engineering Structural Peer Review Required • Yes 0 No
SECTION 11 - OWNER AUTHORIZATION - TO BE COMPLETED WHEN
OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT
, .
i ,L(
I, v , _ , as Owner of the subject property
hereby authorize ,M5 ,& AvL
' act on my behalf, • all m.. -rs relati - . work authorized by this building permit application.
Signature Owner Date
........................ " 1 „_ _________, „„,_________ , as Owner/Authorized
Agent hereby declare that the statements and information on the foregoing application are true and accurate, to the best of my knowledge
lc and belief.
I Signed under the p ) s and penalties otperica , _
Print Name /7
7
2, /2_ ...,..,......___ ...,„.„., „._,....„.,.... ,..,. ,,, „,.
Signature of Owner/Ag nt Date
SECTION 12 - CONSTRUCTION SERVICES
10.1 Licensed Construction Supervisor: Not Applicable 0
Name of License Holder
' — --- --- A- 4 " :4--* .— – ---7 ,
License Number
1 -4 *
5
Address Expiration Date
, V
(212 /
6 * I 4' 1
(
Signature Telephone
SECTION 13 -WORKERS COMPENSATION INSURANCE AFFIDAVIT (M.G.L c. 152, § 25C(6))
Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result
in the denial of the issuance of the buil • g permit.
Signed Affidavit Attached Yes No 0
Version1.7 Commercial Building Permit May 15, 2000
.o
SECTION 9- PROFESSIONAL DESIGN AND CONSTRUCTION;ISERVICES - FOR BUILDINGS AND STRUCTURES SUBJECT TO
CONSTRUCTION CONTROL PURSUANT TO 780 CMR (CONTAINING MORE THAN 35,000 C.F. OF EN„LOSED SPACE)
9.1 Registered Architect:
O v",. � Not Applicable El
______ ____ _ ..._ Name (Registrant):
( q C. PLEAS A T S ! _.NOIZIMPdt.PTIN ...1",P1�_.._ Registration Number
Address _ ___ 1 2
Tv-VA d r e r n S O 6 , % ""� Expiration Date
Signatur �I 7v Telephon ' e T
9.2 Registered Professional Engineer(s):
Name Area of Responsibility
Address Registration Number
Signature Telephone Expiration Date
Name Area of Responsibility
Address Registration N
Signature Telephone Expiration Date
Name Area of Responsibility
Address Registration Number
Signature Telephone Expiration Date
Name Area of Responsibility
Address Registration Number
Signature Telephone Expiration Date
9.3 General Contractor
..._____. ...._ ,._._m Not Applicable ❑
Company Name:
Responsible In Charge of Construction
Address
Signature Telephone
Version1.7 Commercial Building Permit May 15, 2000
8. NORTHAMPTON ZONING
Existing Proposed ` Required by Zoning
This column to Se filled in by
Building Department
Lot Size
Frontage _..,. _ _ -..._. _ _ .. ............. .. ..._..
Setbacks Front
Side L. __.__ R.'_ __ L .... _, R
Rear -----
Building Height
Bldg. Square Footage
Open Space Footage
(Lot area minus bldg & paved
parking)
# of Parking Spaces
Fill:
(volume & Location)
A. Has a Special Permit /Variance /Finding ever been issued for /on the site?
NO Q DONT KNOW ® YES 0
IF YES, date issued:
IF YES: Was the permit recorded at the Registry of Deeds?
NO 0 DONT KNOW 0 YES 0
IF YES: enter Book ` Page and /or Document #
B. Does the site contain a brook, body of water or wetlands? NO ® DONT KNOW (3 YES 0
IF YES, has a permit been or need to be obtained from the Conservation Commission?
Needs to be obtained 0 Obtained 0 , Date Issued:
Do any signs exist on the property? YES NO 0
IF YES, describe size, type and location: IsiO G RAOG 1 t
D. Are there any proposed changes to or additions of signs intended for the property ? YES 0 NO
IF YES, describe size, type and location:
E. Will the construction activity disturb (clearing, grading, excavation, or filling) over 1 acre or is it part of a common plan
that will disturb over 1 acre? YES 0 NO 0
IF YES, then a Northampton Storm Water Management Permit from the DPW is required.
Version1.7 Commercial Building Permit May 15, 2000
SECTION 4- CONSTRUCTION SERVICES FOR PROJECTS LESS THAN 35,000
�
CUBIC FEET OF ENCLOSED SPACE ,
Interior Alterations 21 Existing Wall Signs ❑ Demolition E Repairs 8 Additions ❑ Accessory Buildng ❑
Exterior Alteration ❑ Existing Ground Sign ❑ New Signs ❑ Roofing ❑ Change of Use ❑ Other ❑
Brief Description Enter a brief description here. _ __,._ ; 1
Of Proposed Work i ea. l0 / 2 - REvo VR T low To (EN
SECTION 5 - USE GROUP AND CONSTRUCTION TYPE
USE GROUP (Check as applicable) CONSTRUCTION TYPE
A Assembly El A -1 ❑ A -2 ❑ A -3 0 1A I El
A-4 ❑ A -5 ❑ 1B ❑
B Business ® 2A ❑
E Educational ❑ 2B - ❑
F Factory ❑ F -1 ❑ F -2 ❑ 2C ❑
H High Hazard ❑ 3A ❑
1 Institutional ❑ 1 -1 ❑ 1 -2 ❑ 1-3 ❑ 3B g
M Mercantile ❑ 4 ❑
R Residential ❑ R -1 ❑ R -2 ❑ R -3 ❑ 5A ❑
S Storage ❑ S -1 ❑ S -2 ❑ 5B ( ❑
U Utility ❑ Specify: ' ._ .. ___.._. .
_ _ ____
M Mixed Use ❑ Specify da._e and
S Special Use ❑ Specify
COMPLETE THIS SECTION IF EXISTING BUILDING UNDERGOING RENOVATIONS, ADDITIONS AND/OR CHANGE IN USE
Existing Use Group: __. ,_0,__. _____ _.. Proposed Use Group: _... _______._____..___ __________ ._____ ._
Existing Hazard Index 780 CMR 34): , __ _.
.__ --- _ Proposed Hazard Index 780 CMR 34): ',_.____ ____ _ ___,, -_ ._., __.
SECTION 6 BUILDING HEIGHT AND AREA
BUILDING AREA EXISTING PROPOSED NEW CONSTRUCTION OFFICE USE ONLY
Floor Area per Floor (sf)
_., 1 st;
1s _
2na ' � 2 (e `_ O J A 1 - e P
3rd 3 - -- Spirc,E
..
_
Total Area (sf) Total Proposed New Constructionisf)
IV 0 GHQ 4.s.S ........_. J ..._.
Total Height (ft)
5" If T ►N,(p_.__.
Total Height ft
o n- f-16160 % -
7. Water Supply (M.G.L. c. 40, § 54) 7.1 Flood Zone Information: 7.3 Sewa a Disposal System:
Public Private ❑ Zone _ Outside Flood Zone Municipa On site disposal system
t al(toCf-
Version1.7 Commercial Building Permit May 15, 2000
Depar u s
7 5 2x�� - �`��� �,� �# s �`� t �`� �^ �
ECEIVED City of Northampton state of r�erit}i� ,t g, v OV V , `` .
B Department CgurbG�E3nyewaPert
- 212 Main Street Sewe`rls5 ilffy
3 Room 100 tlitaterMt11�tarfafllit �f
Northampton, MA 01060 uva Sei?s crf truct0 6($ 4 z 0 .!, :
OF THAMP70N MA ING INSPECT1015 h°n 413 - 587 -1240 Fax 413 - 587 -1272 P l o t/ S it e Pl a
p )s~
THAbtP �:,a
Oth Sp eefy x i.
APPLICATION TO CONSTRUCT, REPAIR, RENOVATE, CHANGE THE USE OR OCCUPANCY OF, OR DEMOLISH ANY BUILDING
OTHER THAN A ONE OR TWO FAMILY DWELLING
SECTION 1 SITE INFORMATION
1.1 Property Address:
This section to be completed by office
/So MAIN 5 7 Noll 71.1 firm p f ont My ; Map Lot Unit-
. Sv 6 it 0 210 = Zone Overlay District
Elm St. District' CB District
SECTION 2 - PROPERTY OWNERSHIP /AUTHORIZED AGENT
2.1 Owner of Record:
\fi r ai ., M.__! (s,r_T '' 2 ._._ . .. ' "/ ..' J .;e.F 1.e' 3/0 , ./<'.- 14 ‘4-1 ,44 '' 411
Name (Print) Current Mailing Address:
T O 1 3V 7- lc-I__ x_liz"
Signature IAA 'f Telephone
2.2 Authoriz __A__,..1.2!..:____ m W _ 7 ,......._ ;4 ___,______ , ..... A --...--,.......... ; , ;n _..- # ... .... ,__, --.. )4.7,, i ..
A K Name (Pri ) Cu rrent Mai ij Address
C. Signature Telephone
SECTION 3 - ESTIMATED CONSTRUCTION COSTS •
Item Estimated Cost (Dollars) to be Official Use Only
completed by permit applicant
1. Building �1 (a) Building Permit Fee
2. Electrical �� v (b) Estimated Total Cost of
€ Construction from (6) _. _..__. ._
3. Plumbing _...,, Building Permit Fee
4. Mechanical (HVAC) ......:......_........_._.. ___.., ...._._.., ___ ;
5. Fire Protection
0e) - _ . _.. ___.. . ._ „
6. Total= (1 +2 +3 +4 +5) Z- I od1 Check Number � Sice
53l
This. Section For Official Use Only
Building Permit Number Date.
. Issued •
Signature:
•
Building Commissioner /inspector of Buildings Date
File # BP- 2012 -0953
APPLICANT /CONTACT PERSON HOWARD PAUL
ADDRESS /PHONE 355 MIDDLE ST AMHERST (413) 253 -3698
PROPERTY LOCATION 150 MAIN ST
MAP 32C PARCEL 001 001 ZONE CB(100)/
THIS SECTION FOR OFFICIAL USE ONLY:
PERMIT APPLICATION CHECKLIST b
ENCLOSED REQUIRED DATE . 0
6 .3
ZONING FORM FILLED OUT d 1
Fee Paid
Building Permit Filled out
Fee Paid 5-3 918Q I 1 C
(� �'$
Typeof Construction: RENOVATE INTERIOR TENANT SPACE SUITE 270
New Construction Air
Non Structural interior renovations �/
Addition to Existing ,
Accessory Structure 1
Building Plans Included: G V
Owner/ Statement or License 59242 /J �0
3 sets of Plans / Plot Plan /� lll..���°0°
THE FO LOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON
INF ATION PRESENTED:
Approved Additional permits required (see below)
PLANNING BOARD PERMIT REQUIRED UNDER:§
Intermediate Project: Site Plan AND /OR Special Permit With Site Plan
Major Project: Site Plan AND /OR Special Permit With Site Plan
ZONING BOARD PERMIT REQUIRED UNDER: §
Finding Special Permit Variance*
Received & Recorded at Registry of Deeds Proof Enclosed
Other Permits Required:
Curb Cut from DPW Water Availability Sewer Availability
Septic Approval Board of Health Well Water Potability Board of Health
Permit from Conservation Commission Permit from CB Architecture Committee
Permit from Elm Street Commission _ Permit DPW Storm Water Management
/11111�--�oli;ton D y
Sig . e of B ' ding fficia Date
Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning
requirements and obtain all required permits from Board of Health, Conservation Commission, Department
of public works and other applicable permit granting authorities.
* Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of
Planning & Development for more information.
150 MAIN ST- SUITE 270 BP- 2012 -0953
GIS #: COMMONWEALTH OF MASSACHUSETTS
Map:Block: 32C - 001 CITY OF NORTHAMPTON
Lot: -001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS
Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A)
Category: renovation BUILDING PERMIT
Permit # BP- 2012 -0953
Project # JS- 2012- 001659
Est. Cost: $25000.00
Fee: $150.00 PERMISSION IS HEREBY GRANTED TO:
Const. Class: Contractor: License:
Use Group: HOWARD PAUL 59242
Lot Size(sq. ft.): 16683.48 Owner: THORNES MARKETPLACE LLC C/O HPMG
Zoning: CB(100)/ Applicant: HOWARD PAUL
AT: 150 MAIN ST- SUITE 270
Applicant Address: Phone: Insurance:
355 MIDDLE ST (413) 253 -3698
AMHERSTMA01002 ISSUED ON:5/10/2012 0:00:00
TO PERFORM THE FOLLOWING WORK: RENOVATE INTERIOR TENANT SPACE SUITE
270 (excluding windows pending additional info)
POST THIS CARD SO IT IS VISIBLE FROM THE STREET
Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector
Underground: Service: Meter:
Footings:
Rough: Rough: House # Foundation:
Driveway Final:
Final: Final:
Rough Frame:
Gas: Fire Department Fireplace /Chimney:
Rough: Oil: Insulation:
Final: Smoke: Final:
THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF
ANY OF ITS RULES AND REGULATIONS.
Certificate of Occupancy Signature:
FeeType: Date Paid: Amount:
Building 5/10/2012 0:00:00 $150.00
212 Main Street, Phone (413) 587 -1240, Fax: (413) 587 -1272
Louis Hasbrouck — Building Commissioner